www.desatech.com
123167-01D
12
INSTALLATION
Continued
CAUTION: Do not pick up
heater base assembly by the
burner. This could damage heat
-
er. Only handle base assembly
by grates.
IMPORTANT:
Make sure heater burners are
level. If heater is not level, heater will not
work properly.
Installation Items Needed
• hardware package (provided with heater)
• approved flexible gas hose (not provided)
(if allowed by local codes)
• sealant (resistant to propane/LP gas, not
provided)
• electric drill with 3/16" drill bit
• flathead screwdriver
1. Apply pipe joint sealant lightly to male
threads of fitting to be threaded into gas
regulator. Connect approved flexible gas
hose to gas regulator of heater (see Fig-
ure 11, page 13).
IMPORTANT:
Hold gas regulator with
wrench when connecting flexible gas hose
.
2. Locate masonry screws in hardware
package.
3. Position heater base assembly in fire
-
place.
4. Place logs in their proper position on heater
base (see
Installing Logs,
page 17).
5. Center heater base and logs front-to-front
and side-to-side in fireplace.
6. Carefully remove logs without moving
heater base.
Heater Gas
Regulator
Flexible Gas Hose
(if allowed by local codes)
Figure 10 - Attaching Flexible Gas Hose
to Heater Gas Regulator
Fitting
INSTALLING HEATER BASE
ASSEMBLY
CAUTION: Do not remove the
data plates attached to the heater
base assembly. The data plates
contain important warranty and
safety information.
WARNING: You must secure
this heater to fireplace floor. If
not, heater will move when you
adjust controls. Moving heater
may cause a gas leak.
WARNING: If installing in a
sunken fireplace, special care
is needed. You must raise the
fireplace floor to allow access to
heater control panel. This will in
-
sure adequate air flow and guard
against sooting and controls be
-
ing damaged. Raise fireplace floor
with noncombustible material.
Make sure material is secure.
Area of Various Standard Round Flues
Diameter
Area
5"
20 sq. inches
6"
29 sq. inches
7"
39 sq. inches
8"
51 sq. inches
Chimney Height
Minimum permanent
Flue Opening
6' to 15'
39 sq. inches
15' to 30'
29 sq. inches
See chart below for minimum permanent flue
opening you must provide. Attach damper
clamp so the minimum permanent flue open
-
ing will be maintained at all times.