MAINTENANCE

 

WARNING

To avoid a potential electrostatic discharge 
(ESD), do not wipe or rub the surface of the 
U5015 sensor module.

NOTE

The U5015 Smoke Detector contains no 
user serviceable components and should 
never be opened.  The U5015 wiring 
compartment is the only part of the smoke 
detector that should be opened by the user 
in the field.

ROUTINE INSPECTION

Regularly scheduled maintenance is not 

required, however, the U5015 cover and smoke 

chamber should be inspected periodically when 

detectors are located in abnormally dirty or dusty 

environments, to ensure the smoke chamber is 

not blocked by dirt or debris

The smoke detector can be tested using the 

same methods employed for any photo-electric 

detector.  Det-Tronics recommends using a 

test aerosol smoke dispenser for periodic 

maintenance of the detector. 

Содержание SmokeWatch U5015

Страница 1: ...3 5 95 8723 Instructions Det Tronics SmokeWatch Explosion Proof Smoke Detector U5015 ...

Страница 2: ...Locations 5 Protection Against Moisture Damage 6 Power Supply Requirements 6 Transport Cover 6 Mounting Location Options 6 Mount the Detector 7 Wiring Cable Requirements 7 Jumper 7 Wiring Procedure 8 MAINTENANCE 9 Routine Inspection 9 DEVICE REPAIR AND RETURN 13 ORDERING INFORMATION 13 Spare Parts 13 Accessories 13 U5015 Model Matrix 13 APPENDIX A FM APPROVAL DESCRIPTION 14 APPENDIX B CSA APPROVAL...

Страница 3: ...fe and allows live maintenance while under power without de classifying the hazardous area The integrated junction box is available in a variety of port configurations for simplified wiring and installation See Figure 1 for all the U5015 Smoke Detector components FEATURES FM Approved for use in Class I Division 1 hazardous locations FM Approved for smoke detection performance IECEx Zone approved T...

Страница 4: ...30 Vdc The auxiliary relay has normally open normally closed contacts and normally de energized operation TEMPERATURE RANGE Operating 20 C to 65 C 4 F to 149 F Storage 55 C to 70 C 67 F to 158 F HUMIDITY RANGE 5 to 95 relative humidity INGRESS PROTECTION IP44 Note Applicable to ceiling mount only CURRENT OUTPUT 0 20 mA 0 3 mA dc current with maximum loop resistance of 300 ohms from 12 17 9 Vdc 500...

Страница 5: ...n contacts and normally energized operation The auxiliary relay has a single set of terminals and normally open normally closed contacts and normally de energized operation IMPORTANT The auxiliary relay functions as pre alarm 0 to 20 mA Output The U5015 provides a 0 to 20 mA dc current for transmitting detector status information to other devices The circuit is wired in a non isolated configuratio...

Страница 6: ...mal operation the detector performs the Self Test function automatically in the background once per second During the test detection is not interrupted and no indication is given if the test passed If the test fails a critical fault will occur If degradation is present and approaching critical levels an advisory fault will occur MANUAL SELF TEST The Manual Self Test function will immediately check...

Страница 7: ...resent INSTALLATION WARNING All entries must contain appropriately rated plugs or fittings It is required that each plug or fitting be wrench tightened to an appropriate installation torque and meet the minimum thread engagement requirements per the applicable local standards codes and practices in order to retain the defined ratings PTFE sealant or equivalent should be used on NPT threads NOTE De...

Страница 8: ...ower supply with adequate capability for the calculated load Ensure that the selected power supply provides sufficient regulated and filtered output power for the entire system If a back up power system is required a float type battery charging system is recommended If an existing source of power is being used verify that system requirements are met TRANSPORT COVER The Transport Cover see Figure 4...

Страница 9: ... are rated at 20 C greater than the maximum ambient temperature NOTE In applications where the wiring is installed in conduit dedicated conduit is recommended Avoid low frequency high voltage and non signaling conductors to prevent nuisance EMI problems JUMPER Depending on the wiring option that is used jumpers may be required See Table 3 for the Jumper Usage Guide and Figures 12 to 15 for wiring ...

Страница 10: ... to the appropriate terminals Figure 9 shows the wiring terminals Figure 10 shows the ground lug locations Figures 12 and 13 show wiring for single detector configurations Figures 14 and 15 show wiring for multiple detector configurations 4 Re install the assembly Use the alignment guide see Figure 11 to align the retaining ring with the junction box 5 Screw the retaining ring on to the junction b...

Страница 11: ... should be opened by the user in the field ROUTINE INSPECTION Regularly scheduled maintenance is not required however the U5015 cover and smoke chamber should be inspected periodically when detectors are located in abnormally dirty or dusty environments to ensure the smoke chamber is not blocked by dirt or debris The smoke detector can be tested using the same methods employed for any photo electr...

Страница 12: ...95 8723 10 3 5 Figure 12 Single Detector Wiring 0 20 mA used Relays not used Figure 13 Single Detector Wiring 0 20 mA not used Relays used ...

Страница 13: ...11 95 8723 3 5 Figure 14 Multiple Detector Wiring 0 20 mA used Relays not used ...

Страница 14: ...95 8723 12 3 5 Figure 15 Multiple Detector Wiring 0 20 mA not used Relays used ...

Страница 15: ...inside the packaging Please make certain to display the RMA number clearly on the outside of your packaging Shipments received without this RMA number displayed will be refused Pack the unit properly always using sufficient packing material Wherever possible return the product using the original Det Tronics packing materials Where applicable use an antistatic bag as protection from electrostatic d...

Страница 16: ...uipment protection by Flameproof Enclosures d ANSI ISA 60079 11 2014 Explosive atmospheres Part 11 Equipment protection by intrinsic safety i Special Conditions For Safe Use X 1 The U5015 is to be installed in locations where the risk of mechanical damage is low 2 Potential electrostatic charging hazard please see instructions for proper installation 3 All unused device openings must be closed usi...

Страница 17: ... 0 General Requirements C22 2 No 60079 1 2016 Explosive atmospheres Part 1 Equipment protection by flameproof enclosures d C22 2 No 60079 11 2014 Electrical apparatus for explosive gas atmospheres Part 11 Intrinsic Safety i Special Conditions For Safe Use X 1 Field wiring must be in accordance with CEC Part 1 Section 18 2 The enclosure must be bonded to ground according to CEC Part 1 Section 18 3 ...

Страница 18: ...mospheres Equip protection by Intrinsic Safety Special Conditions For Safe Use X 1 The U5015 is to be installed in locations where the risk of mechanical damage is low 2 Potential electrostatic charging hazard please see instructions for proper installation 3 All unused device openings must be closed using a suitably certified plug 4 For field connections use wire rated 20 C greater than maximum a...

Страница 19: ...ICATE OF CONFORMITY TO TP TC 012 2011 No TC RU C US BH02 B 00239 1Exd ia IICT4 IP44 T4 Tamb 20 C to 65 C Declaration of Conformity to TP TC 020 2011 EMC EAЭC No RU д US PA01 B 50006 RUSSIA VNIIPO CERTIFICATE OF CONFORMITY TO TECHNICAL REGULATIONS GOST R 53325 2012 C US цC13 B 00192 ...

Страница 20: ...ice 6901 West 110th Street Minneapolis MN 55438 USA www det tronics com Specifications subject to change without notice All trademarks are the property of their respective owners 2020 Detector Electronics Corporation All rights reserved Det Tronics manufacturing system is certified to ISO 9001 the world s most recognized quality management standard Phone 952 941 5665 Toll free 800 765 3473 Fax 952...

Отзывы: