background image

FINE ALIGNMENT PROCEDURE

The Fine Alignment procedure should be completed
when maximum optical signal strength is required, such
as most outdoor applications and all installation areas
with high levels of optical contamination or fog.

It is necessary to complete the Basic Alignment
procedure before starting the Fine Alignment
procedure.  A handheld HART communication device
such as the intrinsically-safe Emerson Model 375 HART
communicator is required to complete Fine Alignment.

HART Field Communicator Recommendations

• Ensure that the HART communicator is certified for

use in classified areas.

• The HART communication device used for Fine

Alignment must include the OPECL device descriptor
(DD) software menu.  The use of HART
communication devices without the proper DDs may
establish generic mode HART communication, but will
not enable Fine Alignment to be completed.  Refer to
the HART appendix for additional information.

• A  minimum level of understanding with regard to the

operation and navigation of the HART communicator
is required to complete the Fine Alignment procedure.
Please refer to the appropriate HART communicator
instruction manual for basic operating instructions if
required.  Additional information on the use of the
HART communicator is provided within the HART
Appendix in this document.

• For proper HART communication to occur, it is

required that a 250-500 ohm resistive load be present
in the OPECL analog 4-20 mA signal loop output.

Procedure

After completion of the Basic Alignment procedure,
perform the Fine Alignment procedure as follows:

1. Connect the handheld HART communicator to the

receiver module’s onboard HART communication
port.

2. Turn on the HART communicator and check for

OPECL device recognition.  When HART
communication is established, the OPGD Rx Root
menu will be displayed on the Communicator
display screen.

3. From the Root menu, select the Status Menu

(selection #2).

4. From the Status Menu, select the Sensor Information

Menu (selection #3).

5. The Sensor Information Menu will display the

following screen.

6. Observe the Gas Gain level indicated on the Sensor

Information Menu screen.  

7. Adjust the transmitter in both the vertical and

horizontal directions slowly and in small increments
to a position where the Gas Gain level is minimized.

NOTE

Turn the pan-tilt bolts only a fraction of a turn at a
time.

8. Similarly, adjust the receiver in both the vertical and

horizontal directions slowly and in small increments
to a position where the Gas Gain level is minimized.

9. Table 4 can be used as a guideline for new

installations to assess Gas Gain level with proper
alignment.

NOTE

Do not attempt to tighten any threaded adjuster
bolt if the opposing adjuster bolt is tightened hard
against the mounting plate hardware.  It is
necessary to slightly loosen the opposing adjuster
bolt in all cases before attempting to tighten an
adjuster.

NOTE

Adjust the horizontal alignment angle first in small
increments.  After an adjustment is made, wait for
at least 10 seconds for the Gas Gain display level
to stabilize.  Adjust left and/or right, if necessary,
until the correct level is achieved.

19

95-8556

2.1

Distance (m) Standard Range OPECL Long Range OPECL

20

1 - 2

NA

40

2 - 3

NA

60

4

2

80

NA

2-3

100

NA

3

120

NA

3-4

Table 4— Expected Gas Gain Settings for Standard and Long

Range OPECL vs Distance

1)  Active 

XXX

2)  Reference 

XXX

3)  Ratio 

XXX

4)  Gas Gain 

X

5)  Absorption 

XXX

Gas Gain number 
(adjust to minimum level)

Содержание Open Path Eclipse OPECL

Страница 1: ...Infrared Hydrocarbon Gas Detector Open Path Eclipse Model OPECL Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 87...

Страница 2: ...1 Wiring Cable Requirements 11 Power Wiring Size and Maximum Length 12 Optional Relays 12 Wiring Procedure 13 STARTUP 16 ALIGNMENT 16 Overview 16 Basic Alignment Procedure 16 Fine Alignment Procedure...

Страница 3: ...along with mounting fixture hardware Both modules are powered from an external 24 volt DC supply The receiver provides the measurement signal outputs and is furnished with an onboard status indicatio...

Страница 4: ...ture A xenon lamp illuminates the linear detection path from the transmitter to the receiver In the event that the primary lamp fails the back up lamp is brought into service The receiver recognizes t...

Страница 5: ...on via a flashing red color and a HIGH alarm condition via a steady red color The OPECL internal magnetic switch or HART Field Communicator can be used to reset latched alarms A short duration magneti...

Страница 6: ...communicator for system setup commissioning and diagnostics Onboard LED Indicator Indicates normal fault and backup lamp operation status Green indicates normal operation Amber indicates operation in...

Страница 7: ...this output The factory default for full scale 5 LFL meters output is 20 mA MODBUS interfaces also have the ability to calibrate the 4 mA and 20 mA levels FAULT INDICATION Faults and status conditions...

Страница 8: ...or MODBUS communication FAULT RELAY Form C Type NO NC Energized during Normal mode De Energized on Fault or loss of power Contact Rating 5 amperes at 30 VDC Non Latching Operation only not programmab...

Страница 9: ...001 see Appendix B Class I Div 2 Groups A B C D T4 Type 4X CENELEC Standard range and long range models 0539 II 2 G DEMKO 03 ATEX 135898X EEx de ib IIC T5 T5 Tamb 40 C to 60 C IP67 Transmitter Receive...

Страница 10: ...diameter pipe Refer to Figure 3 for mounting dimensions SHIPPING WEIGHT Transmitter with mounting plate 35 pounds 16 kg Receiver with mounting plate 35 pounds 16 kg WARRANTY 3 year limited warranty f...

Страница 11: ...por density and flashpoint should be identified and used to assist in selecting the optimum detector mounting locations within the area The detector must be installed by qualified personnel only follo...

Страница 12: ...longterm outdoor operation in very cold climates is intended extra shielding covers are recommended to prevent accumulation of snow and ice on the windows Deluge and Flooding The modules are rated IP6...

Страница 13: ...source of 24 Vdc power is being utilized verify that system requirements are met NOTE If disconnection of power is required separate disconnect capability must be provided WIRING CABLE REQUIREMENTS A...

Страница 14: ...y the resistance of the wire ohms foot value available in wire manufacturer s specification data sheet 3 Divide by 2 For example Consider an installation using 18 AWG wiring with a power supply provid...

Страница 15: ...g terminal configuration for the OPECL receiver with relays Figures 11 through 14 show the 4 to 20 mA output of the OPECL receiver in various wiring schemes Figure 15 shows the OPECL wired to a Model...

Страница 16: ...N 4 to 20 MA B2051 TOTAL LOOP RESISTANCE 250 OHMS MINIMUM 600 OHMS MAXIMUM Figure 12 Detector Wired for Non Isolated 4 to 20 ma Current Output Sourcing Figure 11 Detector Wired for Non Isolated 4 to 2...

Страница 17: ...Sinking CURRENT OUTPUT CHASSIS GROUND POWER SENSOR EXTERNAL RESET HIGH ALARM HIGH ALARM OC AUX ALARM AUX ALARM OC LOW ALARM LOW ALARM OC FAULT FAULT OC 1 3 4 5 6 7 8 9 10 11 12 13 14 15 16 18 TO 32 VD...

Страница 18: ...g all OPECL systems The following instructions cover the use of the Telescope Alignment Tool 3 Calibration Magnet 4 For installations with module separation distances between 5 and 30 meters a range r...

Страница 19: ...e to dead center on the window of the receiver module Tighten the vertical alignment locking nuts so that no movement will occur 17 95 8556 2 1 VERTICAL ALIGNMENT LOCKING NUTS 2 VERTICAL ADJUSTMENT BO...

Страница 20: ...y performing a zero calibration 15 Perform a zero calibration Refer to Zero Calibration in the Calibration section of this manual Any faults or alarms that may be present as a result of the alignment...

Страница 21: ...eceiver module s onboard HART communication port 2 Turn on the HART communicator and check for OPECL device recognition When HART communication is established the OPGD Rx Root menu will be displayed o...

Страница 22: ...bject such as cardboard until a beam block fault is generated CALIBRATION CALIBRATION OVERVIEW Although routine calibration of the Open Path Eclipse is normally not required the device supports non in...

Страница 23: ...Zero Calibration 1 Apply magnet for 2 seconds minimum to initiate calibration A The onboard LED turns to steady red B The current output decreases to 1 mA 2 When zero calibration is complete A The onb...

Страница 24: ...ipment transportation prepaid to the factory in Minneapolis 22 95 8556 2 1 Fault Condition Corrective Action Low 24 volts 24 vdc operating voltage is out of range Verify proper wiring to the detector...

Страница 25: ...t flange internal 009186 001 Spare Pan Tilt Mounting Kit for one OPECL module only 007907 001 Sun Shield for one module 008925 001 Spare electronics lamp module for OPECL transmitter 008926 001 Spare...

Страница 26: ...priate DDL s for the Open Path Eclipse are included within your Communicator To review the device descriptions programmed into your HART Communicator 1 From the Main menu press to access Offline menu...

Страница 27: ...igh Alarm Level 2 High Alarm Latch 3 Low Alarm Level 4 Low Alarm Latch RTC Menu 1 RTC Menu Setup Menu 1 OPGD Option Menu 2 Hart Output Menu 3 Com 485 Menu 4 Config Flt Output Menu 5 Gas Type Menu 6 Ra...

Страница 28: ...first menu displayed is the OPGD RX Root menu To select any of the 5 menu options shown highlight the desired option using the up down arrow key and then press the right arrow key COMMONLY USED HART...

Страница 29: ...RITTEN UNLESS OTHERWISE SPECIFIED DIMENSION TOLERANCE INCH MM INCH MM REMOVE ALL BURRS BREAK ALL EDGES AND SHARP CORNERS THIS DRAWING AND SPECIFICATION CONTAIN PROPRIETARY INFORMATION AND ANY REPRODUC...

Страница 30: ...Printed in USA Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 8750...

Отзывы: