background image

www.desatech.com

117001-01B

6

The space in the above example is a confined space 

because the actual Btu/Hr used is more than the maxi

-

mum Btu/Hr the space can support. You must provide 

additional fresh air. Your options are as follows:

A.  Rework  worksheet,  adding  the  space  of  an 

adjoining room. If the extra space provides an 

unconfined  space,  remove  door  to  adjoining 

room or add ventilation grills between rooms. 

See 

Ventilation Air From Inside Building.

B.  Vent room directly to the outdoors. See 

Ventila-

tion Air From Outdoors, 

page 7.

C.  Install a lower Btu/Hr heater, if lower Btu/Hr size 

makes room unconfined.

If the actual Btu/Hr used is less than the maximum 

Btu/Hr the space can support,

 

the space is an un

-

confined space. You will need no additional fresh 

air ventilation.

  WARNING:  If  the  area  in 

which the heater may be oper

-

ated is smaller than that defined 

as an unconfined space or if the 

building  is  of  unusually  tight 

construction, provide adequate 

combustion and ventilation air 

by one of the methods described 

in the 

National Fuel Gas Code, 

ANSI Z223.1/NFPA 54 Section 5.3

 

or applicable local codes.

vENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining 

unconfined space. When ventilating to an adjoin

-

ing  unconfined  space,  you  must  provide  two 

permanent openings: one within 12" (30.5 cm)

 

of the ceiling and one within 12" (30.5 cm)

 of the 

floor on the wall connecting the two spaces (see 

options 1 and 2, Figure 2, page 7). You can also 

remove door into adjoining room (see option 3, 

Figure 2, page 7). Follow the 

National Fuel Gas 

Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for 

Combustion and Ventilation

 for required size of 

ventilation grills or ducts.

DETERMINING FRESH-AIR FLOW 
FOR HEATER LOCATION

Determining if You Have a Confined or 
Unconfined Space

Use this work sheet to determine if you have a 

confined or unconfined space.

Space: 

Includes the room in which you will install 

heater plus any adjoining rooms with doorless pas

-

sageways or ventilation grills between the rooms.

1.  Determine the volume of the space (length x 

width x height).

 

Length x Width x Height =__________cu. ft. 

(volume of space)

 

Example:

 Space size 20 ft. (6.1 m) (length) x 16 

ft. (4.88 m) (width) x 8 ft. (2.44 m) (ceiling height) 

= 2560 cu. ft. (72.49 m

3

) (volume of space)

 

If additional ventilation to adjoining room is 

supplied with grills or openings, add the volume 

of these rooms to the total volume of the space. 

2.  Multiply the space volume by 20 to determine 

the maximum Btu/Hr the space can support.

 

 __________

(volume of space) x 20 = (Maxi

-

mum Btu/Hr the space can support)

 

Example: 

2,560 cu. ft. (72.49 m

3

) (volume of 

space) x 20 = 51,200 (maximum Btu/Hr the space 

can support)

3.  Add the Btu/Hr of all fuel burning appliances in 

the space.

 

Vent-free heater 

 ___________

Btu/Hr

 

Gas water heater* 

 ___________

Btu/Hr

 

Gas furnace 

 ___________

Btu/Hr

 

Vented gas heater 

 ___________

Btu/Hr

 

Gas fireplace logs 

 ___________

Btu/Hr

 

Other gas appliances*  +

 __________

Btu/Hr

 

Total 

= __________

Btu/Hr

 

* Do not include direct-vent gas appliances. Di

-

rect-vent draws combustion air from the outdoors 

and vents to the outdoors.

 

Example:

 

Gas water heater 

 ___________

Btu/Hr

 

Vent-free heater 

+

 __________

Btu/Hr

 

Total 

= __________

Btu/Hr

4.  Compare the maximum Btu/Hr the space can 

support with the actual amount of Btu/Hr used.

 

 __________

Btu/Hr (maximum the space can support) 

 

 __________

Btu/Hr (actual amount of Btu/Hr used)

 

Example:

  51,200 Btu/Hr (maximum the space 

can support) 

 

 

60,000  Btu/Hr  (actual  amount  of 

Btu/Hr used)

AIR FOR COMBUSTION 

AND VENTILATION

Continued

  50,000

  10,000

  60,000

Содержание DWN6

Страница 1: ...flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in yo...

Страница 2: ...cer or birth defects or other reproductive harm IMPORTANT Read this owner s manualcarefullyandcompletely before trying to assemble operate or service this heater Improper use of this heater can cause...

Страница 3: ...propane LP supply tank s in side any structure Locate propane LP supply tank s outdoors 3 Do not install 10 000 Btu hr units in a bath room 6 000 Btu hr heaters are allowed in a bathroom 4 If you smel...

Страница 4: ...upon sale of the unit Vent free gas products are prohibited for bed room and bathroom installation in the Com monwealth of Massachusetts Unpacking 1 Remove heater from carton 2 Remove all protective...

Страница 5: ...e air that leaks around doors and windows may provide enough fresh air for combustion and ventilation However in buildings of unusually tight construction you must provide additional fresh air Unusual...

Страница 6: ...ls or ducts DETERMINING FRESH AIR FLOW FOR Heater LOCATION Determining if You Have a Confined or Unconfined Space Use this work sheet to determine if you have a confined or unconfined space Space Incl...

Страница 7: ...this heater as your primary heat source WARNING A qualified ser vice person must install heater Follow all local codes CHECK GAS TYPE Use only the correct type of gas natural or pro pane LP If your g...

Страница 8: ...currents These currents move heat to wall sur faces next to heater Installing heater next to vinyl or cloth wall coverings or operating heater where impurities such as but not limited to tobacco smoke...

Страница 9: ...thick walls over 1 2 1 3 cm thick or solid walls do not pop open wings 5 Tighten two screws until 1 16 1 6 mm space thickness of penny is between screwheads and wall see Figure 8 Installation Continu...

Страница 10: ...codes Use pipe of large enough diameter to allow proper gas volume to heater If pipe is too small undue loss of volume will occur Installation Continued Figure 12 External Regulator With Vent Pointin...

Страница 11: ...pliance main gas valve control valve and equipment shutoff valve from gas supply piping system Pressures in excess of 1 2 psig will damage heater regulator 2 Cap off open end of gas pipe where equipme...

Страница 12: ...sion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas con...

Страница 13: ...ntil repairs are made light pilot with match To light pilot with match see Manual Lighting Procedure page 14 8 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release...

Страница 14: ...Pilot Burner Thermocouple Blue Flame Yellow Flame Figure 20 Correct Pilot Flame Pattern Figure 21 Incorrect Pilot Flame Pattern Note The pilot flame on natural gas units will have a slight curve but f...

Страница 15: ...ason Blocked air holes will create soot We recommend that you clean the unit every three months during operation and have heater inspected yearly by a qualified service person We also recommend that y...

Страница 16: ...s when in stalled 5 Depleted gas supply propane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Replace pilot assembly 2 Replace pilot assembly 3 Reconnect ignitor cable...

Страница 17: ...knob fully 2 After ODS pilot lights keep control knob pressed in 30 seconds 3 Fully open equipment shutoff valve 4 Hand tighten until snug then tighten 1 4 turn more 5 A Contact local natural or propa...

Страница 18: ...lace gas regulator 1 Problem will stop after a few hours of operation 1 Turn control knob to lowest position and let warm up for a minute 2 Operate burner until air is removed from line Have gas check...

Страница 19: ...ance page 15 1 Locate and correct all leaks see Checking Gas Connec tions page 11 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking...

Страница 20: ...www desatech com 117001 01B 20 9 11 10 1 2 3 4 5 6 7 8 10 12 13 14 16 17 20 21 19 23 22 18 24 15 Illustrated Parts Breakdown Models GWP6 GWN6 GWP10 and GWN10 11 1 11 ODS Pilot...

Страница 21: ...7 Pilot Tubing 1 14 104259 01 Injector 1 piece 1 104259 02 Injector 1 piece 1 104259 03 Injector 1 piece 1 104259 04 Injector 1 piece 1 15 NJF 8C Hex Nut 1 16 099415 17 Pressure Regulator 1 099415 18...

Страница 22: ...www desatech com 117001 01B 22 ILLUSTRATED PARTS BREAKDOWN Models GWP10T and GWN10T 15 1 2 3 5 6 7 8 4 13 9 10 12 13 14 11 17 19 18 9 20 21 16 11 1 11 ODS Pilot...

Страница 23: ...ly 1 11 1 110186 01 Thermocouple Kit 1 12 104263 03 Burner 1 13 099387 11 Pilot Tubing 1 14 104259 05 Injector 1 Piece 1 104259 06 Injector 1 Piece 1 15 NJF 8C Hex Nut 1 16 099415 17 Pressure Regulato...

Страница 24: ...ensions H x W x D 25 x 16 75 x 7 75 63 5 x 42 5 x 19 7 cm Heater Weight 13 5 6 1 kg Heater Shipping Weight 15 lb 6 8 kg GWP6 4 400 6 000 Btu hr Variable Propane LP Gas Piezo Ignition Pressure Regulato...

Страница 25: ...serial numbers of your heater ready You can also visit DESAHeating Products techni cal service web site at www desatech com Service Publications Youcanpurchaseaservicemanualfromtheaddress listed on t...

Страница 26: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Страница 27: ...provide original factory replacement parts Failure to use original factory replacement parts voids this warranty The heater MUST be installed by a qualified installer in accordance with all local cod...

Отзывы: