background image

QUICK START GUIDE , ELITEpro SP™ and ELOG™ 14 SOFTWARE 

This 

QUICK START GUIDE 

is recommended for those that have experience with DENT Instruments or are 

familiar with power measuring products and procedures. For complete operation information, please refer to 

the comprehensive help feature available inside the ELOG 15 application after it is installed. 

IMPORTANT: 

  

DO NOT CONNECT THE ELITEPRO SP TO YOUR COMPUTER UNTIL AFTER YOU HAVE

  

INSTALLED ELOG 15.

  

  

Please note 

ELOG 14 and earlier releases are obsolete, and must be replaced with ELOG 15

There is no need to uninstall any previous version of ELOG before installing ELOG 15. 

  

This software runs on 32 or 64 bit versions of Microsoft Windows® 7 through 10 or Windows® Vista 

Operating Systems. 

  

If you have followed this guide and are still experiencing issues, please contact the Tool Lending 

Library for support. 

ElitePro SP SAFETY SUMMARY 

  

DENT ElitePro SP loggers, and any tools borrowed from the Tool Lending Library that are to be 

connected to a power source of 12V or more, 

must be installed by a licensed, qualified electrician

  

The ElitePro SP is a 600 Volt Over Voltage Category III device. 

DO NOT EXCEED 600V Phase to 

Phase

. This logger is equipped to monitor loads up to 600V. Exceeding this voltage will cause damage 

to the logger and danger to the user.  Always use a Potential Transformer (PT) for loads in excess of 

600V. 

  

USE ONLY SHUNTED CURRENT TRANSDUCERS (CTs) 

with a 333mV maximum output only. 

Serious shock hazard and logger damage can occur if unshunted CTs are used. The Tool Lending 

Library only provides shunted CTs. 

  

Because the ElitePro SP uses load voltage to power the logger, the load should be de-energized when 

installing the logger's voltage leads to the load to reduce the risk of electrical shock during installation. 

Page 1 

Содержание ELITEpro ELOG 15

Страница 1: ...ing issues please contact the Tool Lending Library for support ElitePro SP SAFETY SUMMARY DENT ElitePro SP loggers and any tools borrowed from the Tool Lending Library that are to be connected to a power source of 12V or more must be installed by a licensed qualified electrician The ElitePro SP is a 600 Volt Over Voltage Category III device DO NOT EXCEED 600V Phase to Phase This logger is equipped...

Страница 2: ...TING ELITEPRO SP DRIVER INSTALLATION at the end of this guide Firmware update if needed After the installation is complete logger firmware should be current and you should be ready to configure and install the ELITEPro SP logger and CTs However after connecting the logger if the message below appears you need a firmware update 1 Click YES and follow the prompts to install the firmware update you m...

Страница 3: ...sessions the following items must be completed 1 Current transducers CTs must be connected to one or more of the channel inputs 2 Line voltage connections must be made both for measurement purposes and to power the ElitePro SP 3 A Setup Table that tells the meter how and what to measure must be created in the ELOG software and loaded into the ElitePro SP NOTE To complete this Quick Start you do no...

Страница 4: ...t corresponds with the nominal rating of the CTs in Amps which is printed on the CT See below if you are using more than one CT value If you are using Dent s RoCoil blue flexible coil CTs be sure to make that selection here no Amperage value is entered for RoCoil CTs Click OK e Optional Change the label in the Setup Table Name if desired f Set the Data Interval to the desired logging interval g Ma...

Страница 5: ...Attach the current transducers CTs to the conductors of the load you are measuring Orient the CT properly with respect to the load For clamp on or flexible CTs the arrow on the CT case points towards the load For split core CTs with a removable leg ensure the label that says This Side Toward Source faces away from the load 3 Connect the CT leads to the ElitePro SP Phoenix style screw connectors No...

Страница 6: ...on step above disconnect the logger by clicking Logger Communication Terminate Connection Then remove the USB cable from the logger and remove the PC from the monitoring location Close exposed service panels and perform all other safety measures before leaving the site Post monitoring logger and data retrieval 1 Retrieve and View Logger Data a At the end of the monitoring period remove the logger ...

Страница 7: ...rom a list or specific location Advanced and click Next 8 In the next window select Search for driver software in this location and Include this location in the search Choose Browse and locate the ElitePro SP driver folder in the ELOG 15 directory This will be C Program Files DENT ELOG ESP Driver or something similar 9 Click Next and the ElitePro SP driver will install In the event that you receiv...

Отзывы: