TECHINCAL DATASHEET

 

LYTE DIN Rail Power Supply 

24V 480W 1 Phase / DRL-24V480W1A

□ 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (December 2020, Rev. 05) 

 

9

 

Engineering Data 

Output Load De-rating VS Surrounding Air Temperature 

 

 

 

 

 

 

 

 

Output Load De-rating VS Input Voltage 

 

 

 

 

 

 

Note 

 

1.  Power supply components may degrade, or 

be damaged, when the power supply is 

continuously used outside the shaded region, 

refer to the graph shown in Fig. 1. 

2.  If the output capacity is not reduced when the 

surrounding air temperature exceeds its 

specification as defined on Page 3 under 

“Environment”, the device will run into Over 

Temperature Protection. When activated, 

power supply  will latch off, until the 

surrounding air temperature is lowered or the 

load is reduced as far as necessary to keep 

the device in working condition, and require 

removal/re-application of input AC voltage in 

order to restart. 

3.  In order for the device to function in the 

manner intended, it is also necessary to keep 

a safety distance as recommended in the 

safety instructions while the device is in 

operation.

 

4.  Depending on the surrounding air 

temperature and output load delivered by the 

power supply, the device can be very hot! 

5.  If the device has to be mounted in any other 

orientation, please contact 

[email protected]

 

for more details. 

  No output power de-rating for the  input 

voltage from 100Vac to 264Vac 

Fig. 1  De-rating for Vertical Mounting Orientation 

> 40°C de-rate power by 1.67% / °C @ 115Vac (Test at 115Vac condition) 

> 50°C de-rate power by 2.5% / °C @ 230Vac (Test at 230Vac condition)

 

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Содержание LYTE DRL-24V480W1A Series

Страница 1: ...strial applications without compromising on quality and reliability The convection cooled LYTE series will operate between 20 C to 70 C with full rated power available from 10 C to 50 C at 230Vac The...

Страница 2: ...ltage 24Vdc Factory Set Point Tolerance 24Vdc 2 Output Voltage Adjustment Range 22 28Vdc Output Current 20 0A 480W max Output Power 480W Line Regulation 0 5 85 264Vac 100 load Load Regulation 1 5 0 10...

Страница 3: ...ate power by 2 5 C 230Vac Input Voltage 100Vac de rate power by 1 Vac Operating Humidity 5 to 95 RH Non Condensing Operating Altitude 0 to 5 000 Meters 16 400 ft Shock Test Non Operating IEC 60068 2 2...

Страница 4: ...EN 60950 1 Electrical Safety TUV Bauart EN 60950 1 EN 62368 1 UL cUL recognized UL 60950 1 and CSA C22 2 No 60950 1 File No E131881 UL 62368 1 and CSA C22 2 No 62368 1 File No E131881 CCC GB4943 1 CB...

Страница 5: ...1 150kHz 80MHz 10Vrms Power Frequency Magnetic Fields IEC 61000 4 8 Level 4 Criteria A1 30A m Voltage Dips and Interruptions IEC 61000 4 11 0 of 100Vac 20ms 40 of 100Vac 200ms 70 of 100Vac 500ms 0 of...

Страница 6: ...ified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com December 2020 Rev 05 6 Block Diagram DRL 24V480W1AA DRL 24V480W1AS Downloaded from Arrow com Downloaded from Arrow com Do...

Страница 7: ...connector 2 Output terminal block connector 3 DC OK relay contact for DRL 24V480W1AS only 4 DC voltage adjustment potentiometer 5 DC OK LED Green 6 Universal mounting rail system Dimensions L x W x D...

Страница 8: ...otherwise indicated www DeltaPSU com December 2020 Rev 05 8 L x W x D 123 6 x 85 5 x 128 5 mm 4 87 x 3 37 x 5 06 inch DRL 24V480W1AS Downloaded from Arrow com Downloaded from Arrow com Downloaded fro...

Страница 9: ...to keep the device in working condition and require removal re application of input AC voltage in order to restart 3 In order for the device to function in the manner intended it is also necessary to...

Страница 10: ...st the bottom front side for locking 4 Shake the unit slightly to ensure that it is secured Fig 2 2 Dismounting To uninstall pull or slide down the latch with screw driver as shown in Fig 2 2 Then sli...

Страница 11: ...ecome very hot depending on the surrounding air temperature and load of the power supply Risk of burns The main power must be turned off before connecting or disconnecting wires to the terminals DO NO...

Страница 12: ...lue Inrush Current Inrush current is the peak instantaneous input current measured and occurs when the input voltage is first applied For AC input voltages the maximum peak value of inrush current wil...

Страница 13: ...atch Mode The power supply s overvoltage circuit will be activated when its internal feedback circuit fails The output voltage shall not exceed its specifications as described in Protections section P...

Страница 14: ...ote that output voltage Vout from DRR module will be VO output voltage of power supply Vdrop in DRR module Vdrop will vary from 0 60V to 0 90V Typical 0 65V depending on the load current and surroundi...

Страница 15: ...aspects such as higher purchasing costs Frequently the user does not profit from fulfilling this standard therefore it is important to know whether it is mandatory to meet this standard for a specifi...

Отзывы: