(1) General precautions
Thank you for purchasing this product. This DOP-110IS instruction sheet provides information for the
DOP-110IS series HMI. Before using this product, read through this instruction sheet carefully to ensure
the correct use of the product. Keep this sheet handy for quick reference whenever needed. Before
finishing reading this sheet, follow the instructions below:
Install the product in an indoor location, which is free of vapor and corrosive and inflammable gas.
Refer to the wiring diagram when connecting the wires.
Ensure this product is correctly grounded. The grounding method must comply with the national
electrical standard guidelines (refer to NFPA 70: National Electrical Code, 2005 Ed.).
Do not disassemble the HMI or change the wiring when power is on.
Do not touch the power supply when power is on, or it may cause electric shock.
When the HMI displays a low power notification and requires a battery change, contact Delta or
local distributors for the replacement. Do not change the batteries by yourself.
This product can be used with other industrial automation equipment. Read through this sheet
carefully and install the product according to the instructions to avoid danger.
Cleaning method: use a dry cloth to clean the product.
This product must be used at an altitude below 2,000 m (6561.68 ft).
If the equipment is used in a manner not specified by the manufacturer, the protection function
provided by the equipment may be impaired.
For repair and maintenance, contact Delta Electronics, Inc. Address: No.18, Xinglong Rd.,
Taoyuan City, Taiwan. TEL: +886-3-3626301.
If you have any inquiry during operation, contact our local distributors or Delta Customer Service Center.
The instruction sheet may be revised without prior notice. Contact our distributors or download the latest
version from the Delta website (http://www.deltaww.com.tw/ia).
(2) Communication port pin assignment
DOP-110IS COM1
COM Port
Pin
MODE1
RS-232
1
-
2
RXD
3
TXD
4
-
5
GND
6
-
7
RTS
8
CTS
9
-
DOP-110IS COM2
COM Port
Pin
MODE1
MODE2
MODE3
RS-232
RS-422
RS-485
1
-
TXD+
D+
2
RXD
-
-
3
TXD
-
-
4
-
RXD+
-
5
GND
GND
GND
6
-
TXD-
D-
7
RTS
-
-
8
CTS
-
-
9
-
RXD-
-
Note:
1. The mark “-” means connection is not required.
2. To use COM2 for flow control through RS-232 (RTS and CTS signals), COM3 port is not operable.
DOP-110IS COM3
COM Port
Pin
MODE1
MODE2
MODE3
RS-232
RS-422
RS-485
1
-
TXD+
D+
2
RXD
-
-
3
TXD
-
-
4
-
RXD+
-
5
GND
GND
GND
6
-
TXD-
D-
7
-
-
-
8
-
-
-
9
-
RXD-
-
Note: the mark “-” means connection is not required.
DOP-110IS Ethernet interface (LAN)
Ethernet interface
Pin
Contact
Ethernet
1
TX+
2
TX-
3
RX+
4
-
5
-
6
RX-
7
-
8
-
Note: the mark “-” means connection is not required.
(3) Description of each part
DOP-110IS (front view)
A
A
Operation / display area
DOP-110IS (rear view)
A
C
D
E F G
B
H I
SLA VE
HO ST
AU DIO
O UT
A
Power input connector
F
Ethernet interface (LAN)
B
COM2 (supports communication indicator)
G
USB Slave
C
COM3 (supports communication indicator)
H
USB Host
D
COM1
I
Memory card slot
E
Audio output interface
-
-
(4) Mounting dimensions
DOP-110IS
272.6(10.73")
200.
6
(7.
09
")
261.3
(10.29" )
+1
.0 .0
0
+
0
.04". .0
0
T
54(33.62")
10.4
Note:
T = 1.6 mm – 6 mm (0.063" - 0.24")
(5) Installation and wiring
Precautions:
Mount the HMI according to the illustration below. Incorrect installation direction may result in
malfunction.
To ensure the HMI is well ventilated, make sure there is sufficient space between the HMI and the
adjacent objects or walls.
This product should be used on a case / platform which conforms to enclosure Type 4X standard
(for indoor use only).
The maximum panel thickness for mounting must be no greater than 5 mm (0.2 inches).
Use copper wires.
Installation diagram:
Step 1:
Put the waterproof gasket onto the HMI and
then insert the HMI into the panel cutout.
Step 2:
Place the fasteners into the slots and tighten the
screws until reaching the panel cutouts.
Unit: mm (inches)