OWNER’S MANUAL

Example:

Gas water heater

40,000

Btu/Hr

Vent-free heater   +

10,000

Btu/Hr

Total                    =

50,000

Btu/Hr

DETERMINING FRESH AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between

the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example:

 Space size 18 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2304 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

________________(volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example:

 2304 cu. ft. (volume of space) 

÷

 50 cu. ft. = 46.1 or 46,100 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater              ______________Btu/Hr

Gas water heater*           ______________Btu/Hr

Gas furnace                     ______________Btu/Hr

Vented gas heater            ______________Btu/Hr

Gas fireplace logs           ______________Btu/Hr

Other gas appliances*  +______________Btu/Hr

Total                             =______________Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_______________Btu/Hr (maximum the space can support)

_______________Btu/Hr (actual amount of Btu/Hr used)

       

Example:

46,100 Btu/Hr (maximum the space can support)

50,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors,page 6.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the

 National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

Continued

Содержание Medallion MR10NT

Страница 1: ...qualified installer service agency or the gas supplier WARNING Improper instal lation adjustment alteration service or maintenance can causeinjuryorpropertydam age Refer to this manual for correct in...

Страница 2: ...urns fire explosion and car bon monoxide poisoning DANGER Carbon monoxide poisoning may lead to death 5 This heater needs fresh outside air ven tilation to run properly This heater has an Oxygen Deple...

Страница 3: ...er for shipment 3 Check heater for any shipping damage If heater is damaged promptly inform dealer where you bought heater PRODUCT FEATURES SAFETY PILOT This heater has a pilot with an Oxygen Depletio...

Страница 4: ...lume is less than 50 cubic feet per 1 000 Btu per hour 4 8 m3 per kw of the aggre gate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not les...

Страница 5: ...al ______________Btu Hr Do not include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with t...

Страница 6: ...of the adjoiningunconfinedspace The combined spaces must have enough fresh air to supply all appliances in both spaces Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills...

Страница 7: ...fromfloor ceiling andjoin ing wall CAUTION If you install the heater in a home garage heaterpilotandburnermustbe at least 18 inches above floor locate heater where moving vehicle will not hit it IMPOR...

Страница 8: ...l Stud Method For attaching mounting screw to wall stud 1 Drill hole at marked location using 9 64 drill bit 2 Insert mounting screw into wall stud 3 Tighten screw until 1 16 space thick ness of penny...

Страница 9: ...wn in Figure 12 Locate sediment trap where it is within reach for cleaning Locate sedi ment trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps...

Страница 10: ...onnected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Fig ure 13 2 Pressurize supply piping system by ei ther using compressed air or op...

Страница 11: ...rops below the set temperature Selecting a higher setting will cause the heater to run longer producing greater heat output At lower settings the heater will run less Note The thermostat sensing bulb...

Страница 12: ...INTENANCE ODS PILOT AND BURNER ORIFICE Use a vacuum cleaner pressurized air or small soft bristled brush to clean CLEANING BURNER PILOT AIR INLET HOLE We recommend that you clean the unit ev ery 2 500...

Страница 13: ...base panel 4 Replace ignitor cable 5 Replace ignitor 6 Replace piezo ignitor 7 Replace ignitor 1 Turn on gas supply or open equipment shutoff valve 2 Turn control knob to PILOT position 3 Press in con...

Страница 14: ...s see Cleaning and Maintenance page 12 or replace burner orifice s 2 Contact local natural gas company 3 Replace burner 4 Replace gas regulator 1 Plaque damaged 2 Inlet gas pressure is too low 3 Contr...

Страница 15: ...nections page 10 1 Open window and or door for ventilation 2 Contact local natural gas company 3 Clean ODS pilot see Cleaning and Maintenance page 12 1 Locate and correct all leaks see Checking Gas Co...

Страница 16: ...16 105935 VENT FREE NATURAL GAS HEATER MR10NT 12 A B 16 7 8 4 6 5 3 2 1 11 14 13 19 18 6 17 15 16 10 9 7 1 ODS PILOT 7 2 ILLUSTRATED PARTS LIST MR10NT...

Страница 17: ...823 37 Screw Hex 8 x 1 4 10 7 503329 ODS Pilot Assembly 1 7 1 098514 01 Thermocouple 1 7 2 098594 01 Ignitor Electrode 1 8 099884 03 Burner Assembly 1 9 099056 24 Injector 1 10 104087 01 Tubing Burner...

Страница 18: ...s call Cans Unlimited Incorporated s Technical Ser vice Department at 1 800 922 7407 for in formation When contacting your dealer or Cans Un limited Incorporated have ready your name your address mod...

Страница 19: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Страница 20: ...he unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper mai...

Отзывы: