PORTABLE GASOLINE GENERATORS

GROUND FAULT CIRCUIT
INTERRUPTER RECEPTACLE

All models have a 120-volt ground fault
circuit interrupter (GFCI) receptacle. The
GFCI protects you against hazardous elec-
trical shock caused when your body be-
comes a path through which electricity trav-
els to reach ground. This could happen when
you touch an appliance or cord that is ‘live’
through faulty mechanism, damp or worn
insulation, etc.

When protected by the GFCI, you may still
feel a shock, but the GFCI should cut it off
quickly. A person in normal health should
not receive serious injury.

 Note:

 Infants and

very small children may still be affected.

Test Procedure

Check the GFCI receptacle every month.
This insures it is working right.

1.

Push black TEST button. Red RESET
button should pop out. This should trip
GFCI, resulting in no electrical power
at receptacle. Verify this by plugging
test lamp with good bulb into recep-
tacle. If lamp does not work, GFCI re-
ceptacle is good.

OFF

ON

START

ENGINE SW

CIRCUIT
 BREAKER

ON/push OFF

Figure 4 - Engine Circuit Breaker

Engine Circuit
Breaker Button

RESET

TEST

Figure 3 - GFCI Receptacle

GENERATOR
FEATURES

OIL ALERT SYSTEM

The oil alert system protects the engine from
low oil damage. This system automatically
shuts down the engine and prevents engine
restarting if the oil level falls too low.

Note:

 When this happens, the engine switch

remains in the ON position. The oil alert
system is wired into the ON/OFF Switch.

If this system shuts down the engine, the
engine will not start until you add oil. Add
oil to engine (see Engine Oil, page 7).

Note: 

Operate generator on a level surface.

If not level, the oil may flow away from the
oil level sensing device. This will cause the
oil alert system to shut down engine.

See engine Owner’s Manual for more
information.

Figure 2 - Engine Switch Location

HONDA

OFF

ON

START

ENGINE SW

CIRCUIT
 BREAKER

ELECTRIC START

A battery is not supplied with generator.
You must provide a 12-volt, 32-amp-hour
battery. For more battery information, see
Battery, pages 7 and 8.

RECEPTACLE CIRCUIT
BREAKER

The circuit breakers protect the receptacles
and alternator. Overloading generator will
trip circuit breaker. A short circuit in item
being powered will also trip breaker. If this
occurs, unplug electrical load from recep-
tacle. Let circuit breaker cool down. Push
circuit breaker button to reset.

Electric motors need higher starting current.
They require up to three-times their rated
wattage to start. The starting current needed
may be too high. This can cause nuisance
circuit breaker tripping. To help prevent
this, start electric motors first. Connect ad-
ditional items to generator after starting
motors. If this continues to happen, reduce
the total generator load.

20

20

Tripped

Normal

Figure 5 - Receptacle Circuit Breaker
Button

Note:

 High ambient temperature will cause

nuisance tripping.

2.

If the GFCI receptacle tests okay, re-
store power by pushing the RESET
button back in. The test lamp should
work at this time

. IMPORTANT:

 You

must press the RESET button firmly
and fully. It should lock into place. If
the GFCI does not lock into place, do
not use receptacle. Contact a qualified
electrician for repairs.

 WARNING: If RESET button

does not pop out, do not use the
GFCI receptacle. Contact a quali-
fied electrician for repairs.

ENGINE CIRCUIT BREAKER

This circuit breaker, or fuse, protects the
battery charging circuit. A short circuit will
trip the circuit breaker. The circuit breaker
will also trip if you install battery wrong.
Push circuit breaker button to reset. On
Model PGH11000IE, the fuse is located
inside of the Keyswitch box.

Содержание PGH1100IE

Страница 1: ...r use of generator can cause serious injury Keep this manual for future reference Generator Models PGH7500IE and PGH11000IE RES ET TES T 120 VOL TS F U E L F RES ET 120 240 VOL TS 120 240V FUL L POW E...

Страница 2: ...nfluence of alcohol and those at high altitudes Make certain you read and understand all warnings Keep this manual for reference It is your guide to safe and proper operation of this generator Safetyi...

Страница 3: ...rops if it is sparking if it produces smoke or flames if it vibrates at high levels if it has a damaged receptacle 12 Keep generator and nearby areas clean Keep generator free of oil mud and other for...

Страница 4: ...arts Check for shipping damage If any parts are missing or damaged promptly inform dealer where you bought generator 4 Battery cables are supplied These cables are in a separate bag inside generator c...

Страница 5: ...120 240 V Twist Lock 30 Amp 30 Amp 120 240 V 50 A No Yes General Honda Engine H P 13 20 Honda Model GX390K1VXE GX620VXA3 Fuel Type Gasoline Gasoline Fuel Tank Capacity 5 gal 5 gal Oil Alert System Yes...

Страница 6: ...he oil alert system to shut down engine See engine Owner s Manual for more information Figure 2 Engine Switch Location HONDA OFF ON START ENGINE SW CIRCUIT BREAKER ELECTRIC START A battery is not supp...

Страница 7: ...efueling Do not overfill fuel tank Al ways allow room for fuel to expand Ifyouoverfilltank fuel can overflow onto hot engine This can cause fire or explo sion After refueling tightly close fuel tank c...

Страница 8: ...Locate the red positive battery cable from starter solenoid Connect it to the positive battery terminal see Figures 11 and 12 3 Locate the black negative battery cable attached to engine block Connect...

Страница 9: ...starting This will help guard against deadly electric shock Only use grounded plugs with generator Onlyusegroundedex tension cords Only use three wire or double insulated power tools WARNING For a gr...

Страница 10: ...00 x Chart 2 Always use starting watts not running watts when figuring correct electrical load x Motors of higher horsepower are not generally used Chart 1 Typical Electric Appliance Wattages DETERMIN...

Страница 11: ...damage generator Use only grounded ex tension cords Power only grounded or double insulated items Do not overload receptacles Both generators have the fol lowing receptacles see Figure 14 120V 15 amp...

Страница 12: ...ure 17 Choke Button Closed Model PGH11000IE Only Choke Button Pulled Out Closed Position 4 Start the engine A Recoil Starter Turn engine switch to the ON position see Figure 18 Remove slack from start...

Страница 13: ...ine Let engine reach full speed 3 Connect electrical loads one at a time If the load consists of electric motors start them first Always start the larg est first Start each motor individually DISCONNE...

Страница 14: ...upply the engine Owner s Manualwithgenerator Refertothatmanual for questions concerning engine mainte nance and repairs Non enginepartsrequirelittlemaintenance Keep generator clean Use a damp cloth to...

Страница 15: ...d Yellow Yellow White White Auto Idle Control Board Yellow White White White Circuit Breaker 30A Circuit Breaker 30A Circuit Breaker 45A Circuit Breaker 45A Green T2 Green Black Red White Main Winding...

Страница 16: ...3 Stator 1 14 27003002 Fan Bracket 1 15 27003015S Screw M8 x 20 4 16 099891 01 Rotor Nut Flanged 8mm 1 17 099892 01 Foam Pad 1 18 099842 04 Draw Bolt 1 19 27003003 Bearing 1 20 27003012S Diode 2 21 Ro...

Страница 17: ...ting Bolts 4 10 099891 01 Nuts 4 11 103189 01 Top Box 1 12 099701 01 Screw and Washer 6 13 103198 01 Plastic Cap 1 14 103199 01 Bearing 1 15 103200 01 Borelly Washer 1 16 27003012S Diode 2 17 103201 0...

Страница 18: ...ENERATORS 9 10 11 12 13 11 16 13 13 17 17 18 11 11 11 16 11 16 21 20 19 14 23 14 23 23 16 16 16 16 10 11 16 11 16 22 F U E L F 1 3 2 4 24 7 8 6 6 27 7 25 15 5 26 ILLUSTRATED PARTS LIST FOR MODEL PGH75...

Страница 19: ...4 2 18 099756 01 Engine Spreader 1 19 099750 01 Hook Bolt 5 16 18 2 20 099749 01 Battery Mounting Bracket 1 21 NEC 5C Lock Nut 5 16 18 2 22 100410 01 Sems Screw 8 18 x 1 2 4 23 M10908 74 Screw 1 4 20...

Страница 20: ...ORS 9 10 12 15 33 11 17 13 24 24 18 11 24 5 11 20 11 19 16 14 23 36 35 34 21 25 24 13 27 22 F U E L F 1 3 2 4 26 6 37 7 11 32 25 24 34 11 25 24 8 29 30 31 28 24 11 24 ILLUSTRATED PARTS LIST FOR MODEL...

Страница 21: ...0908 74 1 4 20 x 1 2 Screw 1 24 WP 5C 5 16 Washer 24 25 26007004 5 16 18 x 3 4 Bolt 10 26 WP 4C 1 4 Washer 4 27 WLI 8 1 2 Lock Washer 2 28 H8C5 20C 5 16 18 x 2 50 Screw 4 29 105035 01 Handle 2 30 1030...

Страница 22: ...1 11 100410 01 Sems Screw 8 18 x 1 2 4 12 100149 01 Control Box 1 13 22261000 U Nut 8 103348 04 Control Panel Assembly 1 103348 08 Control Panel Assembly Auto Idle Models 1 100177 07 Panel Schematic...

Страница 23: ...100366 01 Rocker Switch 1 16 15324000 120V 15A Duplex Receptacle 1 102927 01 Control Panel Assembly 1 100177 05 Panel Schematic Diagram 1 103257 01 Auto Idle PC Board Kit 1 103258 02 Solenoid Assembl...

Страница 24: ...orized dealers of this product If they cannot supply original replacement part s either contact your nearest Parts Central or call DESA International s Parts Department at 1 800 972 7879 for referral...

Страница 25: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Страница 26: ...bility of the owner DESA International makes no warranty with respect to the engine and engine components not of its manufacture They are subject to warranties of their manufacturers To the full exten...

Отзывы: