background image

15

Chapter 3    Operation Panel

No. 

Icon

Description

4

SET

When the word ‘

SET

’ illuminates, it means that the UPS is in 

the setup mode. 
You can set up the following items via the LCD. For how to 
setup, please refer to 

5.5 Setup Mode

.

1. Inverter voltage
2. Inverter frequency
3. Bypass range 
4. Buzzer disable
5. Overload alarm 

5

TEST

1. When the word ‘

TEST

’ flashes, it means that the UPS is 

under test. 

2. When the two words ‘

TEST

’ and ‘

BATT

’ flash together, it 

means that the UPS is under battery test.

6

BATT

1. BATT 

&

 %:

When the above two words illuminate together, it means 
the remaining battery capacity. 

2. BATT 

&

 V: 

When the above two words illuminate together, it means 
battery voltage.

7

LOAD

1. LOAD 

&

 %:

 

When the above two words illuminate together, it means 
how much the total load has occupied the rated capacity.

2. LOAD 

&

 KVA:

When the above two words illuminate together, it means 
how much kVA the total load is. 

3. LOAD 

&

 KW:

When the above two words illuminate together, it means 
how much kW the total load is. 

4. LOAD 

&

 % &   : 

When the above word (

LOAD

), unit (

%

) and icon 

 flash 

together, it means that the UPS has an overload situation.

Содержание UPS102N2000N0B0

Страница 1: ...www deltapowersolutions com Delta UPS Amplon Family User Manual The power behind competitiveness N Series Single Phase 1 2 3 kVA...

Страница 2: ...product Any disposition duplication dissemination reproduction modification translation extraction or usage of this Manual in whole or in part is prohibited without the prior written permission of De...

Страница 3: ...8 3 2 Multi function Buttons 9 3 3 LCD Display 11 3 4 7 Segment Display 14 3 5 Flow Chart of the 7 Segment Display 16 Chapter 4 Rear Panel 18 Chapter 5 Operation Modes 20 5 1 Standby Mode 20 5 2 On l...

Страница 4: ...IV Amplon N Series Chapter 9 Troubleshooting 27 Chapter 10 Maintenance 30 10 1 UPS 30 10 2 Batteries 30 10 3 Fan 31 Appendix 1 Technical Specifications 32 Appendix 2 Warranty 34...

Страница 5: ...e at least 15cm around all sides of the UPS for proper ventilation Connection Warnings z z The UPS must be well grounded due to a possible risk of current leakage z z The installation of upstream and...

Страница 6: ...object into the UPS s slits and openings Do not put beverage containers on or around the UPS z z When an emergency occurs press the OFF button and release it after you hear one beep to turn off the UP...

Страница 7: ...UPS302N2002N0B0 3kVA 72Vdc z z Keep the batteries away from heat sources Do not open or mutilate the batter ies The released electrolyte is harmful to the skin and eyes and may be toxic z z A battery...

Страница 8: ...llation If the UPS needs to be stored prior to installation it should be placed in a dry area The allowable storage temperature is between 15 C and 50 C 5 F 122 F z z After usage Press the button make...

Страница 9: ...d its efficiency in on line mode can reach at maximum 93 The UPS not only pro vides safe reliable and uninterrupted power to your sensitive electronic equipment at all times but also produces greater...

Страница 10: ...all of the accessories using the original packing material that came with the unit z z Standard Model UPS102N2000N0B0 1kVA UPS202N2000N0B0 2kVA UPS302N2000N0B0 3kVA SETUP ON OFF 1 2 3 4 No Item Q ty...

Страница 11: ...B 2 1 PC 6 Battery Wire 1 PC 7 Ring type Thimble 2 2 PCS 8 Joint 2 2 PCS 9 Wire Mount 2 1 PC 1 The terminal copper 3 PCS and cable tie Type A 1 PC are used to connect the UPS output terminals L N loca...

Страница 12: ...uttons 3 1 LED Indicators No LED Description 1 Indicates the output status 1 ON green There is output 2 OFF There is no output 2 1 ON red The UPS detects an internal fault or an environmental fault Yo...

Страница 13: ...powersolutions com en in mcis software center php or configure the SNMP card op tional or ModBus card optional z z For manual battery test please press and hold the button for 3 seconds release it aft...

Страница 14: ...press and hold the button for 3 seconds release it after you hear one beep and the UPS will clear the fault condition and return to standby bypass mode Besides the LCD will show the relevant error co...

Страница 15: ...he unit operate in on line mode 3 OFF The AC input is out of the acceptable bypass range and is not sufficient to let the unit operate in on line mode 2 Output Icon Indicates the output status 1 ON Th...

Страница 16: ...he 7 segment display Please refer to the following table for each error code and refer to 3 4 7 Segment Display for relevant 7 segment display information Error Code Meaning E11 Charger Fault E13 Temp...

Страница 17: ...vel Bar Graph Indicates the status of battery level 1 ON The bar graph illuminates according to the re maining battery capacity 1 2 Flashing The bar graph flashes when a low battery situation occurs N...

Страница 18: ...Icon Description 1 IN 1 IN V When the above two words illuminate together it means input voltage 2 IN Hz When the above two words illuminate together it means input frequency 2 OUT 1 OUT V When the a...

Страница 19: ...ans that the UPS is under battery test 6 BATT 1 BATT When the above two words illuminate together it means the remaining battery capacity 2 BATT V When the above two words illuminate together it means...

Страница 20: ...3 5 Flow Chart of the 7 Segment Display The following flow chart helps you to understand how to go through each display screen Here we take Standby Mode as an example Each of the display diagrams show...

Страница 21: ...ond to view the next display Press the button for 0 1 second to view the next display Press the button for 0 1 second to view the next display Press the button for 0 1 second to view the next display...

Страница 22: ...5 6 7 8 No Item Functions 1 Mini Slot Accepts a mini SNMP mini Relay I O mini ModBus or mini TVSS card optional 2 Output Sockets Connect to your loads 3 External Battery Pack Connector N A The UPS can...

Страница 23: ...tem Functions 1 Mini Slot Accepts a mini SNMP mini Relay I O mini ModBus or mini TVSS card optional 2 Output Sockets Connect to your loads 3 External Battery Pack Connector Connects to the external ba...

Страница 24: ...its connected loads 5 3 Bypass Mode In bypass mode the critical loads are directly supplied by the utility power and the batteries are charged 5 4 Battery Mode When the UPS is operating during a powe...

Страница 25: ...e button for 0 1 second to confirm your parameter 4 Press the button for 0 1 second to go to the next setup item 5 You can skip to the next setup item by pressing the button for 0 1 second 6 In setup...

Страница 26: ...Display T 3 seconds T 3 seconds T 0 1S T 0 1S T 0 1S T 3 seconds T 0 1S T 0 1S T 3 seconds T 0 1S T 0 1S T 0 1S T 3 seconds T 0 1S T 0 1S T 0 1S T 3 seconds T 0 1S T 0 1S T 0 1S Inverter Frequency Se...

Страница 27: ...Start up 1 Verify if the UPS s input cord meets with N L G of the wall socket 2 After the UPS is connected to the AC utility the AC utility supplies power to the UPS The UPS is initially set in STANDB...

Страница 28: ...off and the UPS will transfer to standby bypass mode The UPS will keep charging the batteries when the UPS is in standby bypass mode even though the button has been pressed To fully turn off the UPS i...

Страница 29: ...m beeps once every 2 1 seconds 2 Overload_125 150 The audible alarm beeps once every 0 6 seconds 5 Fault The audible alarm beeps continuously for 5 seconds when the UPS detects an internal fault NOTE...

Страница 30: ...ve ModBus communication function 5 Mini TVSS Card Lets the UPS have surge protection function 6 Charger Board 4A only for Long Backup Model Additionally install the 4A charger board to increase the ch...

Страница 31: ...blem The more detailed description of the problem the better 3 When you see the following problems occur please follow the solutions shown below A About the error codes shown on the 7 segment Display...

Страница 32: ...Output has a short circuit issue 1 Check whether the output has a short circuit issue 2 Contact service personnel Sd1 RPO Shutdown Remote shutdown is executed from dry contact After the remote shutdo...

Страница 33: ...e internal battery cables and connect them firmly 3 Weak Battery Battery Replacement Batteries are damaged or battery life time is due Contact service personnel 4 Abnormal Input when the AC icon is fl...

Страница 34: ...cy High temperature environments and high charging discharging frequency will quickly shorten the battery life The UPS does not require maintenance by the user however the batteries should be checked...

Страница 35: ...please check if each fan works normally and make sure if the ventilation air can move freely around and through the UPS If not contact service personnel NOTE Please ask your local dealer or customer s...

Страница 36: ...Vac 50 100 load Frequency 50 60 Hz 10 Hz Power Factor 0 99 full load iTHD 3 Output Power Factor 0 9 Standard Model 0 8 Long Backup Model Voltage 220 230 240 Vac Voltage Regulation 2 linear load Frequ...

Страница 37: ...48 dBA 48 dBA Display LED indicators LCD display Communication Interfaces MINI Slot x 1 USB Port x 1 Physical Dimensions W D H 145 x 320 x 225 mm 190 x 390 x 325 mm 190 x 390 x 325 mm Weight Standard...

Страница 38: ...ge maintenance or irresistible force i e war fire natural disaster etc and this warranty also expressly excludes all incidental and consequential damages Maintenance service for a fee is provided for...

Страница 39: ......

Страница 40: ...5013231700...

Отзывы: