TECHNICAL DATASHEET

 

CliQ II DIN Rail Power Supply 

48V 240W 1 Phase / DRP048V240W1B

□ 

 

 

  

All parameters are specified at 25°C ambient unless otherwise noted.

 

  

www.DeltaPSU.com (September 2013, Rev. 01)

  

 

1

 

 

Highlights & Features 

– 

Worldwide AC input range without power de-rating 

– 

Power Boost 150% for 5 seconds 

– 

Full corrosion resistant Aluminium chassis 

– 

Extreme low temperature cold start at -40°C 

– 

Conformal coating on PCBA to protect against chemical and 
dust pollutants 

– 

Hazardous Locations approval to ATEX and Class I, Div 2 
(DRP048V240W1BA) 

– 

Overvoltage / Overcurrent / Over Temperature Protections 

– 

IP20 Compliant 

 
 

Safety Standards 

 

CB Certified for worldwide use 

 
 

Model Number:

   

DRP048V240W1B

 

Unit Weight

:

 

 

0.96 kg 

Dimensions (L x W x D):

  121 x 85 x 124.1

 

mm

 

 
 

General Description 

The CliQ II 1-phase DIN Rail power supply series  also  offers output voltage of 48V.  These  products  are  encased in rugged yet 
lightweight full aluminium body that can withstand shock and vibration according to IEC 60068-2  standard. The series of 1-phase 
products  operates  over a wide temperature range of -25°C to +80°C and wide input range from 85Vac to 264Vac, with no power 
de-rating throughout the entire range. Another great feature is the conformal coating on the PCBA which allows selected models to be 
certified to ATEX and Class I,  Div 2 for use in hazardous locations. The design conforms  to harmonic current emission 
IEC/EN 61000-3-2 standard.  

 
 

Model Information 

CliQ II DIN Rail Power Supply 

 

Model  Number

 

Input  Voltage Range

 

Output  Voltage

 

Output  Current

 

DRP048V240W1B

□ 

85-264Vac (120-375Vdc) 

48Vdc

 

5.00A 

 

 

Model Numbering 

DR

 

P

 

048V

 

240W

 

1

 

B

 

 

DIN Rail

 

Power Supply

 

Output Voltage

 

Output Power

 

Single Phase

 

CliQ II Series

 

A - Metal Case, 
      with Class I, Div 2 

N - Metal Case, 
      without Class I, Div 2 

 
 

 

Содержание DRP048V240W1B Series

Страница 1: ... DIN Rail power supply series also offers output voltage of 48V These products are encased in rugged yet lightweight full aluminium body that can withstand shock and vibration according to IEC 60068 2 standard The series of 1 phase products operates over a wide temperature range of 25 C to 80 C and wide input range from 85Vac to 264Vac with no power de rating throughout the entire range Another gr...

Страница 2: ...A 240Vac Fulfills tested conditions Output Ratings Characteristics Nominal Output Voltage 48Vdc Output Voltage Tolerance 1 initial set point tolerance from factory Output Voltage Adjustment Range 48 56Vdc Output Current 5 00A continuously operating at 48V 7 50A Power Boost for 5 seconds at 48V refer to the details in the Functions section Output Power 240W continuously operating 360W Power Boost f...

Страница 3: ...ng 40 C de rate power by 2 5 C Operating Humidity 95 RH Non Condensing Operating Altitude 2 500 Meters Shock Test Non Operating IEC 60068 2 27 30G 300m S for a duration of 18ms 1 times per direction 2 times in total Vibration Non Operating IEC 60068 2 6 10Hz to 500Hz 30m S 3G peak 60 min per axis for all X Y Z direction Pollution Degree 2 Protections Overvoltage 57V SELV Output Hicc up Mode Non La...

Страница 4: ...Hazardous Location ATEX For DRP048V240W1BA cCSAus to CSA C22 2 No 213 M1987 ANSI ISA 12 12 01 2007 Class I Division 2 Group A B C D T4 Ta 25 C to 80 C Vertical 50 C derating Horizontal 40 C derating EN 60079 0 2009 EN 60079 15 2010 II 3G Ex nA nC IIC T4 Gc Ta 25 C to 80 C Vertical 50 C derating Horizontal 40 C derating II 3G ATEX 94 9 EC For DRP048V240W1BA Certificate No EPS 12 ATEX 1 491 X CE In ...

Страница 5: ...80 modulation 1kHz Electrical Fast Transient Burst IEC 61000 4 4 Level 3 Criteria A 1 2kV Surge IEC 61000 4 5 Level 3 Criteria A 1 Common Mode2 2kV Differential Mode 3 1kV Conducted IEC 61000 4 6 Level 3 Criteria A 1 150kHz 80MHz 10Vrms Power Frequency Magnetic Fields IEC 61000 4 8 Criteria A 1 10A Meter Voltage Dips IEC 61000 4 11 100 dip 1 cycle 20ms Self Recoverable Low Energy Pulse Test Ring W...

Страница 6: ...ECHNICAL DATASHEET CliQ II DIN Rail Power Supply 48V 240W 1 Phase DRP048V240W1B All parameters are specified at 25 C ambient unless otherwise noted www DeltaPSU com September 2013 Rev 01 6 Block Diagram ...

Страница 7: ...ied at 25 C ambient unless otherwise noted www DeltaPSU com September 2013 Rev 01 7 Device Description 1 Input terminal block connector 2 Output terminal block connector 3 DC Voltage adjustment potentiometer 4 DC OK control LED Green 5 Universal mounting rail system Dimensions L x W x D 121 x 85 x 124 1 mm ...

Страница 8: ... will go into bouncing mode and will recover when the surrounding air temperature is lowered or the load is reduced as far as necessary to keep the device in working condition 3 In order for the device to function in the manner intended it is also necessary to keep a safety distance of 20mm with adjacent units while the device is in operation 4 Depending on the surrounding air temperature and outp...

Страница 9: ...sh downwards until stopped 3 Press against the bottom front side for locking 4 Shake the unit slightly to ensure that it is secured Fig 2 2 Dismounting To uninstall pull or slide down the latch with screw driver as shown in Fig 2 2 Then slide the power supply unit PSU in the opposite direction release the latch and pull out the power supply unit PSU from the rail CAUTION Must tighten wire to housi...

Страница 10: ...nd unplug connectors when power is turned off DO NOT insert any objects into the unit Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected Do not touch the unit during this time The power supplies are built in units and must be installed in a cabinet or room condensation free environment and indoor location that is relatively free of conductive contam...

Страница 11: ...s the time when the AC input collapses and output voltage retains regulation for a certain period of time The time required for the output to reach 90 of its set value after the input voltage is removed Inrush Current Inrush current is the peak instantaneous input current measured and occurs when the input voltage is first applied For AC input voltages the maximum peak value of inrush current will...

Страница 12: ...0 sec 35 214W 18 5 sec 28 5 sec It is not recommended to prolong the duration of Power Boost to be longer than the specified duty cycle calculation this may cause damage to the PSU Power Boost is the reserve power available constantly that allows reliable startup to support sudden and short spike of loads with high inrush current typically during turn on to remove the need of more expensive higher...

Страница 13: ...Circuit Protection The power supply s output OLP OCP function also provides protection against short circuits When a short circuit is applied the output current will operate in Hiccup mode as shown in the illustration in the OLP OCP section on this page The power supply will return to normal operation after the short circuit is removed Overvoltage Protection The power supply s overvoltage circuit ...

Страница 14: ...om DRR module will be VO output voltage of power supply Vdrop in DRR module Parallel Operation These DRR modules can also be used for Parallel function in order to increase the output power by N 1 e g 2 5A 2 5A 5A or 2 5A 2 5A 2 5A 7 5A or current sharing and thus increasing the power supply and system reliability Though the DRP048V240W1B is not designed for current sharing a good current sharing ...

Страница 15: ...enetrates everywhere including under device and prevents leakage The conformal coating dipping can be applied to PCBs or circuit board The coating preserves the performance of precision electronic primarily by preventing ionizable contaminants such as salt from reaching circuit nodes where the material slumps around sharp edges This can be a problem especially in highly conversing atmosphere PFC N...

Отзывы: