Delta DTC1000R Скачать руководство пользователя страница 2

SV 

Alarm Type 

Alarm Output Function 

Deviation upper-limit:   
This alarm output operates when PV value is higher than the setting value 
SV+ (AL-H). 

ON

OFF

SV

AL-H

 

Deviation lower-limit:   
This alarm output operates when PV value is lower than the setting value 
SV- (AL-L). 

ON

OFF

AL-L

SV

 

Reverse deviation upper- and lower-limit:   
This alarm output operates when PV value is in the range of the setting 
value SV+ (AL-H) and the setting value SV- (AL-L). 

ON

OFF

AL-L

SV

AL-H

 

Absolute value upper- and lower-limit:   
This alarm output operates when PV value is higher than the setting value 
AL-H or lower than the setting value AL-L. 

ON

OFF

AL-L

AL-H

 

Absolute value upper-limit:   
This alarm output operates when PV value is higher than the setting value 
AL-H. 

ON

OFF

AL-H

 

Absolute value lower-limit: 
This alarm output operates when PV value is lower than the setting value 
AL-L. 

ON

OFF

AL-L

 

Deviation upper- and lower-limit with standby sequence: 
This alarm output operates when PV value reaches set point (SV value) 
and the value is higher than the setting value SV+(AL-H) or lower than the 
setting value SV- (AL-L). 

ON

OFF

AL-L

AL-H

SV

 

Deviation upper-limit with standby sequence: 
This alarm output operates when PV value reaches set point (SV value) 
and the reached value is higher than the setting value SV+ (AL-H). 

ON

OFF

SV

AL-H

 

10 

Deviation lower-limit with standby sequence:   
This alarm output operates when PV value reaches the set point (SV 
value) and the reached value is lower than the setting value SV- (AL-L). 

ON

OFF

AL-L SV

 

11 

Hysteresis upper-limit alarm output: 
This alarm output operates if PV value is higher than the setting value 
SV+ (AL-H). This alarm output is OFF when PV value is lower than the 
setting value SV+ (AL-L). 

ON

OFF

AL-H

AL-L

 

12 

Hysteresis lower-limit alarm output:   
This alarm output operates if PV value is lower than the setting value SV- 
(AL-H). This alarm output is OFF when PV value is higher than the setting 
value SV- (AL-L). 

ON

OFF

AL-H

AL-L

 

Attention: AL-H and AL-L include AL1H, AL2H and AL1L, AL2L. When the 1

st

 group output is set to alarm output, AL1H (1024H) and AL1L (1025H) 

will be used. When the 2

nd

 group output is set to alarm output, AL2H (1026H) and AL2L (1027H) will be used. 

 

 

LED Display

 

1.  When power is normal, POWER LED will be lit. 
2.  LED will be lit after power on. Within one second after power on, communication protocol will be displayed; and at 

the following second after communication protocol displayed, communication address will be displayed. After that, 
LED will all be lit to show operation is normal. 

3.  When control action is executing, RUN LED will be lit. 
4.  When input, memory, or communication happens to error, ERROR LED will be lit. 
5.  When output is acted, the corresponding LED will be lit. 
6.  When PID program is auto adjusting parameter, AT LED will blink. 
7.  RX LED will blink when receiving communication signal and TX LED will blink when transmitting communication 

signal. 

Protocol Format of LED Display When Power On 

AT 

TX 

RX 

O1 

O2 

Err 

Run 

000: 2,400bps  001: 4,800bps   010: 9,600bps 
011: 19,200bps 100: 38,400bps   

Parity  00: None  01: Even 
       10: Odd 

0: ASCII 
1: RTU 

0:2 Stop bit 
1:1 Stop bit 

Communication address display: AT (bit 6) and Run (bit 0) will combine to binary code. 

 

 

Password Function

 

The default of password will not operate. After writing 4-byte password into specific communication address, password 
function will be activated. There are three levels for password protection: 
1.  Level1: only LED status, settings, and input values can be read via communication. It is unable to revise anything. 
2.  Level2: only LED status, settings, and input value can be read via communication. Also, it is able to revise setting. 
3.  Level3: all the settings can be read via communication, but it is only revisable for settings and AT adjustment. 
4.  No password function. 
Once password is set (106EH ~ 1070H), the controller will enter level 1. For entering another level, please key in 
corresponding password in 106BH ~ 106DH (see Address and content of Data Register). After power off, it will get back 
to level one. If password protection function shall be dismissed, it is necessary to clear all password setting. 
To enable password function, it is necessary to write corresponding password (106EH ~ 1070H) when password status 
is dismissed. To dismiss password levels, intended password setting should be written in specific function address 
106EH ~ 1070H. 
Password status can be read from 106EH~1070H. Statuses corresponding to each bit are shown as the following table: 

Bit 

b0 

b1 

b2 

b3 

b4 

b5 

b6 

Status Level 

1  Level 2  Level 3 

Level 1 locked 

Level 2 locked 

Level 3 locked 

Unlock 

Bit = 0 means no password setting. Bit = 1 means password is set (b0 ~ b2). b3 ~ b6 are used for displaying current 
password status. 

 

 

Synchronous Communication Protocol & Auto Number ID

 

By using Auto Number ID function, the communication protocol of DTC2000 can be set the same as the one of 
DTC1000. ID numbers tend to increase. 
1.  Set the auto communication flag to be “1” for DTC1000 (communication address 1022H). 
2.  Switch off the controller before connecting to another DTC2000. After that, switch on the power again. 
3.  Communication default: 9600bps, 7bits, Even, 1 stop bit. 
4.  This function will result in additional 3~5 seconds for power on.

 

 

 

RS-485 Communication

 

1.  Supporting transmission speed: 2,400, 4,800, 9,600, 19,200, 38,400bps. 
2.  Non-supported formats: 7, N, 1 or 8, E, 2 or 8, O, 2. 
3.  Communication protocol: Modbus (ASCII or RTU) 
4.  Function code: 03H to read the content of register (max. 8 words). 06H to write one word into register. 01H to read 

bits data (max. 16 bits). 05H to write one bit to register. 

5.  Address and Content of Data Register: 

Address 

Setting 

Content 

Explanation 

Temperature unit: 0.1 degree. Analog input: 1EU. 
Following read values happen to errors: 
8002H: Initial process (Temperature value is not got yet) 
8003H: Temperature sensor is not connected   
8004H: Temperature sensor input error   
8006H: Cannot get temperature value, ADC input error 

1000H  Process 

value 

(PV) 

8007H: Memory read/write error 

1001H 

Set point (SV) 

Unit: 0.1 degree. Analog input: 1EU. 

1002H 

6,000 

Upper-limit of temperature range  Upper-limit ban, unit: 0.1 degree. 

1003H 

-200 

Lower-limit of temperature range  Lower-limit ban, unit: 0.1 degree. 

1004H 

12 

Input temperature sensor type 

Please refer to the contents of the “Temperature Sensor 
Type and Temperature Range” for detail 

1005H 0 Control 

method 

0: PID, 1: ON/OFF, 2: manual tuning, 3: PID program 
control 

1007H 4 

1st group of Heating/Cooling 
control cycle 

0 ~ 99, 0: 0.5sec 

1008H 4 

2nd group of Heating/Cooling 
control cycle 

0 ~ 99, 0:0.5sec (it will be invalid when both groups are 
control output at the same time) 

1009H 

476 

PB Proportional band 

1 ~ 9,999, unit: 0.1 degree, analog input: 1EU 

100AH 

260 

Ti Integral time 

0 ~ 9,999 

100BH 

41 

Td Derivative time 

0 ~ 9,999 

100CH 

Integration default 

0 ~ 1,000, unit: 0.1% 

100DH 0 

Proportional control offset 
error value, when Ti = 0 

0 ~ 1,000, unit: 0.1% 

100EH 100 

COEF setting when Dual 
Loop output control are used 

1 ~ 9,999, unit: 0.01 

100FH 0 

Dead band setting when Dual 
Loop output control are used 

-999 ~ 9,999, unit: 0.1 degree or 1EU 

1010H 0 

Hysteresis setting value of the 
1st output group   

0 ~ 9,999, unit: 0.1 degree or 1EU 

1011H 0 

Hysteresis setting value of the 
2nd output group 

0 ~ 9,999, unit: 0.1 degree or 1EU 

1012H 0 

Output value read and write of 
Output 1 

Unit: 0.1%, write is valid only under manual control mode 

1013H 0 

Output value read and write of 
Output 2 

Unit: 0.1%, write is valid only under manual control mode 

1014H 0 

Upper-limit regulation of analog   
linear output 

1 scale = 2.8

μ

A = 1.3mV 

1015H 0 

 

Lower-limit regulation of analog   
linear output 

1 scale = 2.8

μ

A = 1.3mV 

1016H 

Temperature regulation value   

-999 ~

999, unit: 0.1 degree or 1EU 

1020H 

Alarm 1 type 

Please see the contents of the “Alarm Outputs” for detail 

1021H 

Alarm 2 type 

Please see the contents of the “Alarm Outputs” for detail 

1022H 0 

Auto-setting communication 
flag 

Auto setting ban of communication: 0, auto setting of 
communication: 1 

1024H 

40 

Upper-limit alarm 1 AL1H 

Please see the contents of the “Alarm Outputs” for detail 

1025H 

40 

Lower-limit alarm 1 AL1L 

Please see the contents of the “Alarm Outputs” for detail 

1026H 

40 

Upper-limit alarm 2 AL2H 

Please see the contents of the “Alarm Outputs” for detail 

1027H 

40 

Lower-limit alarm 2 AL2L 

Please see the contents of the “Alarm Outputs” for detail 

102AH  Read/Write 

status 

b1: 

ALM2, 

b2:

 o

C, b3:

 o

F, b4: ALM1, b5: O2, b6:O1, b7: AT 

102CH 0 

Setting of positive/negative 
proportional output   

0: positive, 1: negative 

102EH 

 

LED status 

b0: RUN, b1: ERR, b2: O2, b3: O1, b4: RX, b5:TX b6: AT 

102FH 

 

Software version 

V1.00 indicates 0x100 

1030H 

Start pattern number 

0 ~ 7 

1032H  

Remaining time of read 
execution 

Unit: second 

1033H  

Remaining time of reading 
execution step 

Unit: minute 

1034H  

Step number of reading 
current execution step 

0 ~ 7 

1035H  

Executing number of reading 
current pattern 

0 ~ 7 

1037H 1,000 

Upper-limit of proportional 
output 

0 ~ 100% max. analog output is upper limit, unit: 0.1% 

1038H 0 

Lower-limit of proportional 
output 

0 ~ 100% max. analog output is lower limit, unit: 0.1% 

1040H~ 

1043H 

Actual step number setting 
inside the correspond pattern 

0 ~ 7 = N means the pattern is executed from step from 0 
to N. 

1050H~ 

1053H 

Cycle number of repeating 
executing pattern 0 ~ 7 

0 ~ 199 means the pattern is executed for 1 ~ 200 times. 

1060H~ 

1063H 

Link pattern number setting of 
the current pattern 

0 ~ 8, 8 means program end. 0 ~ 7 means the next 
execution number after completing current pattern. 

1068H 

Control execution/Stop setting 

0: Stop, 1: execute, 2: program end, 3: program hold 

1069H 

Output 1: control selection 

0: heating, 1: cooling, 2: alarming, 3: proportional output 

106AH 

Output2: control selection 

0: heating, 1: cooling, 2: alarming 

106BH 0 

Dismiss level 1 
Read/write allowed 

Shall be same as level 1 password setting (106E) 

106CH 

Dismiss level 2. Use level 3. 

Shall be same as level 2 password setting (106F) 

106DH 

Dismiss level 3. Use level 2 

Shall be same as level 3 password setting (1070) 

106EH 

Dismiss level 1/Set password 

Clear old password before new password setting 

106FH 

Dismiss level 2/Set password 

Clear old password before new password setting 

1070H 

Dismiss level 3/Set password 

Clear old password before new password setting 

1071H 1 

Read/Write communication 
address 

1 ~ 247 

1072H 0 

Read/Write communication 
format 

RTU: 1,    ASCII: 0 

1073H 2 

Baud rate setting of 
communication 

0 ~ 4: 2,400 ~ 38,400 

1074H 1 

Data length setting of 
communication 

0: 8bit  1: 7bit 

1075H 

Parity bit setting 

0: None    1:Even    2: Odd   

1076H 

Stop bit setting 

0: 2 stop bit    1: 1stop bit 

Address 

Setting 

Content 

Explanation 

2000H~ 

203FH 

Pattern 0 ~ 7 to set target 
temperature 
Pattern 0: 2000H ~ 2007H 

Temperature measure unit: 0.1 degree 

2080H~ 

20BFH 

Pattern 0~7 to set execution   
time.  
Pattern 0: 2080H ~ 2087H 

Time 0 ~ 900 (1 minute for each scale) 

6.  Address and Content of Bit Register: ( First bit of reading will put into LSB, Write data = FF00H for bit set, 0000H 

for bit data as “0”) 

0811H 

Temperature unit display selection 

0: 

o

F,  1: 

o

C (default) 

0813H 

AT setting 

AT setting OFF: 0 (default), AT setting ON: 1 

0814H 

Control RUN/STOP setting 

0: STOP, 1: Execute (default) 

0815H 

Program hold flag 

1: Program temporary stop 

0816H 

Program stop flag 

1: Program stop 

7.  Communication format: 01: read bit data, 05: write bit data, 03: read word, 06: write word.

 

 

ASCII Mode:

 

To Read Instruction 

To Read Response 

Message 

To Write Instruction 

To Write Response 

Message 

Starting word 

’ 

’ 

Starting word 

’  ’

’  Starting word  ’

’ 

’ 

Starting word 

’ 

’ 

Machine 

address 1 

‘0’ 

‘0’  Machine address 

‘0’ 

‘0’ 

Machine 

address 1 

‘0’ 

‘0’ 

Machine 

address 1 

‘0’ 

‘0’ 

Machine 

address 0 

‘1’ 

‘1’  Machine address 

‘1’ 

‘1’ 

Machine 

address 0 

‘1’ 

‘1’ 

Machine 

address 0 

‘1’ 

‘1’ 

Instruction 1 

‘0’ 

‘0’ 

Instruction 1 

‘0’ 

‘0’ 

Instruction 1 

‘0’ 

‘0’ 

Instruction 1 

‘0’ 

‘0’ 

Instruction 0 

‘3’ 

‘1’ 

Instruction 0 

‘3’ 

‘1’ 

Instruction 0 

‘6’ 

‘5’ 

Instruction 0 

‘6’ 

‘5’ 

‘1’ 

‘0’ 

‘0’ 

‘0’ 

‘1’ 

‘0’ 

‘1’ 

‘0’ 

‘0’ 

‘8’ 

Response data 

length (byte) 

‘4’ 

‘2’ 

‘0’ 

‘8’ 

‘0’ 

‘8’ 

‘0’ 

‘1’ 

‘0’ 

‘1’ 

‘0’ 

‘1’ 

‘0’ 

‘1’ 

To read 

data/Staring 

word address 

‘0’ 

‘0’ 

‘1’ 

‘7’ 

To write data 

address 

‘1’ 

‘0’ 

To write data 

address 

‘1’ 

‘0’ 

‘0’ 

‘0’ 

‘F’ 

‘0’ 

‘0’ 

