Door close control parameters: 

4-00 -18.0, 4-01-15.0, 4-02 -6.0, 4-03 -5.0, 4-04-4.0, 4-15-20, 4-22-999.9 

Digital output parameters: 6-00-21, 6-01-22 

Door width tuning process: 1.put door in half position ,after this enter 
parameter 0-12-0, 2-23-1 then give run command ( in this time the door 
open and close completely ) if tuning complete successfully ok .go to step3. 

1.

 

If you get AUE error immediately increase value slightly in 0-17 
parameter  

2.

 

 if you get AUE error after full open and close change the value in 2-
12-1 0r 2   

3.

 

In door width tuning the door close completely first then open ,if the 
door  not open you decrease the value slightly in 0-17 upto opening  

4.

 

If you get PGER error check the encoder direction this you change 
value 2-12-1 or 2 

5.

 

Put 0-12-1, Check door operation by door open and close signals. 

Note: 

how to calculate 0-17 parameter value depends on site  

0-17= 100xsite current (check in drive in constant speed     
running)/2.5amps (drive current) 

For example at 6 Hz speed motor takes 0.5 amps current then  

    0-17=100x0.5/2.5=20+ (3 to 5 extra) =23 or 25 

Note: for reset the drive put parameter 0-02-09 (for restore the parameters 
into default values.) 

if you have any queries please call to 9600073866 

 

 

 

 

 

                                  