BLUE FLAME NATURAL GAS HEATER

Figure 3 - Ventilation Air from Outdoors

Outlet
Air

Ventilated
Attic 

Outlet
Air

Inlet
Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation
grills or ducts. You must provide two per-
manent openings: one within 12" of the
ceiling and one within 12" of the floor.
Connect these items directly to the outdoors
or spaces open to the outdoors. These spaces
include attics and crawl spaces. Follow the
National Fuel Gas Code, NFPA 54/ANS
Z223.1, Section 5.3, Air for Combustion and
Ventilation
 for required size of ventilation
grills or ducts.

IMPORTANT:

 Do not provide openings for

inlet or outlet air into attic if attic has a
thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

Or 

Remove 

Door into 
Adjoining 

Room, 

Option 3

Ventilation Grills 

Into Adjoining Room,

Option 2

12"

12"

Ventilation

Grills

into Adjoining

Room, 

Option 1

VENTILATION AIR

Ventilation Air From Inside
Building

This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must pro-
vide two permanent openings: one within
12" of the ceiling and one within 12" of the
floor on the wall connecting the two spaces
(see options 1 and 2, Figure 2). You can also
remove door into adjoining room (see op-
tion 3, Figure 2). Follow the National Fuel
Gas Code, NFPA 54/ANS Z223.1, Section
5.3, Air for Combustion and Ventilation
 for
required size of ventilation grills or ducts.

Figure 2 - Ventilation Air from Inside Building

 WARNING: Rework work-

sheet, adding the space of the
adjoining unconfined space. The
combined spaces must have
enough fresh air to supply all
appliances in both spaces.

Содержание Glo-Warm FGHS30NGB

Страница 1: ...rformed by a qualified installer service agency or the gas supplier Aftermarket Completion of sale not for purpose of resale from the manufacturer WARNING This is an unvented gas fired heater It uses...

Страница 2: ...ilation to run properly This heater has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shuts down the heater if not enough fresh air is available See Air for Combustion and Ventilation...

Страница 3: ...If heater is damaged promptly inform dealer where you bought heater Figure 1 Vent Free Natural Gas Heater Ignitor Button Control Knob Heater Cabinet Front Panel PRODUCT FEATURES SAFETY DEVICE This he...

Страница 4: ...ion and ventilation However in buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is de fined as construction where a walls and ceilings expos...

Страница 5: ...include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr use...

Страница 6: ...atticwillactivatethepowervent AIR FOR COMBUSTION AND VENTILATION Continued Or Remove Door into Adjoining Room Option 3 Ventilation Grills Into Adjoining Room Option 2 12 12 Ventilation Grills into Adj...

Страница 7: ...n and Ventilation pages 4 through 6 CAUTION This heater cre ates warm air currents These currents move heat to wall sur faces next to heater Installing heater next to vinyl or cloth wall coverings or...

Страница 8: ...et Removing Front Panel Of Heater 1 Remove two screws near bottom cor ners of front panel 2 Liftstraightupongrillguarduntilitstops Grill guard will slide up about 1 4 3 Pull bottom of front panel forw...

Страница 9: ...acket and into wall anchors 7 Tighten screws until mounting bracket is firmly fastened to wall Figure 12 Installing Bottom Mounting Screws Figure 10 Popping Open Anchor Wings For Thin Walls Figure 11...

Страница 10: ...alled wrong heater may not run properly IMPORTANT Holdpressureregulatorwith wrench when connecting it to gas piping and or fittings CAUTION Use only new black iron or steel pipe Inter nally tinned cop...

Страница 11: ...ent shutoff valve see Figure 14 2 Open main gas valve located on or near gas meter 3 Make sure control knob of heater is in the OFF position 4 Check all joints from equipment shutoff valve to thermost...

Страница 12: ...theequip ment shutoff valve Figure 17 Pilot LIGHTING INSTRUCTIONS 1 STOP Read the safety information column 3 page 11 2 Make sure equipment shutoff valve is fully open 3 Turn control knob clockwise Cl...

Страница 13: ...ol areas burner and circu lating air passageways of heater clean Inspect these areas of heater before each use Have heaterinspectedyearlybyaquali fied service person Heater may need more frequent clea...

Страница 14: ...llowing A Low gas pressure B Dirty or partially clogged ODS pilot 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Replace ignitor 2 Replace ignitor 3 Reconnect ignitor cable 4 Free ignitor cab...

Страница 15: ...em will stop after a few hours of operation 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local natural gas c...

Страница 16: ...g statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak SeeWarning statement at top of page 1 Not enough combustion ventilation air OBSERVED P...

Страница 17: ...2 0724 www tarantin com Heater and Fireplace Store 58 Halbe Lane Cape May Court NJ 08210 1110 609 390 9774 Parts Department Dayton Hardware P O Box 275 North Dayton Station Dayton OH 45404 0275 All St...

Страница 18: ...BLUE FLAME NATURAL GAS HEATER ILLUSTRATED PARTS BREAKDOWN THERMOSTAT MODEL FGHS30NGB 7 7 5 2 5 27 22 26 23 19 17 24 25 12 26 21 20 18 9 8 18 16 10 16 13 1 14 14 15 7 6 11 3 7 4 7 7 24 1 24 2 ODS Pilot...

Страница 19: ...1 097159 04 Ignitor 1 12 L98411 01 Ignitor Line 1 13 L99029 03 Pressure Regulator 1 14 L98801 01 Washer 2 15 L98806 01 Self Tapping Screw 2 16 L98115 03 Main Inlet Tube Assembly 1 17 L98123 06 ODS Lin...

Страница 20: ...produce specified heat When Gas Quality Is Bad pilot will not stay lit burner will produce flames and soot heater will backfire when lit Youmayfeelyourgaspressureistoolowor gas quality is bad If so c...

Страница 21: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Страница 22: ...oids this warranty The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not...

Отзывы: