PJH-36V300WB

www.DeltaPSU.com

REV.00

Instruction Manual

0

30

60

90

120

150

180

210

240

270

300

-25 -20 -15 -10 -5

0

5

10 15 20 25 30 35 40 45 50 55 60 65 70

Output Power ( W )

Surrounding Air Temperature 

(

o

C)

Forced Air

Convection

Convection

�, �

Fig. 4. Power Derating Curve

Fig. 5. Installation of Forced Air

5.    Connection

4.    Power Derating Curve (

Refer to Fig .4)

Power Supply Header

Mating Connector

Terminal

AWG

Input (CN1)

JST

B2P3-VH(LF)(SN)

VHR-3N

SVH-21T-P1.1

18

Standby (CN101)

BM10B-SRSS-TB(LF)(SN)

SHR-10V-S

SSH-003T-P0.2

32-28

Input (CN1)

Molex

26-62-4030

26-03-3031

6838 Series

18

Standby (CN101)

104141-1010

104142-1000

104539-8002

32-30

Input (CN1

JWT

A3963WV2-3P-D

A3963H02-3P

A3963T0P-2

18

Standby (CN101)

A1002WV0-10PS-5E

A1002H00-10P-66

A1002TOP-2

36-28

Output (CN102, CN103)

-

TERMINAL M3 x 0.5

-

-

16-10

6.   Installation of Forced Air 

(Refer to Fig. 5)

►  To ensure sufficient air flow, always maintain a distance and air flow direction as recommended in Fig. 5. 

 

while the device is in operation.

Forced Air: 10CPM Forced Air

 

All orientations

> 50°C de-rate power by 2.5% / °C

(300W @ 50°C, 225W @ 60°C, 150W @ 70°C)

 

 

Convection

 

Ⓐ, Ⓑ 

orientations

 

> 45°C de-rate power by 1.5333% / °C

(240W @ 45°C, 171W @ 60°C, 125W @ 70°C)

For 

 

orientations, ensure sufficient convection 

cooling, always maintain a distance of ≥ 30mm below 

the device while the device is in operation.

Ⓔ 

orientations

> 50°C de-rate power by 1.9165% / °C

(240W @ 50°C, 180W @ 60°C, 125W @ 70°C)

PJH-36V300WBC

(y)

PJH-36V300WBB

(y)

Forced air cooling

300W = 36V/8.3A. 12V/0.5A
150W = 36V/4.2A. 12V/0A

300W = 36V/8.3A. 5V/1.2A
150W = 36V/4.2A. 5V/0A

Convection cooling

240W = 36V/6.6A.   12V/0.25A
125W = 36V/3.47A. 12V/0A

240W = 36V/6.6A.   5V/0.6A
125W = 36V/3.47A. 5V/0A