background image

QUICK START GUIDE , ELITEpro SP™ and ELOG™ 14 SOFTWARE 

(cont.) 

4.

  

Send the Setup Table to the ElitePro SP. 

a)  Once your setup table is successfully saved, click on the "Send Setup Table to Logger" button. 

b)  Select Overwrite ACTIVE Table. ELOG 15 automatically initiates logging when a Setup Table is 

downloaded to the Logger. 

c)

  

At the prompt, select Continue Logging if you have already installed or are about to install the 

logger.  Note that logging will not occur unless its voltage leads are connected to a load or a power 

transformer is used (see Appendix B, “ElitePro SP Power Source” on page 6 for more information). 

ElitePro SP Field Installation 

This step can be completed before or after creating and uploading the Setup Table covered in the previous 

section. 

1.

  

Make the voltage connections between the logger and load as needed using the voltage leads provided 

(L1, L2, L3, and N). Note that typically, the logger is powered by voltage provided to L1 and L2 when 

connected to the load being monitored.  See Appendix B, "ElitePro SP power source" at the end of this 

document for more information. 

2.

  

Attach the current transducers (CTs) to the conductors of the load you are measuring. Orient the CT 

properly with respect to the load.  For clamp-on or flexible CTs, the arrow on the CT case points 

towards the load. For split-core CTs with a removable leg, ensure the label that says “This Side Toward 

Source” faces away from the load. 

3.

  

Connect the CT leads to the ElitePro SP Phoenix-style screw connectors. Note that the high (+) wire of 

the CT (the white, banded, or numbered wire depending on CT type) should go to the left (+) screw 

terminal of each channel input.  If you are using Dent RoCoil (blue flexible coil) CTs, be sure to 

connect the shield wires from all CTs to the shield terminal. This reduces interference and improves the 

accuracy of the CT. See illustration below for typical Dent RoCoil connections. 

Example showing two properly wired Dent RoCoil CT’s (voltage leads not yet installed) 

4.

  

Attach the CTs to the load conductors that correspond to the voltage connections made in step 1.  For 

example, the CH1 CT must attach to the conductor whose voltage is being monitored by L1.  A helpful 

diagram illustrating wiring can be viewed in the ELOG setup table screen by clicking "View typical 

setup" (see previous section for more information). 

Verify Proper Configuration and Installation 

Page 5 

Содержание ELITEpro ELOG 15

Страница 1: ...ing issues please contact the Tool Lending Library for support ElitePro SP SAFETY SUMMARY DENT ElitePro SP loggers and any tools borrowed from the Tool Lending Library that are to be connected to a power source of 12V or more must be installed by a licensed qualified electrician The ElitePro SP is a 600 Volt Over Voltage Category III device DO NOT EXCEED 600V Phase to Phase This logger is equipped...

Страница 2: ...TING ELITEPRO SP DRIVER INSTALLATION at the end of this guide Firmware update if needed After the installation is complete logger firmware should be current and you should be ready to configure and install the ELITEPro SP logger and CTs However after connecting the logger if the message below appears you need a firmware update 1 Click YES and follow the prompts to install the firmware update you m...

Страница 3: ...sessions the following items must be completed 1 Current transducers CTs must be connected to one or more of the channel inputs 2 Line voltage connections must be made both for measurement purposes and to power the ElitePro SP 3 A Setup Table that tells the meter how and what to measure must be created in the ELOG software and loaded into the ElitePro SP NOTE To complete this Quick Start you do no...

Страница 4: ...t corresponds with the nominal rating of the CTs in Amps which is printed on the CT See below if you are using more than one CT value If you are using Dent s RoCoil blue flexible coil CTs be sure to make that selection here no Amperage value is entered for RoCoil CTs Click OK e Optional Change the label in the Setup Table Name if desired f Set the Data Interval to the desired logging interval g Ma...

Страница 5: ...Attach the current transducers CTs to the conductors of the load you are measuring Orient the CT properly with respect to the load For clamp on or flexible CTs the arrow on the CT case points towards the load For split core CTs with a removable leg ensure the label that says This Side Toward Source faces away from the load 3 Connect the CT leads to the ElitePro SP Phoenix style screw connectors No...

Страница 6: ...on step above disconnect the logger by clicking Logger Communication Terminate Connection Then remove the USB cable from the logger and remove the PC from the monitoring location Close exposed service panels and perform all other safety measures before leaving the site Post monitoring logger and data retrieval 1 Retrieve and View Logger Data a At the end of the monitoring period remove the logger ...

Страница 7: ...rom a list or specific location Advanced and click Next 8 In the next window select Search for driver software in this location and Include this location in the search Choose Browse and locate the ElitePro SP driver folder in the ELOG 15 directory This will be C Program Files DENT ELOG ESP Driver or something similar 9 Click Next and the ElitePro SP driver will install In the event that you receiv...

Отзывы: