HEX080PD Heat Exchanger Instruction Manual
Page 4
Definition
N. O
N. C
Connection
Pin 3 , 4
Pin 5 , 4
Control board, NTC and fan are in
normal status
OPEN
CLOSE
Power-off or control board is disabled
CLOSE
OPEN
NTC resistance is over range such as
“open circuit” or “short circuit”
CLOSE
OPEN
Fan speed is lower than 50% of
definition or fan is locked
CLOSE
OPEN
LED indicator
Fan
NTC sensor
Normal
GREEN
GREEN
Abnormal or failed
RED
Blinking RED
4-2. Standalone control mode
HEX can detect ambient temperature to control cooling capacity .
Internal fan and external fan speed default settings are shown below
Full speed : 3150 RPM ± 10%
Half speed : 1450RPM ± 200RPM