Detroit Radiant Products DSC series Скачать руководство пользователя страница 17

17

16

DSC 

Series

2.0

 Installation

 

 Electrical Requirements

Electrical Requirements

All field wiring to the patio heater must be done in accordance with the national, state, provincial, local 
codes and the guidelines in this manual. In the United States, refer to the most current revisions to the 
Electrical Code ANSI/NFPA 70 and in Canada refer to the most current revisions of the Canadian 
Electrical Code CSA C22.1 Part 1. The unit must be electrically grounded according to these codes.

This patio heater system is designed to operate on an external 24VAC electrical system. Provide only 
24VAC with a NEC Class 2 transformer to the control wires inside the controls compartment. Use at least 
18 AWG Solid core thermostat type wire that has an adequate capacity and temperature rating for the 
total load. Never locate the transformer inside the controls compartment.

Installing the control wire

Each heater includes a rubber grommet to allow 
for control wire to be brought into the unit with a 
water resistant seal. Feed the control wire 
through the grommet, piercing the rubber with 
the wire. Ensure enough wire length is available 
to make the proper connections. Tie the control 
wire into a loose knot, as shown in Figure 2.6. 
Ensure knot is loose enough to not cause any 
damage to the wire. This will allow for a strain 
relief for the connections to the heater.

Wiring: 

From the control wire, connect the 

24VAC to the blue wire (labeled “24VAC”) inside 
the control compartment. Then connect the 
Common from the control wire to the green wire 
(labeled “Common”). See Fig 2.8, page 18.

Controls Operation

This patio heater was designed for use in an outdoor environment. Therefore, controlling the heater by 
use of a thermostat may not be the best means of temperature control. In an outdoor application, the air 
temperature may not increase and never satisfy the thermostat. The preferred control device when 
operating this heater in an outdoor area is a switching or timer device. 

In an application where there are several wind breaks or a partially enclosed area, a thermostat can be 
used.

NOTICE

The power supply to the heater must be /-5% of the voltage rating as indicated on the rating plate 
of the appliance. If input power does not meet these specifications, contact your utility company.

WARNING

!

Incorrect or improper wiring may result in shock, injury or death. Field wiring to the heater 
must be connected and grounded in accordance with national, state, provincial, local codes 
and to the guidelines in this manual. Refer to the most current revisions to the ANSI/NFPA 
70 Standard.

Figure 2.6 

 Control Wire Installation

Loose Knot in 

Control Wire

Control Wire 

Connections

Содержание DSC series

Страница 1: ...d for use shall not be stored in the vicinity of this or any other appliance Maintain clearance to combustibles at all times For outdoor use only This heater is not approved for use in any indoor residential application This includes but is not limited to attached garages solarium living quarters etc Installation in residential indoor spaces may result in property damage asphyxiation serious injur...

Страница 2: ...Installation 9 Design 9 Heater Mounting 10 Recommended Mounting Heights 11 Gas Supply 13 Gas Connection 14 Leak Testing 16 Electrical Requirements 17 Wiring Diagrams 18 Ventilation 19 3 0 Operation 20 Sequence of Operation 20 4 0 Maintenance 21 Periodic Maintenance 21 Service Access Panel Removal 22 Troubleshooting Guide 23 Maintenance Log 24 5 0 Parts 26 6 0 Limited Warranty 28 ...

Страница 3: ...de heated comfort in an outdoor environment When properly integrated into a patio design the heaters generally increase the comfort levels Outdoor Residential This heater may only be used in outdoor residential applications and is NOT approved for use in any indoor residential application This includes but not limited to attached garages living quarters solarium etc Consult the local fire marshal ...

Страница 4: ...ld be inspected before use and at least annually by a qualified service person More frequent cleaning may be required as necessary It is imperative that the control compartment air passage ways and burner of the heater are kept clean 1 0 Safety Clearance to Combustibles Clearance to Combustibles Gas and electrical lines Combustible and explosive materials Chemical storage areas Areas of high chemi...

Страница 5: ...quire the heater to be mounted at a distance in excess of the published clearances to combustibles Contact the factory or the building material manufacturer for additional information Model No BTU h Voltage Mounting Angle Sides Back Top Below Ends Front DSC 31 31 000 24 VAC 0 18 N A 13 48 12 N A 30 N A 18 18 40 12 36 DSC 34 34 000 24 VAC 0 18 N A 13 48 12 N A 30 N A 18 18 40 12 36 SIDE VIEW End En...

Страница 6: ...g or other objects High Altitude The installation of this heater is approved without modifications for elevations up to 2 000 ft above MSL sea level Contact Detroit Radiant Products Company for installations above these elevations Gas Connection To ensure your safety and to comply with the terms of the warranty all units must be installed in accordance with these instructions Under no circumstance...

Страница 7: ...eater must be installed in accordance with the requirements set forth in this manual and with the NFPA 54 ANSI Z223 1 National Fuel Gas Code latest edition See ventilation requirements on page 19 Re Verber Ray units comply or are certified by one or more of the following organizations or standards CSA International Requirement CSA 2 37 American National Standards Institute ANSI Z83 26 Intertek ETL...

Страница 8: ...pictured below In locations used for the storage of combustible materials signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to combustibles Signs must either be posted adjacent to the heater device or in the absence of such control in a prominent location Figure 1 2 Heater Safety Label Locations 1 0 Safety Safety Signs and L...

Страница 9: ...es must be maintained at all times See Chart 1 1 on page 5 The infrared patio heaters may be laid out in a number of configurations depending on the structures constraints of the application heating requirements and therefore the basic recommendations of installation The minimum mounting height for all Re Verber Ray Patio Heaters is 6 5 feet above the finished floor The heater must always be opera...

Страница 10: ...from horizontal Figure 2 1 Heater Dimensions Optional Mounting Kit Optional adjustable mounting kits and brackets are available for the Patio Heater Refer to the insert that was packaged with the mounting brackets for complete installation instructions WARNING Improper suspension of the infrared heater may result in collapse and persons being crushed Always suspend from a permanent part of the bui...

Страница 11: ...nting Bracket 0 30 End End NOTE This chart is provided as a guideline Actual conditions dictate variances from this data Recommended Mounting Heights WARNING Heater must be installed at least 6 5 feet above the finished floor BTU h Recommended Mounting Height Approximate Coverage Area Approx Coverage sq ft 31 000 8 0 to 12 0 8 x 8 64 sq ft 34 000 8 6 to 13 0 9 x 9 81 sq ft ...

Страница 12: ...or Check that it is securely attached 4 Attach heater to turnbuckle Adjust turnbuckle until the heater is level and equal weight distribution is achieved Threaded rod must be straight up and down do not install threaded rod at an angle Figure 2 3 Heater Mounting DSC Series 2 0 Installation Heater Mounting Optional Mounting bracket attached to ceiling Optional Mounting bracket attached to wall 0 Mo...

Страница 13: ... other gas appliances being connected to the supply line Check that the main gas supply line is of proper diameter to supply the required fuel pressures If utilizing used pipe verify that its condition is clean and comparable to a new pipe Test all gas supply lines in accordance with local codes The gas outlet must be in the same space as the appliance installation and must be accessible It may no...

Страница 14: ...three inches long Ideally the trap would be installed as close as possible to the shut off Chart 2 2 Gas Consumption and Manifold Pressure Inches W C To connect the gas Pressure Equivalents 1 inch W C equals 058 oz sq in equals 2 49 Mbar Model No Input Manifold Pressure Minimum Inlet Pressure Maximum Inlet Pressure Gas Consumption CFH Gallons per Hour Orifice Size DSC 31N 31 000 6 0 W C 7 0 W C 14...

Страница 15: ...re exceeds 14 inches W C Figure 2 5 Gas Connection End View shown installed from below WARNING Failure to disconnect the electricity to the heater before disconnecting the gas supply may result in explosion fire property damage injury or death To disconnect the gas 1 Disconnect the power to the heater 2 Turn off the gas supply to the heater and bleed the gas line 3 Using two wrenches slowly loosen...

Страница 16: ... unit s gas controls must be isolated from the supply pipe Close the field installed manuals shut off valve disconnect the supply line to the unit and temporarily cap the supply line for testing purposes 2 0 Installation Gas Supply Leak Testing WARNING Gas pressures to the appliance controls must never exceed 14 inches W C 1 2 PSI Supply pressures greater than 14 inches W C can damage the controls...

Страница 17: ... knot is loose enough to not cause any damage to the wire This will allow for a strain relief for the connections to the heater Wiring From the control wire connect the 24VAC to the blue wire labeled 24VAC inside the control compartment Then connect the Common from the control wire to the green wire labeled Common See Fig 2 8 page 18 Controls Operation This patio heater was designed for use in an ...

Страница 18: ... Draw 0 65 Amp Running Amp Draw 0 48 Amp Field Wiring 1 24 VAC 20VA transformer 8 Amp per heater is required supplied by installer 2 Maintain electrical polarity when hooking up multiple heaters 3 Allow heaters to be switched by zones for heating flexibility 4 Do not attempt to install transformer inside of heater SPARK SPARK IGNITION MODULE SPARK SENSE GROUND VALVE THERMOSTAT VALVE ...

Страница 19: ...complished by either gravity or mechanical means Mechanical exhausters are preferred and typically mounted at high points on the roof over where stagnant air accumulates inside For a flat roof considerations of prevailing winds high and low pressure areas and distribution of air movement must be taken into consideration when locating exhausters Best air distribution is accomplished by using a numb...

Страница 20: ...s Once the flame on the burner is established the ignition module will continuously monitor the flame The heater will continue to run as long as there is 24VAC present in the call for heat If the heater does not light on the first trial the heater will attempt two more ignitions prior to going into a lockout mode Running Circuit After ignition the flame rod monitors the flame As long as a flame is...

Страница 21: ...sure testing of the gas supply piping system Cleaning the main burner 1 Use an air hose to blow any accumulated dust and or dirt off the heater Air hose pressure should not exceed 30 psi 2 Pass the air hose over the entire exposed area of the ceramic A distance of 2 to 4 from the unit is recommended 3 Place the air hose outlet into the venturi tube and allow the air to flow for approximately one m...

Страница 22: ...e face to rotate open towards the component side of unit and remove service access panel Failure to support the service access panel during removal can result in damage to the piece and or uncontrolled dropping of the panel possibly causing injury Figure 4 1 Service Access Panel Removal WARNING Detroit Radiant Products Company makes every possible effort to remove sharp edges however caution shoul...

Страница 23: ...ection Check connections Tighten as necessary Heater cycles repeatedly Heater located in drafty area Low gas pressure Thermostat located in drafty area Defective flame electrode or circuit board Relocate or shield from draft See Section 2 0 Gas Supply Relocate thermostat Replace electrode and or circuit board No spark no ignition Lack of 24V incoming voltage Open high voltage wire Improper electro...

Страница 24: ...24 DSC Series 4 0 Maintenance Maintenance Log Date Maintenance Performed Replacement Parts Required Maintenance Log ...

Страница 25: ...25 DSC Series 4 0 Maintenance Notes Notes ...

Страница 26: ...5 0 Parts Figure 5 1 Heater Components 1198 1298 1110 1198 1298 1104 1143 1142 1147 1197 1197 1140 1141 1137 1151 1153 1134 1155 1152 1170 1123 1106 1178 1117 1157 1172 1120 1121 1122 1174 1148 1146 1149 1144 1101 1105 1112 1150 1111 1113 1124 ...

Страница 27: ... 1134 In Line Fuse PH 1137 Thermostat Wire Grommet PH 1140 Gas Valve Natural Gas PH 1141 Gas Valve Propane PH 1142 3 Gas Pipe PH 1143 4 Gas Pipe PH 1144 Gas Orifice Specify Model PH 1146 Coupler Natural Gas Only PH 1147 Rubber Inlet Grommet PH 1148 1 2 to 1 8 NPT Adapter PH 1149 Air Metering Washer Natural Gas Only PH 1150 Electrode PH 1151 Circuit Board PH 1152 Circuit Board Wiring Harness PH 115...

Страница 28: ...formation and illustrations are for the sole purpose of identification and do not express or imply a warranty that the products are merchantable or fit for a particular purpose or that the products will necessarily conform to the illustrations or descriptions Except as provided below no warranty or affirmation of fact expressed or implied other than as stated in the LIMITED WARRANTY above is made ...

Отзывы: