111826-01F
For more information, visit www.desatech.com
6
AIR FOR COMBUSTION AND
VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfi ned space. When
ventilating to an adjoining unconfi ned space, you must pro vide two
permanent open ings: one within 12" of the ceiling and one within
12" of the fl oor on the wall con nect ing the two spaces (see options
1 and 2, Figure 2). You can also remove door into adjoining room
(see op tion 3, Figure 2). Follow the
National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You
must provide two per ma nent open ings: one within 12" of the ceil-
ing and one within 12" of the fl oor. Connect these items directly to
the outdoors or spaces open to the outdoors. These spaces include
attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation
for required size of ven ti la tion grills or ducts.
IMPORTANT:
Do not provide openings for inlet or outlet air into
attic if attic has a ther mo stat-controlled power vent. Heated air
entering the attic will activate the power vent.
Figure 3 - Ventilation Air from Outdoors
Figure 2 - Ventilation Air from Inside Building
Outlet
Air
Ventilated
Attic
Outlet
Air
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills
Into Adjoining
Room,
Option 1
12"
12"
AIR FOR COMBUSTION AND VENTILATION
Ventilation Air