Model FP-700
FP-700 Instruction Manual
Rev. 5.1
Page 5 of 46
2.
Installation
2.1
Operational Guidelines for Safe Use – HazLoc Certifications
1.
It is recommended for end-users to read and reference the procedures described in IEC 60079-29-2 for
guidance on the proper installation, operation, and servicing of this type of combustible gas detectors.
2.
Install sensor only in areas with classifications matching with those described on the ATEX approval
label. Follow all warnings listed on the label.
3.
Detector is performance tested to ANSI/UL 12.13.01:2013 Performance Requirements of Detectors for
Flammable Gases. Performance Testing was completed by CSA Group on March 28, 2018. This Model
FP-700 detector is performance tested only for methane gas measurement in the 0-100 % LEL (0-5%
by volume) range and with use of Accessory PN 613-120000-700 Sensor Splashguard with integral Cal
Port. There are no special conditions for use other than what is specified here in Section 2.1 of
Instruction Manual.
Figure 8
HazLoc Certification Approval Label
4.
Ensure that the sensor is properly threaded into a suitable flameproof rated junction box with a
downward pointing female ¾” NPT threaded connection. The sensor should be threaded up at least 5
full turns until tight, with the LED display facing forward (+/-15°). Minimize use of Teflon Tape, or
any type of non-conductive pipe thread coating on the NPT threaded connection.
5.
A good ground connection should be verified between the sensor’s metal enclosure and the junction
box. If a good ground connection is not made, the sensor can be grounded to the junction box using the
sensor’s external ground lug. Also verify a good ground connection between the junction box and earth
ground. Installer shall use ring terminal to make connection to earth ground to be secured by screw and
lock washer on sensor housing.
6.
Ensure that the Housing Bottom and plug-in sensor are installed during operation. The Housing Bottom
should be threaded tightly to the Intelligent Transmitter Module. The locking setscrew (M3 x 0.6 6g6h
Stainless Steel Allen set screw cup point with yield strength of greater than 40,000 PSI, typical 80,000
PSI) should then be tightened down to keep the Housing Bottom from being inadvertently removed or
from becoming loose under vibration. The locking setscrew ensures that Housing Bottom is only
removable by authorized personnel with the use of special tools. A M1.5 Allen Wrench is required. If
screw requires replacement, only an identical screw may be used.
7.
Removal of the Housing Bottom violates the Ex d protection method and hence power must be removed
from the sensor prior to its safe removal.