background image

6

101805

AIR FOR

COMBUSTION

AND

VENTILATION

Continued

DETERMINING AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining rooms with

doorless passageways or ventilation grills between the rooms.

1. Determine the volume of the space (length x width x height).

Length x Width x Height =

___________________

cu. ft. (volume of space)

Example:

Space size

20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) =
2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the
volume of these rooms to the total volume of the space.

2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space

can support.

____________ (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr the space can

support)

Example: 

2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the

space can support)

3. Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

___________________ Btu/Hr

Gas water heater*

___________________ Btu/Hr

Gas furnace

___________________ Btu/Hr

Vented gas heater

___________________ Btu/Hr

Gas fireplace logs

___________________ Btu/Hr

Other gas appliances*

___________________ Btu/Hr

Total

___________________ Btu/Hr

Example:

Gas water heater

40,000

Btu/Hr

Vent-free heater

+

18,000

Btu/Hr

Total

=

58,000

Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the
outdoors and vents to the outdoors.

4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr

used.

_________________ Btu/Hr (maximum the space can support)
_________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200

Btu/Hr (maximum the space can support)

58,000

Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more
than the maximum Btu/Hr the space can support. You must provide additional fresh air.
Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides

an unconfined space, remove door to adjoining room or add ventilation grills between
rooms. See Ventilation Air From Inside Building, page 7.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 8.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space
is an unconfined space. You will need no additional fresh air ventilation.

Содержание CGP18C

Страница 1: ...o not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas s...

Страница 2: ...onoxide poisoning WARNING ICON G 001 DANGER Carbon monoxide poisoning may lead to death Carbon Monoxide Poisoning Early signs of carbon monoxide poisoning resemble the flu with headaches dizziness or...

Страница 3: ...pilot light safety system The ODS shuts down the heater if not enough fresh air is available See Air for Combustion and Ventilation pages 5 through 8 7 Keep all air openings in the front and bottom o...

Страница 4: ...move heater from carton 2 Remove all protective packaging applied to heater for shipment 3 Check heater for any shipping damage If heater is damaged promptly inform dealer where you bought heater LOCA...

Страница 5: ...1992 Section 5 3 defines confined space as having an air volume of less than 50 cubic feet 127 cubic cm for each 1000 Btu Hr input rating of all appliances in the space cubic feet equals length x widt...

Страница 6: ...heater ___________________ Btu Hr Gas fireplace logs ___________________ Btu Hr Other gas appliances ___________________ Btu Hr Total ___________________ Btu Hr Example Gas water heater 40 000 Btu Hr...

Страница 7: ...TILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space When ventilating to an adjoining unconfined space you must provide two permanent openings...

Страница 8: ...nt openings one within 12 of the ceiling and one within 12 of the floor Connect these items directly to the outdoors or spaces open to the outdoors These spaces include attics and crawl spaces Follow...

Страница 9: ...in the minimum clearances shown in Figure 4 page 10 If you can provide greater clearances from floor ceiling and joining wall You can locate model CGP18C on floor away from a wall An optional floor mo...

Страница 10: ...where there is easy access for operation inspection and service where strong wind gusts from an open door or garage door can not blow directly into heater An optional fan kit is available from your d...

Страница 11: ...003B FRONT PANEL REMOVAL G H Methods For Attaching Mounting Bracket To Wall Only use last hole on each end of mounting bracket to attach bracket to wall These two holes are 16 inches apart from their...

Страница 12: ...drill bit 2 Place mounting bracket onto wall Line up last hole on each end of bracket with holes drilled in wall 3 Insert mounting screws through bracket and into wall studs 4 Tighten screws until mo...

Страница 13: ...ttom mounting holes These holes are near bottom on back panel of heater see Figure 11 2 Mark screw locations on wall 3 Remove heater from mounting bracket 4 If installing bottom mounting screws into h...

Страница 14: ...ocal codes Use pipe of 1 2 diameter or greater to allow proper gas volume to heater If pipe is too small undue loss of pressure will occur Propane LP Supply Tank Figure 12 External Regulator With Vent...

Страница 15: ...C to 14 W C Pressure 3 Minimum Sediment Trap CONNECTING TO GAS SUPPLY Continued WARNING ICON G 001 WARNING Test all gas piping and connections for leaks after installing or servicing Correct all leaks...

Страница 16: ...rming show a leak 4 Correct all leaks at once PRESSURE TESTING HEATER GAS CONNECTIONS 1 Open manual shutoff valve see Figure 14 2 Open propane LP supply tank valve 3 Make sure control knob of heater i...

Страница 17: ...e gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician or gas supplier Force or attempted repair may result in a fir...

Страница 18: ...cated behind the heat shield If needed keep pressing ignitor button until pilot lights Note If pilot does not stay lit refer to Troubleshooting pages 21 through 24 Also contact a qualified service per...

Страница 19: ...ctions pages 17 and 18 3 With control knob pressed in strike match Hold match to pilot until pilot lights 4 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release co...

Страница 20: ...your heater could produce increased levels of carbon monoxide If burner flame pattern shows yellow tipping follow instructions at bottom of this page NOTICE Do not mistake orange flames with yellow t...

Страница 21: ...to clean ODS pilot This can damage ODS pilot unit ODS PILOT AND BURNER Use a vacuum cleaner pressurized air or small soft bristled brush to clean CABINET Air Passageways Use a vacuum cleaner or press...

Страница 22: ...e or both of the following A Low gas pressure B Dirty or partially clogged ODS pilot 6 Thermocouple dam aged 7 Control valve damaged 1 Burner orifice is clogged REMEDY 1 Turn on gas supply or open man...

Страница 23: ...gas line 3 Air passageways on heater blocked 4 Dirty or partially clogged burner orifice Continued REMEDY 2 Replace burner orifice 3 Contact local propane LP gas company 1 Contact local propane LP ga...

Страница 24: ...ng statement at top of page 2 Control valve defective 1 Foreign matter be tween control valve and burner 2 Gas leak See Warn ing statement at top of page 1 Not enough combus tion ventilation air OBSER...

Страница 25: ...ater Maximum 14 14 Minimum 11 11 Dimensions Inches H x W x D Heater 23 5 x 25 9 x 8 0 23 5 x 18 5 x 8 0 Carton 26 x 27 75 x 9 63 26 x 20 5 x 9 63 Weight pounds Heater 30 22 Shipping 35 27 When gas pre...

Страница 26: ...support our customer s needs by providing original replacement parts and accessories When calling a Parts Central ask for the Parts Department Baltimore Electric 1348 Dixwell Avenue Hamden CT 06514 1...

Страница 27: ...r accessories from your local dealer If they can not supply these accessories either contact your nearest Parts Central see page 26 or call DESA International s Parts Department at 1 800 972 7879 for...

Страница 28: ...28 101805 1 2 3 4 5 6 7 8 8 9 10 11 12 13 14 15 17 19 21 22 23 24 20 27 26 18 28 16 25 ODS PILOT 10 1 10 2 RP30C...

Страница 29: ...mocouple 1 10 2 098594 01 Ignitor Electrode 1 11 099126 02 Burner 1 12 099387 05 3 16 Pilot Tubing 1 13 098251 03 Injector 1 14 098250 01 Injector Holder 1 15 098867 06 Pressure Regulator 1 16 099553...

Страница 30: ...30 101805 ODS PILOT 12 1 12 2 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 15 16 17 19 27 21 23 24 25 26 22 29 28 20 30 18 CGP18C...

Страница 31: ...S Pilot Assembly 1 12 1 098514 01 Thermocouple 1 12 2 098594 01 Ignitor Electrode 1 13 099120 02 Burner 1 14 099387 05 3 16 Pilot Tubing 1 15 098251 01 Injector 1 16 098250 01 Injector Holder 1 17 098...

Страница 32: ...t This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenan...

Отзывы: