FAULT
Message
Possible cause
Action
DC
Injection
(F01, F02,
F03)
1. Utility waveform is abnormal
2. Detection circuit malfunction
1. Check the utility waveform.
Grid connection of inverter need to be
far away from non-linear load if necessary
2. Check the detection circuit inside the
inverter
Temperature
(F05)
1. The ambient is over 60
℃
(The installation is abnormal)
2. Detection circuit malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter
Temperature
(F07)
1. Ambient temperature is
<-30
℃
2. Detection circuit malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter
HW NTC1
Fail
(F06)
1. Ambient temperature
>90
℃
or <-30
℃
2. Detection circuit malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter
HW NTC2
Fail
(F08)
1. Ambient temperature
>90
℃
or <-30
℃
2. Detection circuit malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter
HW NTC3
Fail
(F09)
1. Ambient temperature
>90
℃
or <-30
℃
2. Detection circuit malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter
HW NTC4
Fail
(F10)
1. Ambient temperature
>90
℃
or <-30
℃
2. Detection circuit malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter
HW RLY
(F13)
1. Driver circuit for relay is
defective
2. Relay(s) is defective
3. Detection circuit malfunction
(Inverter voltage)
1. Check the input voltage, must >150Vdc
2. Replace the defective relay
3. Check the detection circuit inside the
inverter
HW DSP
ADC1
(F15)
1. Insufficient input power
2. Auxiliary power circuitry
malfunction
3. Detection circuit malfunction
1. Check the input voltage, must >150Vdc
2. Check the auxiliary circuitry inside the
inverter
3. Check the detection circuit inside the
inverter
59
Error message and Trouble Shooting
Содержание RPI M50A 12s
Страница 2: ......
Страница 75: ...RPI M50A_12s The power behind competitiveness www deltaww com English 1 75 149...
Страница 81: ...81...
Страница 83: ...2 1 RPI M50A 2 1 2 2 2 1 2 2 1 2 2 83...
Страница 84: ...2 2 M50A RPI M50A 1 1 pc 1 pc 1 pc 1 pc RPI 2 3 AC AC 4 5 1 5mm x 4 6 DC 12 DC 2 1 M50A 1000V 1A Midget 84...
Страница 85: ...2 3 2 3 RPI503M221000 DC RPI M50A_12s 2 2 2 3 85...
Страница 88: ...3 2 90 Not Recommended Not Recommended Keep 30 cm from floor and water if installed this way 88...
Страница 89: ...3 3 3 4 14 30 3 30 97 8 192 8 129 M6 Screw 6 M6 Screw 6 Wall 89...
Страница 90: ...3 5 3 5 25 60 3 6 30cm 20cm 50cm 30cm 30cm 90...
Страница 91: ...M50A DC 15A DC 10A 4 1 MC4 DC AC DC DC insulation 5 2 7 Install Settings 4 4 1 DC OFF E34 L1 L2 L3 N 91...
Страница 93: ...M50A M50A Note for Field Wiring M50A 16A 4 2 4 1 4 2 RPI M50A_12s 16A 93...
Страница 95: ...4 3 AC AC AC 95mm 22 2mm L1 L2 L3 N PE 22 2mm 95 mm 0 5 95...
Страница 96: ...AC 4 4 AC Plug 4 4 1 2 3 4 5 96...
Страница 98: ...1 AC AC 55kgf cm 75kgf cm 2 A B 3 B B D 4 4 4 L1 L2 L3 N PE D1 D2 D3 L1 L2 N PE L3 A B C C D D A B C D 98...
Страница 99: ...O 5 3 3N M 6 A B B 7 4 4 B D 38 2CV 25 12N m 99...
Страница 102: ...4 7 RPI M50A 4 7 VCC RS 485 20 AWG 0 5mm 4 4 Dry Contact VCC RS 485 EPO 1 Digital Inputs 6 Terminal Resistor 102...
Страница 106: ...4 11 4 4 3 RPI M50A 2 5 2 7 5 Dry Contact 250Vac 28Vdc 9A 20 AWG 0 5mm Dry Contact B Dry Contact A 106...
Страница 124: ...RPI M50A_12s AC DC PV Inverter 6 6 1 SPD AC DC SPD Fail 1 AC DC 2 6 1 3 6 2 4 6 3 5 SPD 6 4 6 7 8 6 1 10Kgf cm 124...
Страница 125: ...6 1 6 2 125...
Страница 126: ...6 3 6 4 SPD 8 Kgf cm 0 8N m 126...
Страница 128: ...6 6 6 7 6 7 6 3 10 Kgf cm 1N m 128...
Страница 129: ...6 8 6 9 6 9 4 6 5 6 4 8 Kgf cm 0 8N m 8 Kgf cm 0 8N m 129...
Страница 136: ...8 Manual Switch OFF AC voltmeter AC DC AC DC RS 485 136...
Страница 145: ...IV 1000Vdc A I V A I V curve limitation 145 A I V curve limitation...
Страница 148: ......
Страница 149: ...RPI M50A_12s The power behind competitiveness www deltaww com English 1 75 149...
Страница 155: ...155...
Страница 157: ...2 1 RPI M50A 2 1 2 2 2 1 2 2 1 2 2 157...
Страница 158: ...2 2 M50A RPI M50A 1 1 pc 1 pc 1 pc 1 pc RPI 2 3 AC AC 4 5 1 5mm x 4 6 DC 12 DC 2 1 M50A 1000V 1A Midget 158...
Страница 159: ...2 3 2 3 DC 2 2 2 3 RPI503M221000 RPI M50A_12s 159...
Страница 162: ...3 2 90 Not Recommended Not Recommended Keep 30 cm from floor and water if installed this way 162...
Страница 163: ...3 3 3 4 14 30 3 30 97 8 192 8 129 M6 Screw 6 M6 Screw 6 Wall 163...
Страница 164: ...3 5 3 5 25 60 3 6 30cm 20cm 50cm 30cm 30cm 164...
Страница 165: ...M50A DC 15A DC 10A 4 1 MC4 DC AC DC DC insulation 5 2 7 Install Settings 4 4 1 DC OFF E34 L1 L2 L3 N 165...
Страница 167: ...M50A M50A Note for Field Wiring M50A 16A 4 2 4 1 4 2 RPI M50A_12s 16A 167...
Страница 169: ...4 3 AC AC AC L1 L2 L3 N PE 22 2mm 95 mm 0 5 95mm 22 2mm 169...
Страница 170: ...AC 4 4 AC Plug 4 4 1 2 3 4 5 170...
Страница 172: ...1 AC AC 55kgf cm 75kgf cm 2 A B 3 B B D 4 4 4 L1 L2 L3 N PE D1 D2 D3 L1 L2 N PE L3 A B C C D D A B C D 172...
Страница 173: ...O 5 3 3N M 6 A B B 7 4 4 B D 38 2CV 25 12N m 173...
Страница 176: ...4 7 RPI M50A 4 7 VCC RS 485 20 AWG 0 5mm 4 4 Dry Contact VCC RS 485 EPO 1 Digital Inputs 6 Terminal Resistor 176...
Страница 180: ...RPI M50A 2 5 2 7 5 Dry Contact 250Vac 28Vdc 9A 20 AWG 0 5mm 4 11 Dry Contact A Dry Contact B 4 4 3 180...
Страница 198: ...RPI M50A_12s AC DC PV Inverter 6 6 1 SPD AC DC SPD Fail 1 AC DC 2 6 1 3 6 2 4 6 3 5 SPD 6 4 6 7 8 6 1 10Kgf cm 198...
Страница 199: ...6 1 6 2 199...
Страница 200: ...6 3 6 4 SPD 8 Kgf cm 0 8N m 200...
Страница 202: ...6 6 6 7 6 7 6 3 10 Kgf cm 1N m 202...
Страница 203: ...6 8 6 9 6 9 4 6 5 6 4 8 Kgf cm 0 8N m 8 Kgf cm 0 8N m 203...
Страница 210: ...8 Manual Switch OFF AC voltmeter AC DC AC DC RS 485 210...
Страница 219: ...IV 1000Vdc A I V A I V curve limitation 219 A I V curve limitation...
Страница 222: ......
Страница 223: ......
Страница 224: ...Version 06190528 5013237005...