INStALLAtION FOR VERtICAL tERMINAtION

Note:

 Vertical restrictor must be installed in all vertical installations.

1.  Determine the route your vertical venting will take. If ceiling 

joists, roof rafters, or other framing will obstruct the venting 

system, consider an offset (see Figure 19) to avoid cutting 

load bearing members. 

Note: 

Pay special attention to these 

installation instructions for required clearances (air space) 

to combustibles when passing through ceilings, walls, roofs, 

enclosures, attic rafters, etc. Do not pack air spaces with insu

-

lation. Also note maximum vertical rise of the venting system 

and any maximum horizontal offset limitations.

2.  Set the fireplace in desired location. Drop a plumb line down 

from the ceiling to the position of the fireplace exit flue. Mark 

the center point where the vent will penetrate the ceiling. Drill 

a small locating hole at this point.

 

Drop a plumb line from the inside of the roof to the locating 

hole in the ceiling. Mark the center point where the vent will 

penetrate the roof. Drill a small locating hole at this point.

VENTING INSTALLATION 

INSTRUCTIONS

Continued

Flat Ceiling Installation

1.  Cut a 10 

3

/

4

" square hole in the ceiling using the locating hole as 

a center point. The opening should be framed to 10 

3

/

4

"x10 

3

/

4

"

 

(27.3 cm x 27.3 cm) inside dimensions, as shown in Figure 9 

on page 8 using framing lumber the same size as the ceiling 

joists. If the area above the ceiling is an insulated ceiling or an 

attic space, nail firestop from the top side. This prevents loose 

insulation from falling into the required clearance space. If the 

area above the ceiling is a living space, install firestop below 

the framed hole. The firestop should be installed with no less 

than three nails per side (see Figure 20).

Figure 19 - Offset with Wall Strap and 45° Elbows

Figure 20 - Installing Firestop

If area above is a living 

space, install firestop 

below framed hole.

If area above is an attic 

space or insulated area, 

install firestop above 

framed hole.

2.  Assemble the desired lengths of pipe and elbows necessary to 

reach from the fireplace flue up through the firestop.  Be sure all 

pipe and elbow connections are fully twist-locked (see Figure 

8, page 8).

3.  Cut a hole in the roof using the locating hole as a center point. 

(Cover any exposed open vent pipes before cutting hole in roof.) 

The 10 

3

/

4

" x 10 

3

/

4

" hole must be measured on the horizontal; 

actual length may be larger depending on the pitch of the roof. 

There must be a 1" clearance from the vent pipe to combustible 

materials. Frame the opening as shown in Figure 9, page 8.

4.  Connect a section of pipe and extend up through the hole.

 

Note:

 If an offset is needed to avoid obstructions, you must 

support the vent pipe every 3 feet. Use wall straps for this 

purpose (see Figure 19). Whenever possible, use 45° elbows 

instead of 90° elbows. The 45° elbow offers less restriction to 

the flow of the flue gases and intake air.

5.  Place the flashing over the pipe section(s) extending through 

the roof. Secure the base of the flashing to the roof and framing 

with roofing nails. Be sure roofing material overlaps the top 

edge of the flashing as shown in Figure 19. There must be a 

1" clearance from the vent pipe to combustible materials.

6.  Continue to add pipe sections until the height of the vent cap 

meets the minimum building code requirements described in 

Figure 7 on page 6.

 Note:

 You must increase vent height for 

steep roof pitches. Nearby trees, adjoining roof lines, steep 

pitched roofs, and other similar factors may cause poor draft 

or down-drafting in high winds. Increasing the vent height may 

solve this problem.

7.  Twist-lock the vent cap onto the last section of vent pipe.

Note:

 If the vent pipe passes through any occupied areas above the 

first floor, including storage spaces and closets, you must enclose 

pipe. You may frame and sheetrock the enclosure with standard 

construction material. Make sure and meet the minimum allow

-

able clearances to combustibles. Do not fill any of the required air 

spaces with insulation.

45° Elbow

Wall Strap

Roof Flashing

Ceiling Firestop

Содержание VV36N Series

Страница 1: ...sale not for purpose of resale from the manufacturer WARNING Iftheinformationinthismanualis not followed exactly a fire or explosion may result causing property damage personal injury or loss of life...

Страница 2: ...tdoors To prevent performance problems do not use pro pane LP fuel tank of less than 100 lbs capacity 3 If you smell gas shut off gas supply do not try to light any appliance do not touch any electric...

Страница 3: ...se are a few facts that can help you understand and enjoy your direct vent fireplace The venting system may be routed to the outside of your home in several ways It may vent through the roof vertical...

Страница 4: ...18 above top of louver opening When locating termination cap it is important to observe the minimum clearances shown in Figure 7 page 6 If recessing into a wall you can avoid extra framing by positio...

Страница 5: ...le mantels may discolor Pre Installation Preparation Continued Figure 4 Framing Clearances for Installation Against an Exterior Wall C B A D E F G Top of Louver Opening 3 2 1 4 5 6 7 Wall A B E F G H...

Страница 6: ...ve paved side walk or a paved driveway located on public property 84 213 3 cm minimum M clearance under veranda porch deck 12 30 5 cm minimum N clearance above a roof shall extend a minimum of 24 61 c...

Страница 7: ...y Installation Precautions Wear gloves and safety glasses for protection Use extreme caution when using ladders or when on roof tops Be aware of electrical wiring locations in walls and ceilings The f...

Страница 8: ...vent will be terminated If the wall being penetrated is constructed of noncombustible material such as masonry block or concrete a 8 1 2 hole with zero clearance is acceptable see Figure 9 WARNING Do...

Страница 9: ...erlap should be a minimum of 11 4 9 Slide wall firestop against interior wall surface and attach with screws provided See Figure 13 for horizontal termination details 10 Place fireplace into position...

Страница 10: ...ap Exterior Portion of Wall Firestop Round Termination Only Round Termination Kit 01491 for V36 V42 Series Kit SDHTRK 58 CHDV Series Horizontal Termination Configurations Figures 14 through 18 show di...

Страница 11: ...l Termination Wall Firestop 90 Elbow 45 Elbow Figure 16 Snorkel Termination Configurations for Below Ground Installation 12 Minimum Adequate Drainage HORIZONTAL SYSTEM INSTALLATION USING TWO 90 ELBOWS...

Страница 12: ...ove is an attic space or insulated area install firestop above framed hole 2 Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop Be sure...

Страница 13: ...e 22 Vertical Venting Configuration Using One 90 Elbow Vertical Round High Wind Termination Shown Note Install restrictor into inner collar of fireplace as shown Venting with Two 90 Elbows Vertical V1...

Страница 14: ...Wind Termination 1 01800 Horizontal Square High Wind Termination 1 01801 14 Snorkel Termination Galvanized 1 01802 36 Snorkel Termination Galvanized 1 DESA Venting Accessories Number Description 0150...

Страница 15: ...l wire terminals are securely attached to ter minals on blower motor and that the screw retaining the green ground wire is tight 5 Mount speed control box to switch bracket by placing the plastic cont...

Страница 16: ...Place control knob provided on shaft see Figure 26 page 15 7 Check to make sure that the power cord is completely clear of the blower wheel and that there are no other foreign objects in blower wheel...

Страница 17: ...ip leg in supply line as shown in Figure 31 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supply and fireplace Locate sediment trap drip leg...

Страница 18: ...Pa 1 Close equipment shutoff valve see Figure 33 2 Pressurize supply piping system by either opening propane LP supply tank valve for propane LPgas fireplace or opening main gas valve located on or ne...

Страница 19: ...wire from TH to TPTH on control valve see Figure 37 6 Connect wires from receiver to TH and TPTH to control valve see Figure 38 7 Replace the switch bracket Figure 36 Attaching Alkaline Battery to Re...

Страница 20: ...Lift up on latches to unlock There are two on top of firebox and two below firebox that hold glass door in place see Figure 41 3 While holding glass door to prevent it from falling and causing injury...

Страница 21: ...3 rear log onto pins on rear of grate as shown in Figure 46 4 Place log 4 crossover log onto pins from both logs 2 and 3 as shown in Figure 47 5 Install rear brick panel first Rest bottom edge of pane...

Страница 22: ...ormance problems 9 Pull ember material apart into pieces no larger than a dime Place these pieces loosely and sparingly directly onto the exposed sec tion of the front burner and along the space betwe...

Страница 23: ...Follow the gas supplier s instructions C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repairit call a qualified...

Страница 24: ...w locked If the fire is on it will be turned off automatically In the locked state the light will not light up when any button is pressed To Unlock press both buttons togetheron hand held remote contr...

Страница 25: ...ontrol etc The keypad is locked in either on or off Press the POWER and LOCK buttons together to turn the unit on or off Operating optional GWMT1 Wall Mounted Thermostat WARNING Do not connect the the...

Страница 26: ...osened Check mechanical supports such as wall straps for rigidity Cleaning and Maintenance WARNING Turn off fireplace and let cool before cleaning CAUTION Youmustkeepcontrolareas burners and circulati...

Страница 27: ...Dirty or partially clogged pilot 5 Thermocouple connection loose at con trol valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by an...

Страница 28: ...from line Have gas line checked by local propane LP or natural gas company 3 Clean burner see Cleaning and Main tenance page 26 or replace burner orifice 1 Adjust the log set so that the flame does no...

Страница 29: ...d 3 Burner flame holes blocked OBSERVED PROBLEM Fireplace produces unwanted odors Fireplace shuts off in use Gas odor even when control knob is in OFF position Gas odor during combustion Dark residue...

Страница 30: ...ay lit burners will have delayed ignition fireplace will not produce specified heat propane LP gas supply might be low propane LP units only You may feel your gas pressure is too low If so contact you...

Страница 31: ...Brass ELKD42B 42 Extruded Brushed Brass ELKD42P 42 Extruded Platinum ELKD42PB 42 Extruded Polished Brass Rolled Louver trim kit Not Shown LT36B 36 Brushed Brass LT36P 36 Platinum LT36PB 36 Polished B...

Страница 32: ...atech com 108861 01F 32 Illustrated Parts Breakdown MODELS V V36N V V36NS V V36NH V V36P V V36PS V V36PH and CHDV36NR 6 7 21 18 19 14 13 2 12 20 8 10 1 4 11 9 15 3 17 16 5 23 2 23 1 23 5 23 4 23 3 23...

Страница 33: ...duit Assembly 1 22 108760 01 108760 01 108760 01 108760 01 Burner Assembly Natural Gas 1 108760 02 108760 02 108760 02 108760 02 Burner Assembly Propane LP Gas 1 23 108032 01 108032 01 108032 01 10803...

Страница 34: ...www desatech com 108861 01F 34 4 3 2 5 6 7 8 9 10 11 12 13 14 15 16 17 1 21 19 20 18 illustrated parts breakdown Burner Assembly Models V V36N V V36NS V V36NH V V36P V V36PS V V36PH and CHDV36NR...

Страница 35: ...Gas 1 14514 Pan Burner Orifice Propane LP Gas 1 6 108084 02 Pilot Assembly Natural Gas 1 108084 03 Pilot Assembly Propane LP Gas 1 7 11102 Screw 8 32 x 3 8 PPH Zinc 2 8 108755 01 Pilot Bracket 1 9 145...

Страница 36: ...ch com 108861 01F 36 Illustrated Parts Breakdown MODELS V V42N V V42NS V V42NH V V42P V V42PS V V42EPH and CHDV42nr 6 7 21 18 19 14 13 2 12 20 8 10 1 4 11 9 15 3 17 16 5 23 2 23 1 23 5 23 4 23 3 23 7...

Страница 37: ...8329 01 108329 01 Burner Assembly Natural Gas 1 108329 02 108329 02 108329 02 Burner Assembly Propane LP Gas 1 23 108778 01 108778 01 108778 01 Log Set 1 23 1 109396 01 109396 01 109396 01 Front Log L...

Страница 38: ...ww desatech com 108861 01F 38 illustrated parts breakdown Burner Assembly Models V V42N V V42NS V V42NH V V42P V V42PS V V42EPH and CHDV42NR 4 3 2 5 6 7 8 9 10 11 12 13 14 15 16 17 1 21 22 19 19 20 18...

Страница 39: ...20 Pan Burner Orifice Propane LP Gas 1 6 108084 02 Pilot Assembly Natural Gas 1 108084 03 Pilot Assembly Propane LP Gas 1 7 11102 Screw 8 32 x 3 8 PPH Zinc 2 8 108755 01 Pilot Bracket 1 9 104506 25 Tu...

Страница 40: ...ted to repairing a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDE...

Отзывы: