Mounting the Thermostat
The DZNT-T0-VAV backplate is designed for mounting directly on a standard North American, European or
Australian electrical box, but may be mounted in other ways as well.
Wiring Diagram – Thermostat / Termination Board Connections
For further wiring details regarding reheat and other applications see the
DZNT VAV/VVT Application Guide.
Notes
:
1.
Ensure you use straight-through Cat3 or higher (Cat5, Cat5e, Cat6) cables to join boxes. Although
Cat5 is mentioned throughout the documentation, any of these cable types are acceptable.
2.
Although it is not necessary to go from NET OUT on one box to NET IN on the next, doing so will
likely give the most even distribution of devices on the network and allow for easier troubleshooting
of network problems.
3.
At the last box on each trunk, keep the loop-back connector, ADP45-MSTP-LOOP, in place on the
NET OUT connector. Doing so will provide improved network stability and allow any one device to
be removed from the network without causing a loss of communications to the devices downstream
4.
If the same power source is used for more than one device, ensure that the transformer is properly
sized for the rated VA and ensure that the same polarity is observed from device to device.