RMC200 Startup Guide
36
Delta Computer Systems, Inc.
CPU40, CA4, CV8: Discrete I/O
CPU40:
2 discrete inputs, 2 discrete outputs
CA4:
4 discrete inputs (Fault), 4 discrete outputs (Enable)
CV8:
8 discrete I/O, individually configurable as inputs or outputs
The CPU40, CA4, and CV8 discrete inputs and outputs are individually
isolated.
Discrete Inputs
Apply 12-24 V to the input. The polarity can be positive or negative.
Max current draw is 3 mA.
Used with a sourcing output
Used with a sinking output
Discrete Outputs
The discrete outputs are solid state relays. Outputs can be wired in
either a high-side or low-side configuration.
Outputs
On Impedance
15
Ω max
.
Max Current
75 mA
Max Voltage
30 V
RMC Module
Resistive
load
+VCC (12-24 VDC)
DOut +
DOut -
RMC Module
+VCC (12-24 VDC)
DOut +
DOut -
Resistive
load
RMC Module
In+
In -
PLC
+VCC (12-24 VDC)
DOut +
DOut -
PLC
RMC Module
In+
In-
Power
Output
(24VDC)