WARNING
!
Use only kerosene or No. 1 fuel oil to avoid risk of fire or
explosion. Never use gasoline, naphtha, paint thinners,
alcohol, or other highly flammable fuels.
Do not use heavy fuels such as No. 2 fuel oil or No. 2 Diesel. Using heavy fuels
will result in:
• clogged fuel filter and nozzle
• carbon build up on spark plug
• the need of non-toxic anti-icer in fuel during very cold weather
IMPORTANT:
Use a KEROSENE ONLY storage container. Be sure storage
container is clean. Foreign matter such as rust, dirt, or water will cause the flame-
out control to shut down heater. Foreign matter may also require you to clean fuel
system often.
FUELS
WARNING
!
VENTILATION
Follow the minimum fresh, outside air ventilation
requirements. If proper fresh, outside air ventilation is not
provided, carbon monoxide poisoning can occur. Provide
proper fresh, outside air ventilation before running heater.
Provide at least a three-square-foot opening of fresh, outside air for each 100,000
Btu/Hr rating. Provide extra fresh air if more heaters are being used.
Example:
A 55,000 Btu/Hr heater requires one of the following:
• a two-car garage door (16 feet wide opening) raised two inches
• a single-car garage door (9 feet wide opening) raised three inches
• two, windows (30 inches wide opening) raised five inches
OPERATION
WARNING
!
Review and understand the warnings in the Safety Informa-
tion Section, pages 2 and 3. They are needed to safely
operate this heater. Follow all local codes when using this
heater.
To Start Heater
1. Follow all ventilation and safety information.
2. Fill fuel tank with kerosene or No. 1 fuel oil.
3. Attach fuel cap.
4. Plug power cord of heater into three-prong, grounded extension cord. Exten-
sion cord must be at least six feet long.
Extension Cord Wire Size Requirements
6 to 10 feet long, use 18 AWG rated cord
11 to 100 feet long, use 16 AWG rated cord
101 to 200 feet long, use 14 AWG rated cord
Continued