Door close control parameters:
4-00 -18.0, 4-01-15.0, 4-02 -6.0, 4-03 -5.0, 4-04-4.0, 4-15-20, 4-22-999.9
Digital output parameters: 6-00-21, 6-01-22
Door width tuning process: 1.put door in half position ,after this enter
parameter 0-12-0, 2-23-1 then give run command ( in this time the door
open and close completely ) if tuning complete successfully ok .go to step3.
1.
If you get AUE error immediately increase value slightly in 0-17
parameter
2.
if you get AUE error after full open and close change the value in 2-
12-1 0r 2
3.
In door width tuning the door close completely first then open ,if the
door not open you decrease the value slightly in 0-17 upto opening
4.
If you get PGER error check the encoder direction this you change
value 2-12-1 or 2
5.
Put 0-12-1, Check door operation by door open and close signals.
Note:
how to calculate 0-17 parameter value depends on site
0-17= 100xsite current (check in drive in constant speed
running)/2.5amps (drive current)
For example at 6 Hz speed motor takes 0.5 amps current then
0-17=100x0.5/2.5=20+ (3 to 5 extra) =23 or 25
Note: for reset the drive put parameter 0-02-09 (for restore the parameters
into default values.)
if you have any queries please call to 9600073866