34
FAULT
CAUSE
SOLUTIONS
THE BURNER STOPS
ANOMALOUSLY AND
CASUALLY
LIMIT thermostat cut-in
Check the opening of the flow
directing fins
Check for the absence of
obstructions on air inlet grids
Check fan motor
Burner flame detached
Check the burner setting
Check that the generator doesn’t
work in a depressed room
Room thermostat incorrectly
installed
Check that the room thermostat
sensor is not installed on the hot air
outlet
LIMIT THERMOSTAT CUT-IN
Obstruction on the air circuit
Check the opening of the flow
directing fins
Check for the absence of
obstructions on air inlet grids
Hot air recirculation
Check the opening of the flow
directing fins so that it can be
excluded a hot air recirculation from
outlet to inlet
Check the air inlet temperature
To be verified or out of order fan
Check that the fan wheel is clean
Check the fan motor efficiency
Check the state and the tension of
the belts (for three-phase versions)
Verify an eventual anomalous cut-in
of the fan motor thermal protection
(for three-phase versions)
Excessive thermal power
Check the burner setting
FAN MOTOR THERMAL
PROTECTION CUT-IN (FOR
THREE-PHASE VERSIONS)
Excessive fan motor electric
absorption and/or heating
Check that the air diffusion plenum
is mounted
Check the electricity supply voltage
Check the air inlet temperature
THE FAN DOESN’T START
WITHIN ABOUT A MINUTE
FROM THE STARTING OF
THE BURNER
Insufficient thermal power
Check the burner setting
To be verified or out of order
FAN-LIMIT dual thermostat
Check FAN index setting
Replace the FAN-LIMIT dual
thermostat