D e lt a M u lt i- C ir c u i t P o w e r M e t e r D P M - M A11 2 1 U s e r M a n u a l
4 - 1 4
4
MODBUS
Address
Item
Range
Data
Type
Unit
BYTE
Read(R)/
Write(W)
Hex
Modicom
Format
203
400516
Reading status code
0: Clear all record datas
(Reset reading index)
1: Abort current read
2: Read success
word
2
W
The length of each data record can be obtained by reading the length address (0x200) of each record. The data length
obtained is read through the data reading address (0x202), as shown in the figure below:
The data content will be returned in the following format:
Address
Code
Byte
Count
Voltage Unit
Current Unit
Power Unit
Year
Month
Hi
Lo
Hi
Lo
Hi
Lo
Hi
Lo
Hi
Lo
01h
03h
30h
00h
00h
00h
01h
00h
02h
07h
E1h
00h
0Ch
Day
Hour
Minute
Second
Data
CRC
Hi
Lo
Hi
Lo
Hi
Lo
Hi
Lo
Lo
Hi
00h
01h
00h
0Dh
00h
19h
00h
2Ah
…………………………
xxh
xxh
Byte Count: Read from 0x200
Date: 2017/12/01 => 07E1H/000CH/0001H
Time: 13:25:42 => 000DH:0019H:002AH
Each read order can only read a log record. Reading unread number (0x201) shows how many logs remain unread.
If there is no record that has not been read yet, then the data return will be 0x20h, indicating that the data record has been
read.
After reading a record of log must be send back the read status(0x203) to meter, as a basis for recording indicators
move. It can also give up the record read or clear data records via send back the read status.
Содержание DPM-MA1121
Страница 3: ......
Страница 9: ...Delta Multi Circuit Power Meter DPM MA1121 User Manual 1 4 _1 MEMO...
Страница 14: ...Chapter 2 Specifications 2 5 2_ Setting UI interface tree MA1121...
Страница 15: ...Delta Multi Circuit Power Meter DPM MA1121 User Manual 2 6 _2 2 4 Physical Dimensions unit mm inch Rear view...
Страница 34: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...