background image

Instruction Manual

PMU-13V155WL

A

1.  Safety Instructions

• 

Must select correct AC input voltage range through selectable switch before turning on (Refer to 

Fig. 1, 

).

• 

To  ensure  sufficient  convection  cooling,  always  maintain  a  safety  distance  of  ≥  20mm  from  all 

ventilated surfaces while the device is in operation.

• 

For safety reasons, please ensure the mounted device is kept at ≥ 7mm safety distance at the top 

and left side from other components and equipments (Refer to Fig. 2).

• 

The  device  is  not  recommended  to  be  placed  on  low  thermal  conductive  surface,  for  example, 

plastics.

• 

Note that the enclosure of the device can become very hot depending on the ambient temperature 

and load of the power supply. Do not touch the device while it is in operation or immediately after 

power is turned OFF. Risk of burning!

• 

Do not touch the terminals while power is being supplied. Risk of electric shock.

• 

Prevent any foreign metal, particles or conductors to enter the device through the openings during 

installation. It can cause: Electric shock; Safety Hazard; Fire; Product failure

• 

Battery need to be protected from short circuit while installation & servicing. Danger of explosion.

• 

Signal cable should not interact with AC Input.

• 

Warning: When connecting the device, secure Earth connection before connecting L and N. When 

disconnecting the device, remove L and N connections before removing the Earth connection.

2.  Device Descriptions

Refer to Fig. 1.:

 

Input & Output terminal block connector

 

DC voltage adjustment potentiometer (12V - 14V)

 

Green  LED  ON  =  DC  OK  (Normal  operation  through  mains  supply  or  through  battery  when 

operating in buffering mode)

 

մ

Red LED ON       = Battery reverse polarity

 

յ

Battery charging current adjustment potentiometer (Factory Setting: 1A)

Max charging current shall not exceed 1.5A (Refer to Fig. 1, 

). 

 

ն

AC selectable switch

 

Signal connector

 - JST: XHP-4 (for PMU-13V155WLCA only)

3.  Installation of the Device

Refer to Fig. 3.: 

 

Mounting holes for the power supply assembly onto the mounting surface. The power supply shall 

be mounted on minimum 2 mounting holes using M3 screw minimum 5mm length.

 

This surface belongs to customer’s end system or panel where the device is mounted.

 

Connector

• 

Use flexible cable (stranded or solid), AWG No. 16-14. 

• 

The torque at the Connector shall not exceed 13 Kgf.cm. The insulation stripping length should not 

exceed 0.275” or 7mm (Refer to Fig. 4).

4.  Battery Information

Battery Capacity

3.2AH - 15AH

Battery Cut-off Voltage

10V ± 1V

Battery Low (Deep Discharge) Detection*

7V ± 1V

*If the battery is deep discharged, the power supply will not recognize the battery. 

5.  Installation of Mounting Accessories

Refer to Fig. 5.:

• 

Only use M3 screw ≤ 2.5mm through the base mounting holes. This is to keep a safety distance 

between the screw and internal components.

• 

Recommended mounting tightening torque: 4~8 Kgf.cm.

www.DeltaPSU.com

REV.00

Fig. 1. Device Descriptions

Fig. 4. Wire Type

Fig. 5. Mounting Screw

Lug

Stripped wire

Mounting

accessories

Mounting

screw

Chassis of 

the device

2.5mm

max.

7 mm

Side Mounting (Vertical)

Base Mounting (Vertical)

Side Mounting (Horizontal)

A

B

C

A

C

B

A

B

C

A

B

C

A

C

B

A

B

C

A

B

C

A

C

B

A

B

C

Fig. 3. Mounting Orientation

Signal connector - JST: XHP-4

(for PMU-13V155WLCA only)

7

Base surface

Side surface

1

2

7

3

5

4

6

Fig. 2. Assembly Reference

≥ 

7mm

CN1

PSU

CN1

≥ 

7mm

PSU

TOP SIDE

LEFT SIDE

LEFT

TOP

Pin No.

1

2

3

4

DC OK

Low Battery

GND

AC OK

Description

400mm.(Ref.)