STEP 14:
COVER INSTALLATIONS
DEVICE OPERATION TROUBLESHOOTING
Device not latching
when door closes
Latches release, but pushpad
will not fully depress
Latches are not releasing when
pushpad is fully depressed
Bottom bolt is not properly aligned with bottom strike hole.
Top strike insert is not installed or not correctly aligned with
the holdback.
Through fasteners for trim (if applicable) are interfering with
internal centerlift assembly.
Rods improperly adjusted
Device centercase lift finger not inserted properly into
centerlift assembly.
Top adjustment screw is adjusted too far in the retracted
direction (CCW).
Device centercase lift finger not inserted properly into
centerlift assembly.
Top adjustment screw is adjusted too far in the extended
direction (CW).
Bottom adjustment screw is adjusted too far in the extended
direction (CCW).
Modify bottom strike hole for fit.
Install and/or position strike insert per instructions.
Loosen and re-position through screws to clear.
Adjust rods per instructions.
Remove device and re-install per instructions.
Remove device from backplate and re-install with
lift finger correctly inserted.
Rotate top adjustment screw in the extended
direction (CW) per FINE LATCH ADJUSTMENT
procedure.
Remove device from backplate and re-install with
lift finger correctly inserted.
Rotate top adjustment screw in the retracted
direction (CCW) per FINE LATCH ADJUSTMENT
procedure.
Rotate bottom adjustment screw in the retracted
direction (CW) per FINE LATCH ADJUSTMENT
procedure.
SOLUTION
POSSIBLE CAUSE
SYMPTOM
EC2
flush
endcap shown
104924 Page 19
INSTALL
centercase cover with
(4) flat head screws
IMPORTANT
TIGHTEN screws
at this end first
INSTALL
endcap with
(2) flat head screws
10-32 x 5/16"
6-32 x 3/8
14a
14b