AIR FOR
COMBUSTION AND
VENTILATION

Today’s homes are built more energy effi-
cient than ever. New materials, increased
insulation, and new construction methods
help reduce heat loss in homes. Home owners
weather strip and caulk around windows and
doors to keep the cold air out and the warm air
in. During heating months, home owners
want their homes as airtight as possible.

While it is good to make your home energy
efficient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning
appliances need fresh air for proper com-
bustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and
fuel burning appliances draw air from the
house to operate. You must provide ad-
equate fresh air for these appliances. This
will insure proper venting of vented fuel-
burning appliances.

PROVIDING ADEQUATE
VENTILATION

The following are excerpts from National
Fuel Gas Code. NFPA 54/ANS Z223.1, Sec-
tion 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three
following ventilation classifications:

1.

Unusually Tight Construction

2.

Unconfined Space

3.

Confined Space

The information on pages 5 through 7 will
help you classify your space and provide
adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and win-
dows may provide enough fresh air for
combustion and ventilation. However, in
buildings of unusually tight construction,
you must provide additional fresh air.

Unusually tight construction is de-
fined as construction where:

a.

walls and ceilings exposed to the
outside atmosphere have a con-
tinuous water vapor retarder with
a rating of one perm (6 x 10

-11

 kg

per pa-sec-m

2

) or less with open-

ings gasketed or sealed 

and

b. weather stripping has been

added on openable windows and
doors 

and

c.

caulking or sealants are applied
to areas such as joints around
window and door frames, be-
tween sole plates and floors, be-
tween wall-ceiling joints, be-
tween wall panels, at penetra-
tions for plumbing, electrical, and
gas lines, and at other openings.

If your home meets all of the three
criteria above, you must provide ad-
ditional fresh air. See 

Ventilation Air

From Outdoors, page 7.

If your home does not meet all of the
three criteria above, proceed to 

De-

termining Fresh-Air Flow For Fire-
place Location, page 6.

 WARNING: This heater shall

not be installed in a confined space
or unusually tight construction
unless provisions are provided
for adequate combustion and ven-
tilation air. Read the following in-
structions to insure proper fresh
air for this and other fuel-burning
appliances in your home.

Confined and Unconfined Space

The National Fuel Gas Code (ANS Z223.1,
1992 Section 5.3) 
defines a confined space
as a space whose volume is less than 50
cubic feet per 1,000 Btu per hour (4.8 m

3

 per

kw) of the aggregate input rating of all
appliances installed in that space and an
unconfining space as a space whose volume
is not less than 50 cubic feet per 1,000 Btu
per hour (4.8 m

3

 per kw) of the aggregate

input rating of all appliances installed in that
space. Rooms communicating directly with
the space in which the appliances are in-
stalled*, through openings not furnished
with doors, are considered a part of the
unconfined space.

This heater shall not be installed in a con-
fined space or unusually tight construction
unless provisions are provided for adequate
combustion and ventilation air.

* Adjoining rooms are communicating only
if there are doorless passageways or ventila-
tion grills between them.

Continued

Содержание Vanguard VMH26TNA

Страница 1: ...partment Installation and service must be per formed by a qualified installer service agency or the gas supplier WARNING Improper installa tion adjustment alteration ser vice ormaintenancecancause inj...

Страница 2: ...l into the control area of fireplace 7 You must operate this fireplace with the fireplace screen in place Make sure fireplace screen is in place before run ning fireplace 8 This fireplace is designed...

Страница 3: ...packet 4 Check fireplace for any shipping damage If fireplace is damaged promptly inform dealer where you bought fireplace PRODUCT FEATURES SAFETY PILOT This fireplace has a pilot with an Oxygen Depl...

Страница 4: ...er now Follow installation in structions provided with blower 5 Gently place back log on burner sup port see Figure 2 The log should fit flat against top of burner support Place two 10 one inch long s...

Страница 5: ...kg per pa sec m2 or less with open ings gasketed or sealed and b weather stripping has been added on openable windows and doors and c caulking or sealants are applied to areas such as joints around wi...

Страница 6: ...dd the Btu Hr of all fuel burning appliances in the space Vent free fireplace __________________Btu Hr Gas water heater __________________Btu Hr Gas furnace __________________Btu Hr Vented gas heater...

Страница 7: ...Inlet Air Inlet Air Ventilated Crawl Space To Crawl Space To Attic Figure 4 Ventilation Air from Inside Building Shown with Optional Mantel VENTILATION AIR Ventilation Air From Inside Building Thisfre...

Страница 8: ...ough open ings to create the easiest installation see Built In Fireplace Installation page 9 CHECK GAS TYPE Use only natural gas If your gas supply is not natural gas do not install fireplace Call dea...

Страница 9: ...se dimen sions shown in Figure 8 for the rough opening If installing in a corner use dimensions shown in Figure 9 for the rough open ing The height is 26 7 8 which is the same as the wall opening abov...

Страница 10: ...two 3 wood screws provided and attach fireplace base to wooden base see Figure 12 8 Remove brass trim kit and mantel Be careful not to damage wall or mantel 9 Place wood base next to wall at instal la...

Страница 11: ...er Louver Assembly Upper Louver Assembly Brass Screws Blower Bracket Mounting Holes 1 2 Remove Screw Valve Cover Shield Shoulder Screw Removing Valve Cover Shield 1 Open bottom louver assembly by swin...

Страница 12: ...rear of the valve cover shield and through the rectangular hole in the front of shield see Figure 17 8 Reconnect red wire to switch position 3 Reconnect blue wire to switch posi tion 1 Reconnect gree...

Страница 13: ...rd ware kit into one of the holes found on rear of valve cover shield The other hole is for a strain relief clamp not supplied to secure incoming electrical supply 2 Follow steps 2 through 6 in Instal...

Страница 14: ...monly known as wellhead gas CAUTION Use only new black iron or steel pipe Inter nally tinned copper tubing may be used in certain areas Check your local codes Use pipe of 1 2 or greater diameter to al...

Страница 15: ...exible gas line is provided to allow accessibility fromthefireplace seeFigure23 The flexible gas supply line con nection to the manual shutoff valve should be accessible Flexible Gas Line from Firepla...

Страница 16: ...dual manual shutoff valve from gas supply piping system Pressures in excess of 1 2 psig will damage fireplace regulator 2 Cap off open end of gas pipe where manual shutoff valve was connected 3 Pressu...

Страница 17: ...iedservicetechniciantoinspect the appliance and to replace any part of the control system and any gas con trol which has been under water Control Knob WARNING You must operate this fireplace with the...

Страница 18: ...ll shut off The burner willcyclebackonwhenroomtemperature drops below the set temperature The control knob can be set to any heat level between HI and LO Note The thermostat sensing bulb mea sures the...

Страница 19: ...attern WARNING If yellow tipping occurs your fireplace could pro duce increased levels of carbon monoxide If burner flame pattern shows yellow tipping follow in structions at bottom of this page Yello...

Страница 20: ...1 Turn on gas supply or open manual shutoff valve 2 Turn control knob to PILOT position 3 Press in control knob while in PILOT position 4 Continue holding down control knob Re peatignitingoperationun...

Страница 21: ...oblem will stop after a few hours of operation 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local natural ga...

Страница 22: ...tatement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak SeeWarning statement at top of page 1 Not enough combustion ventilation air OBSERVED PROB...

Страница 23: ...ore or home center may carry com pressed air in a can You can use a vacuum cleaner in the blow position If using com pressed air in a can please follow the direc tions on the can If you don t follow d...

Страница 24: ...HEARTH FIREPLACE VMH26TNA ILLUSTRATED PARTS BREAKDOWN VMH26TNA 12 1 12 2 23 29 43 32 36 38 13 7 8 33 43 11 10 27 4 7 30 1 3 2 9 17 19 6 22 31 21 41 26 42 39 40 16 15 18 24 28 5 34 25 20 35 1 4 35 2 12...

Страница 25: ...303 02 Regulator Screw 2 19 104335 01CK Outer Shell Base 1 20 102649 01CJ Branch Support 1 21 099415 10 Gas Regulator 1 22 102875 01 Regulator Bracket 1 23 101381 01 Valve Cover and Piezo 1 24 099387...

Страница 26: ...national have ready model number of your fireplace the replacement part number SPECIFICATIONS Btu Variable 14 000 26 000 Type Gas Natural Only Ignition Piezo Pressure Regulator Setting 3 W C Inlet Gas...

Страница 27: ...stain or paint Complete assembly instructions in cluded Three sided brass trim kit included CABINET MANTEL WITH BUILT IN HEARTH BASE Unfinished GM923U Finished GM922F For use with fireplace A hardwood...

Страница 28: ...scausedbyimproperinstallation Travel diagnosticcost labor transportation and any and all such other costs related to repairing a defective fireplace will be the responsibility of the owner TO THE FULL...

Отзывы: