16

104277

VENT-FREE NATURAL GAS COMPACT FIREPLACE

TROUBLESHOOTING

POSSIBLE  CAUSE

1. Ignitor cable pinched or wet

2. Ignitor electrode not connected to igni-

tor cable

3. Broken ignitor cable
4. Bad piezo ignitor
5. Ignitor electrode broken
6. Ignitor electrode positioned wrong

1. Gas supply turned off or manual shutoff

valve closed

2. Control knob not in PILOT position
3. Control knob not pressed in while in

PILOT position

4. Air in gas lines when installed

5. ODS/pilot is clogged

6. Gas regulator setting is not correct

1. Control knob not fully pressed in
2. Control knob not pressed in long enough

3. Safety interlock system has been trig-

gered

4. Manual shutoff valve not fully open
5. Thermocouple connection loose at con-

trol valve

6. Pilot flame not touching thermocouple,

which allows thermocouple to cool,
causing pilot flame to go out. This prob-
lem could be caused by one or both of
the following:
A) Low gas pressure
B) Dirty or partially clogged ODS/pilot

7. Thermocouple damaged
8. Control valve damaged

1. Burner orifice is clogged

2. Burner orifice diameter is too small
3. Inlet gas pressure is too low

REMEDY

1. Free ignitor cable if pinched by any

metal or tubing. Keep ignitor cable dry

2. Reconnect ignitor cable

3. Replace ignitor cable
4. Replace piezo ignitor
5. Replace ignitor
6. Replace ignitor

1. Turn on gas supply or open manual

shutoff valve

2. Turn control knob to PILOT position
3. Press in control knob while in PILOT

position

4. Continue holding down control knob.

Repeat igniting operation until air is
removed

5. Clean ODS/pilot (see Cleaning and

Maintenance, page 19) or replace ODS/
pilot assembly

6. Replace gas regulator

1. Press in control knob fully
2. After ODS/pilot lights, keep control

knob pressed in 30 seconds

3. Wait one minute for safety interlock sys-

tem to reset. Repeat ignition operation

4. Fully open manual shut-off valve
5. Hand tighten until snug, then tighten 1/4

turn more

6. A) Contact local natural gas company

B) Clean ODS/pilot (see Cleaning and
Maintenance
, page 19) or replace ODS/
pilot assembly

7. Replace thermocouple
8. Replace control valve

1. Clean burner (see Cleaning and Mainte-

nance, page 19) or replace burner orifice

2. Replace burner orifice
3. Contact local natural gas company

OBSERVED PROBLEM

When ignitor button is pressed, there is no
spark at ODS/pilot

When ignitor button is pressed, there is
spark at ODS/pilot but no ignition

ODS/pilot lights but flame goes out when
control knob is released

Burner does not light after ODS/pilot is lit

 WARNING: Turn off and un-

plug fireplace and let cool before
servicing. Only a qualified ser-
vice person should service and
repair fireplace.

 CAUTION: Never use a wire,

needle, or similar object to clean
ODS/pilot. This can damage ODS/
pilot unit.

Note:

 For additional help, visit DESA

International’s Technical Service web
site at 

www.desatech.com

.

Note:

 All troubleshooting items are listed in

order of operation.

www.desatech.com

Содержание Comfort Glow CGCF26TNA

Страница 1: ...or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a...

Страница 2: ...all into the control area of fireplace 7 You must operate this fireplace with the fireplace screen in place Make sure fireplace screen is in place before run ning fireplace 8 This fireplace is designe...

Страница 3: ...et 4 Check fireplace for any shipping damage If fireplace is damaged promptly inform dealer where you bought fireplace PRODUCT FEATURES SAFETY PILOT This fireplace has a pilot with an Oxygen Depletion...

Страница 4: ...ided with blower 5 Gently place back log on burner sup port see Figure 2 The log should fit flat against top of burner support Place two 10 one inch long screws through burner support into the log and...

Страница 5: ...buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is de fined as construction where a walls and ceilings exposed to the outside atmosphere ha...

Страница 6: ...__ Btu Hr Do not include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amou...

Страница 7: ...LATION AIR Ventilation Air From Inside Building Thisfreshairwouldcomefromanadjoining unconfined space When ventilating to an adjoining unconfined space you must pro vide two permanent openings one wit...

Страница 8: ...lling fireplace make sure you have the items listed below piping check local codes sealant resistant to propane LP gas manual shutoff valve test gauge connection ground joint union sediment trap tee j...

Страница 9: ...mfort Glow fireplace is de signed to be used in zero clearance installa tions Wallorframingmaterialcanbeplaced directly against any exterior surface on the rear sides or top of your fireplace Actual F...

Страница 10: ...houlder Screws Assembled Brass Trim Hole for 3 wood screw for attaching fireplace to wooden base Hole for 3 wood screw for attaching fireplace to mantel 5 Firmly snap brass trim kit on shoulder screws...

Страница 11: ...m LP gas Purchase the optional A G A design cer tifiedmanualshutoffvalvefromyourdealer See Accessories page 22 Figure 16 Gas Connection ATTACHING WOOD BASE TO SOLID FLOOR For attaching base to solid f...

Страница 12: ...to flexible gas line see Figure 18 Con nect flexible gas line to flexible gas line attached to gas regulator of fireplace see Figure 18 5 Check all gas connections for leaks See Checking Gas Connecti...

Страница 13: ...ect all leaks at once WARNING Neveruseanopen flame to check for a leak Apply a mixture of liquid soap and water toalljoints Bubblesformingshow a leak Correct all leaks at once Pressure Testing Firepla...

Страница 14: ...repair it call a qualified service technician or gas supplier Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call...

Страница 15: ...ool When the thermo couple cools the fireplace will shut down If pilot flame pattern is incorrect as shown in Figure 24 turn fireplace off see To Turn Off Gas to Appliance see Troubleshooting pages 16...

Страница 16: ...valve 2 Turn control knob to PILOT position 3 Press in control knob while in PILOT position 4 Continue holding down control knob Repeat igniting operation until air is removed 5 Clean ODS pilot see Cl...

Страница 17: ...on 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local natural gas company 3 Observe minimum installation cle...

Страница 18: ...atement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak SeeWarning statement at top of page 1 Not enough combustion ventilation air OBSERVED PROBL...

Страница 19: ...ur local natural gas supplier SERVICE HINTS CLEANING BURNER INJECTOR HOLDER AND PILOT AIR INLET HOLE The primary air inlet holes allow the proper amount of air to mix with the gas This provides a clea...

Страница 20: ...GAS COMPACT FIREPLACE 17 23 29 32 8 14 36 37 13 7 8 42 33 11 4 17 10 4 7 8 8 30 3 1 2 9 19 6 22 31 21 40 41 38 39 16 15 18 24 28 5 34 26 25 20 35 1 4 35 2 12 24 12 1 25 14 8 3 27 12 1 12 2 ILLUSTRATE...

Страница 21: ...1 17 097403 01 Screw Panhead 10 x 1 3 4 2 18 098303 02 Regulator Screw 2 19 104335 01CK Outer Shell Base 1 20 102649 02CJ Branch Support 1 21 099415 10 Gas Regulator 1 22 102875 01 Regulator Bracket 1...

Страница 22: ...nstructions included Three sided brass trim kit included CORNER MANTEL WITH BUILT IN HEARTH BASE Unfinished Birch GMC20U Walnut Finished Birch GMC19F Forusewithfireplace Space savingmantel andhearthba...

Страница 23: ...entrals are privately owned businesses They have agreed to support our customer s needs by providing original replacement parts and accessories Dayton Hardware P O Box 275 North Dayton Station Dayton...

Страница 24: ...efects caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a defective fireplace will be the responsibility of the owner T...

Отзывы: