Safety Instructions

DANGER  

Electric shock

Potentially fatal voltages are present in the 

inverter during operation. When the inverter 

is disconnected from all power sources, this 

voltage remains in the inverter for up to 60 

seconds. 

You should therefore always carry out the fol-

lowing steps before working on the inverter:
1.  Turn both DC isolating switches to the 

OFF 

position.

2.  Disconnect the inverter from all AC and 

DC voltage sources and make sure that 

none of the connections can be restored 

accidentally.

3.  Wait at least 60 seconds for the internal 

capacitors to discharge.

DANGER  

Electric shock

Potentially fatal voltages are present at the 

DC connections of the inverter. When light 

falls on the solar modules, they immediately 

start to generate electricity. This also hap-

pens when light does not fall directly on the 

solar modules.

 

Never disconnect the inverter from the 

solar modules when it is under load. 

 

Turn both DC isolating switches to the 

OFF 

position.

 

Disconnect the connection to the grid so 

that the inverter cannot feed energy into 

the grid. 

 

Disconnect the inverter from all AC and 

DC voltage sources. Make sure that 

none of the connections can be restored 

accidentally.

 

Ensure that the DC cables cannot be 

touched accidentally.

DANGER  

Electric shock

The inverter has a high leakage current 

value.

 

Always

 connect the ground cable first, 

then the AC and DC cables.

WARNING

Electric shock

The IP66 protection degree is no longer 

guaranteed when the door is open.

 

Only open the door when absolutely 

necessary.

 

Do not open the door if water or dirt might 

enter the inverter. 

 

After work is completed, ensure that the 

door is properly shut and tightened again. 

Check that the door is properly sealed.

WARNING

Heavy weight

The inverter is heavy.

 

Lift and carry the inverter with at least two 

people, or use a suitable lifting device.

WARNING

Hot surfaces

The surface of the inverter can get very hot 

during operation. 

 

Always wear safety gloves when touching 

the inverter.

NOTICE

Use of aluminum cables

 

Always observe the applicable regulations 

and rules for the use of aluminum cables. 

For detailed information, refer to the com-

plete Installation and Operation Manual.

NOTICE

Working in freezing conditions

In freezing conditions, the rubber seal on the 

front door can freeze to the housing and tear 

when opened. 

 

Before opening the front door, defrost the 

rubber seal with some warm air.

 

To comply with IEC 62109-5.3.3 safety requirements 

and avoid injury or material damage, the inverter 

must be installed and operated in accordance with 

the safety and operating instructions set out in this 

manual. Delta Electronics is not responsible for 

damage resulting from failure to follow the safety 

and operating instructions set out in this manual.

 

The inverter may only be installed and commis-

sioned by installers who have been trained and 

approved for the installation and operation of grid-

connected solar inverters.

 

All repair work on the inverter must be carried out 

by Delta Electronics. Otherwise the warranty will be 

void.

Содержание M100A 280

Страница 1: ...inverter M100A_280 Delta part number RPI104M280000 product version 0 European Union Graphical Installation Guide Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1 0 EN 2022...

Страница 2: ...nstallers who are trained and approved for installation and com missioning of grid connected solar inverters The information in this manual is to be treated as con fidential and no part of this manual...

Страница 3: ...00 1000Vdc MPPT 390 900Vdc MAX Idc 26A 6 MPPT 1000Vdc max MAX Idc 50A 6 MPPT 220 380Vac 230 400Vac 3P4W 3P3W 50 60Hz 83 4A max cos 0 8ind 0 8 cap 50kW 50kVA nom 50kW 55kVA max IP Code IP66 Product ver...

Страница 4: ...and DC cables WARNING Electric shock The IP66 protection degree is no longer guaranteed when the door is open Only open the door when absolutely necessary Do not open the door if water or dirt might...

Страница 5: ...lightning strikes follow the applicable regulations in your country All external connections must be sufficiently sealed in order to ensure an IP66 protection degree Seal any unused connections with...

Страница 6: ...INV I 1x 6 Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1 0 EN 2022 01 03 1x MOU H INV Q 1x INV X 1x Scope of Delivery Do not use any damaged components...

Страница 7: ...Guide M100A_280 RPI104M280000 Product Version 0 EU V1 0 EN 2022 01 03 Scope of Delivery Amphenol H4 4 6 mm2 DC H4CFC4D MS DC P 16x Amphenol H4 4 6 mm2 DC H4CMC4D MS DC P 16x 6x DC B 2x DC T DC AC AC...

Страница 8: ...sories and software Accessories must be ordered separately 2x MOU G Delta Service Software DSS DOWNLOAD partnerportal delta emea com en portal login htm Windows PC RS485 USB Adapter 0 25 1 5 mm2 A Win...

Страница 9: ...60 seconds after the power supply is disconnected Before working on the inverter read the supplied manual and follow the instructions provided The housing of the inverter must be grounded if local re...

Страница 10: ...10 Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1 0 EN 2022 01 03 Dimensions 82 82 82 410 82 82 460 11 31 17 27 20 95 25 595 263 4 max 1 8 699 144 5 629 538 7 6 5 mm...

Страница 11: ...11 Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1 0 EN 2022 01 03 Sub 1G 739 80 mm 340 310 130 75 15 12 5 60 60 mm Dimensions...

Страница 12: ...300 300 600 200 200 150 12 Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1 0 EN 2022 01 03 P UV 2020 2021 2022 2023 2024 Installation...

Страница 13: ...300 300 200 200 150 200 300 600 830 380 A A 50 300 300 200 A A 13 Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1 0 EN 2022 01 03 Installation...

Страница 14: ...14 Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1 0 EN 2022 01 03 Wall mounting 8 x 6 5 mm A1 A2 77 kg 8 5 mm 10 Nm 8 5 mm 10 Nm A3 A4 A5 A6...

Страница 15: ...15 Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1 0 EN 2022 01 03 Floor mounting 13 mm 24 5 Nm 13 mm 77 kg B1 B2 B3 B4...

Страница 16: ...16 Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1 0 EN 2022 01 03 SWITCH 1 OFF OFF ON ON SWITCH 2 1 2 3 4 5 6 Mounting...

Страница 17: ...17 Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1 0 EN 2022 01 03 Communication card RS485...

Страница 18: ...2 VCC GND DATA DATA DATA DATA RS485 CAT5 CAT6 7 2 8 0 10 0 mm 0 25 1 5 mm2 1 1 RS485 terminal block 2 DIP switch for RS485 termination resistor Switch on the RS485 terminator resistor of the data log...

Страница 19: ...T6 7 2 8 0 10 0 mm 0 25 1 5 mm2 3 Digital inputs Pin Pin V1 K0 External power off EPO K1 V1 K1 Pmax 0 K2 V1 K1 Pmax 30 K3 V1 K1 Pmax 60 K4 V1 K1 Pmax 100 K5 Reserved K6 Reserved Digital inputs Dry con...

Страница 20: ...ide M100A_280 RPI104M280000 Product Version 0 EU V1 0 EN 2022 01 03 Connect a PC VCC GND DATA DATA DATA DATA RS485 RS485 USB Adapter Delta Service Software DSS Windows PC Connect the PC to the inverte...

Страница 21: ...1 57 65 mm 15 Nm 5 5 2 0 mm D4 1 45 57 mm 15 Nm 5 5 0 mm D5 1 33 45 mm 15 20 Nm 4 5 0 mm P AC C1 AC C2 D0 D1 1 D2 1 D2 2 D2 3 D1 2 D1 3 D1 4 AC C2 d mm M Nm P mm D2 1 25 28 mm 15 20 Nm 6 5 2 0 mm D2...

Страница 22: ...E Al se Cu Al re rm se 70 240 mm2 70 240 mm2 30 mm L1 L2 L3 N a b c PE a b c M8 24 mm 8 4 mm 12 5 mm M10 40 mm 11 mm 22 mm AC C1 AC PE 22 Graphical Installation Guide M100A_280 RPI104M280000 Product V...

Страница 23: ...henol H4 4 6 mm2 DC H4CFC4D MS DC P 16x Amphenol H4 4 6 mm2 DC H4CMC4D MS DC P 16x DC B 1 2 23 Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1 0 EN 2022 01 03 Connecting t...

Страница 24: ...ct Version 0 EU V1 0 EN 2022 01 03 The inverter must be supplied with alternating current grid and or direct current solar modules Commissioning SWITCH 1 OFF OFF ON ON SWITCH 2 Delta Service Software...

Страница 25: ...25 Graphical Installation Guide M100A_280 RPI104M280000 Product Version 0 EU V1 0 EN 2022 01 03...

Страница 26: ...nal voltage 5 380 400 480 V 20 30 3 phases PE 3 phases N PE Y Nominal current 160 A Maximum current 168 A at 380 400 V 133 A at 480 V Frequency range 5 50 60 Hz 5 Hz Adjustment range power factor 0 8...

Страница 27: ...ad behavior Current limitation power limitation Safety IEC 62109 1 2 CE compliance EMC EN 61000 6 2 6 3 3 11 3 12 Noise immunity IEC 61000 4 2 3 4 5 6 8 Distortion factor EN 61000 3 2 Voltage fluctuat...

Страница 28: ...00 9323 toll free Great Britain support uk solar inverter com 0800 051 4281 toll free Greece support greece solar inverter com 49 7641 455 549 Israel supporto israel solar inverter com 800 787 920 tol...

Отзывы: