TECHNICAL DATASHEET

 

CliQ II DIN Rail Power Supply 

48V 240W 1 Phase / DRP048V240W1B

□ 

 

 

  

All parameters are specified at 25°C ambient unless otherwise noted.

 

  

www.DeltaPSU.com (September 2013, Rev. 01)

  

 

10

 

Safety Instructions 

 

Vertical Mounting 

 

          

 
 

– 

ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit. If mains are not 
turned OFF, there is risk of explosion / severe damage. 

– 

To guarantee sufficient convection cooling, keep a distance of 50mm above and below the device as well as a lateral 
distance of 20mm to other units. 

– 

Note that the enclosure of the device can become very hot depending on the surrounding air temperature and load of the power 
supply. Risk of burns! 

– 

Only plug in and unplug connectors when power is turned off! 

– 

DO NOT insert any objects into the unit. 

– 

Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected. Do not touch the unit during 
this time. 

– 

The power supplies are built in units and must be installed in a cabinet or room (condensation free environment and indoor 
location) that is relatively free of conductive contaminants. 

– 

CAUTION: “For use in a controlled environment”. 
 

For DRP048V240W1BA: 

– 

The power supplies unit must be installed in an IP54 enclosure or cabinet in the final installation. The enclosure or cabinet must 
comply with EN 60079-0 or EN 60079-15. 

– 

Warning: Explosion Hazard – Substitution of components may impair suitability for Class I, Division 2. 

– 

Warning: Explosion Hazard – Do not disconnect equipment or adjust potentiometer unless the power has been switched off or the 
area is known to be non-hazardous. 

 

 

 

Horizontal Mounting 

Содержание DRP048V240W1B Series

Страница 1: ... DIN Rail power supply series also offers output voltage of 48V These products are encased in rugged yet lightweight full aluminium body that can withstand shock and vibration according to IEC 60068 2 standard The series of 1 phase products operates over a wide temperature range of 25 C to 80 C and wide input range from 85Vac to 264Vac with no power de rating throughout the entire range Another gr...

Страница 2: ...A 240Vac Fulfills tested conditions Output Ratings Characteristics Nominal Output Voltage 48Vdc Output Voltage Tolerance 1 initial set point tolerance from factory Output Voltage Adjustment Range 48 56Vdc Output Current 5 00A continuously operating at 48V 7 50A Power Boost for 5 seconds at 48V refer to the details in the Functions section Output Power 240W continuously operating 360W Power Boost f...

Страница 3: ...ng 40 C de rate power by 2 5 C Operating Humidity 95 RH Non Condensing Operating Altitude 2 500 Meters Shock Test Non Operating IEC 60068 2 27 30G 300m S for a duration of 18ms 1 times per direction 2 times in total Vibration Non Operating IEC 60068 2 6 10Hz to 500Hz 30m S 3G peak 60 min per axis for all X Y Z direction Pollution Degree 2 Protections Overvoltage 57V SELV Output Hicc up Mode Non La...

Страница 4: ...Hazardous Location ATEX For DRP048V240W1BA cCSAus to CSA C22 2 No 213 M1987 ANSI ISA 12 12 01 2007 Class I Division 2 Group A B C D T4 Ta 25 C to 80 C Vertical 50 C derating Horizontal 40 C derating EN 60079 0 2009 EN 60079 15 2010 II 3G Ex nA nC IIC T4 Gc Ta 25 C to 80 C Vertical 50 C derating Horizontal 40 C derating II 3G ATEX 94 9 EC For DRP048V240W1BA Certificate No EPS 12 ATEX 1 491 X CE In ...

Страница 5: ...80 modulation 1kHz Electrical Fast Transient Burst IEC 61000 4 4 Level 3 Criteria A 1 2kV Surge IEC 61000 4 5 Level 3 Criteria A 1 Common Mode2 2kV Differential Mode 3 1kV Conducted IEC 61000 4 6 Level 3 Criteria A 1 150kHz 80MHz 10Vrms Power Frequency Magnetic Fields IEC 61000 4 8 Criteria A 1 10A Meter Voltage Dips IEC 61000 4 11 100 dip 1 cycle 20ms Self Recoverable Low Energy Pulse Test Ring W...

Страница 6: ...ECHNICAL DATASHEET CliQ II DIN Rail Power Supply 48V 240W 1 Phase DRP048V240W1B All parameters are specified at 25 C ambient unless otherwise noted www DeltaPSU com September 2013 Rev 01 6 Block Diagram ...

Страница 7: ...ied at 25 C ambient unless otherwise noted www DeltaPSU com September 2013 Rev 01 7 Device Description 1 Input terminal block connector 2 Output terminal block connector 3 DC Voltage adjustment potentiometer 4 DC OK control LED Green 5 Universal mounting rail system Dimensions L x W x D 121 x 85 x 124 1 mm ...

Страница 8: ... will go into bouncing mode and will recover when the surrounding air temperature is lowered or the load is reduced as far as necessary to keep the device in working condition 3 In order for the device to function in the manner intended it is also necessary to keep a safety distance of 20mm with adjacent units while the device is in operation 4 Depending on the surrounding air temperature and outp...

Страница 9: ...sh downwards until stopped 3 Press against the bottom front side for locking 4 Shake the unit slightly to ensure that it is secured Fig 2 2 Dismounting To uninstall pull or slide down the latch with screw driver as shown in Fig 2 2 Then slide the power supply unit PSU in the opposite direction release the latch and pull out the power supply unit PSU from the rail CAUTION Must tighten wire to housi...

Страница 10: ...nd unplug connectors when power is turned off DO NOT insert any objects into the unit Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected Do not touch the unit during this time The power supplies are built in units and must be installed in a cabinet or room condensation free environment and indoor location that is relatively free of conductive contam...

Страница 11: ...s the time when the AC input collapses and output voltage retains regulation for a certain period of time The time required for the output to reach 90 of its set value after the input voltage is removed Inrush Current Inrush current is the peak instantaneous input current measured and occurs when the input voltage is first applied For AC input voltages the maximum peak value of inrush current will...

Страница 12: ...0 sec 35 214W 18 5 sec 28 5 sec It is not recommended to prolong the duration of Power Boost to be longer than the specified duty cycle calculation this may cause damage to the PSU Power Boost is the reserve power available constantly that allows reliable startup to support sudden and short spike of loads with high inrush current typically during turn on to remove the need of more expensive higher...

Страница 13: ...Circuit Protection The power supply s output OLP OCP function also provides protection against short circuits When a short circuit is applied the output current will operate in Hiccup mode as shown in the illustration in the OLP OCP section on this page The power supply will return to normal operation after the short circuit is removed Overvoltage Protection The power supply s overvoltage circuit ...

Страница 14: ...om DRR module will be VO output voltage of power supply Vdrop in DRR module Parallel Operation These DRR modules can also be used for Parallel function in order to increase the output power by N 1 e g 2 5A 2 5A 5A or 2 5A 2 5A 2 5A 7 5A or current sharing and thus increasing the power supply and system reliability Though the DRP048V240W1B is not designed for current sharing a good current sharing ...

Страница 15: ...enetrates everywhere including under device and prevents leakage The conformal coating dipping can be applied to PCBs or circuit board The coating preserves the performance of precision electronic primarily by preventing ionizable contaminants such as salt from reaching circuit nodes where the material slumps around sharp edges This can be a problem especially in highly conversing atmosphere PFC N...