‘F’ 

‘0’ 

‘F’ 

‘0’ 

‘0’ 

 

Data content of 

1000H/081xH 

‘4’ 

‘1’ 

‘3’ 

‘F’ 

‘3’ 

‘F’ 

‘0’ 

‘0’ 

‘0’ 

 ‘E’ 

‘0’ 

‘E’ 

‘0’ 

To read data 
length/Word 
length 
(word/bit) 

‘2’ 

‘9’ 

‘0’ 

 

To write data 

content 

‘8’ 

‘0’ 

To write data 

content 

‘8’ 

‘0’ 

LRC1 check    ‘E’ 

‘D’ 

‘0’ 

 LRC1 

 

‘F’ 

‘E’ 

LRC1  

‘F’ 

‘E’ 

LRC 0 check 

‘A’ 

‘D’ 

Data content of 

1001H 

 

‘0’ 

 LRC 

 

‘D’ 

‘3’ 

LRC 0   

‘D’ 

‘3’ 

Ending word 1  CR 

CR 

LRC1 check   

‘0’  ‘E’  Ending word 1  CR 

CR  Ending word 1  CR 

CR 

Ending word 0  LF 

LF 

LRC 0 check 

‘3’ 

‘4’  Ending word 0  LF 

LF 

Ending word 0  LF 

LF 

 

 

 

Ending word 1 

CR  CR 

 

 

 

 

 

 

 

 

 

Ending word 0 

LF  LF 

 

 

 

 

 

 

LRC Check: 

LRC check is the added sum from “Machine Address” to “Data content”. For example, 01H + 03H + 10H+ 00H + 00H + 02H 
= 16H, then take the complementary of 2 to get EA. 

RTU Mode: 

To Read Instruction 

To Read Response 

Message 

To Write Instruction 

To Write Response 

Message 

Machine 

address 

01H  01H 

Machine address 

01H  01H 

Machine 

address 

01H  01H 

Machine 

address 

01H  01H 

Instruction 03H  01H 

Instruction 03H  01H 

Instruction 06H  05H 

Instruction 06H  05H 

10H  08H 

10H  08H 

10H  08H 

Starting 

address of 

reading data 

00H  10H 

Response data 

length (byte) 

04H  02H 

To write data 

address 

01H  10H 

To write data 

address 

01H  10H 

00H  00H 

01H  17H 

03H  FFH 

03H  FFH 

To read data 

length 

(word/bit) 

02H  09H 

Data content 1  F4H  01H 

To write data 

content 

20H  00H 

To write data 

content 

20H  00H 

CRC low byte  C0H  BBH 

03H 

 

CRC low byte  DDH  8FH  CRC low byte  DDH  8FH 

CRC high byte  CBH  A9H 

Data content 2 

20H 

 CRC 

high 

byte  E2H  9FH  CRC high byte  E2H  9FH 

 

 

 

CRC low byte  BBH  77H   

 

 

 

 

 

  

 

CRC 

high 

byte  15H  88H   

 

 

 

 

 

Following is a CRC (Cyclical Redundancy Check) program example: 

unsigned int reg_crc = 0xffff; i = 0;   
while (length--) 
{  
  reg_crc ^= RTUData[i];   
 i ++;  
  for (j = 0; j < 8; j++) 
 {  
 

if (reg_crc & 0x01) 

reg_crc = (reg_crc >> 1) ^ 0xA001;   

 

else   

reg_crc = reg_crc >> 1;   

 } 
}  
return(reg_crc); 

 

 

Installation

 

DTC modules can be expanded up to 8, and installed with DIN rail mounting 

 

 

 

 

 

How to Set Up Current Input 

For normal input 

For current input (4 ~ 20mA, 0 ~ 20mA) 

JU MPER

PIN HEADER

JP1

DEFAU LT SETTING

 

J UMPER

PIN HEADER

JP1

 

 

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most 

updated version at http://www.delta.com.tw/industrialautomation 

Отзывы: