C h a p t e r 2 Sp e c i f i c a t i o n s a n d S y s t e m C o n f i g u r a t i o
n
2 - 2 4
2_
S-type
:
K0 ~ K17,500
T-type
:
K-1,500 ~ K3,900
E-type
:
K-1,500 ~ K9,800
N-type
:
K-1,500 ~ K12,800
S-type
:
K320 ~ K31,820
T-type
:
K-2,380 ~ K7,340
E-type
:
K-2,380 ~ K17,960
N-type
:
K-2,380 ~ K23,360
Hardware resolution
16-bit (0.1°C)
16-bit (0.1°F)
16-bit
(0.01 mV)
Average function
Yes, CR#8 ~ CR#11, setting range: K1 ~ K100
Self-diagnosis
function
Detecting if exceeding upper and lower limts or channel disconnection
Isolation
An analog circuit is isolated from a digital circuit by a digital integrated circuit/an
optocoupler, and the analog channels are isolated from one another by
optocouplers.
Isolation between a digital circuit and a ground: 500 VDC
Isolation between an analog circuit and a ground: 500 VDC
Isolation between an analog circuit and a digital circuit: 500 VDC
Isolation between the 24 VDC and a ground: 500 VDC
Isolation between analog channels: 120 VAC
2.5.2
Temperature Measurement Module Profiles
1
4
5
3
6
7
8
2
9
0 4P T- E 2
4AI -P T
Unit: mm
Number
Name
Description
1
Removable terminal block
The inputs are connected to sensors.
The outputs are connected to loads to be driven.
2
External module connection
port
Connects the modules
3
Terminal number
Terminal number
4
Model name
Model name of the module
5
POWER LED indicator
Indicates the status of the power supply
ON: the power is on
OFF: no power
Содержание DVP-ES3 Series
Страница 26: ...DVP ES3 Series Operation Manual 1 14 _1 MEMO ...
Страница 59: ...Chapter 3 Installing Software 3 5 3_ 9 Check the installation information and then click Install ...
Страница 232: ...DVP ES3 Series Operation Manual 8 28 _8 MEMO ...
Страница 385: ...DVP ES3 Series Operation Manual 13 8 _13 MEMO ...
Страница 399: ...DVP ES3 Series Operation Manual B 4 _ B MEMO ...
Страница 405: ...DVP ES3 Series Hardware Manual C 6 _C MEMO ...