10
1.2.2 Wall-Mount Humidity and Temperature Sensor
If our dehumidifier was ordered with a wall-mount humidity and temperature sensor,
mount the sensor about five feet above floor, on an interior wall with natural air
circulation. Avoid the following locations:
• Hot spots near concealed heating pipes, warm air ducts, supply register
outlets, or solar radiation.
• Cold spots due to a cold wall or draft from stairwells, doors, windows, or
supply register outlets.
• Dead spots such as behind doors or in corners where room air cannot
circulate freely
Install using 24-16 AWG stranded wire; 18 AWG stranded wire recommended.
Do not run sensor wiring adjacent to, OR in the same conduit as, wires carrying more
than 24 VAC. See manufacturer’s specifications for more details.
1.3
Auxiliary Air Heating Control Wiring
Note:
You must use the Desert Aire CM3540 control system to control or interlock with the
room heating system. This prevents the heater from trying to heat the room while the
dehumidifier is running in cooling mode.
1.3.1 Auxiliary Heating - Dry Contact Closure
The standard Desert Aire CM3540 controller provides a dry contact closure to operate
the auxiliary space heater. The contact closes to energize a heater (may be supplied
by others) which has its own power source.
Install two wires from the thermostat terminal blocks on the heater to the terminals
H1 and H2 in the control panel of the dehumidifier. See your wiring schematic for
connection details.
1.3.2 Auxiliary Heating - Proportional Signal
Desert Aire will provide a proportional 0-10 VDC direct-acting signal to modulate a
heating coil control valve or other auxiliary modulating heater. Most proportional
valves have either three (3) or four (4) terminals for field-installed wiring.
• Four-terminal valves have two terminals for 24 VAC power and two
terminals for the signal input.
• Three-terminal valves have one terminal for the “hot” 24 VAC input, a
second terminal for the “neutral” 24 VAC input and the “negative” signal
input.
The control signal may also be set for reverse-acting or for 2-10 VDC. Contact
Desert Aire Service Department for recommendations or instructions on how these
options can be implemented.
Desert Aire - CM3540 Manual
Содержание CM3540 Series
Страница 2: ...2 ...
Страница 5: ...5 Product Warning for the State of California Desert Aire CM3540 Manual ...
Страница 6: ...6 Desert Aire CM3540 Manual ...
Страница 12: ...12 Desert Aire CM3540 Manual ...
Страница 29: ...29 Figure 28 Figure 29 Figure 30 Desert Aire CM3540 Manual ...
Страница 42: ...42 Figure 53 Figure 54 Figure 55 To return to the SERVICE MENU press the Esc key Desert Aire CM3540 Manual ...
Страница 44: ...44 Desert Aire CM3540 Manual ...
Страница 48: ...48 Figure 60 To return to the Home screen press the Esc key Desert Aire CM3540 Manual ...