Delta Controls 

Jumpers 

 

10K

5V

10V

 

INPUT SIGNAL TYPE 
 
The input type is selected by placing the jumper in the correct location on 
the Input Type Selector Block.  The diagram to the left shows the factory 
default selection of 10 K

 
10K 

 For 10 K

 Thermistor temperature sensors, as well as Binary 

or Dry Contact inputs. 

 
5V 

  For sensors and other field devices that use a 5 VDC signal. 

 
10V 

  For sensors and other field devices that use a 10 VDC signal. 

 

INTERNAL

EXTERNAL

 

INPUT CONNECTION SELECTOR – DNT-T221X MODELS ONLY 
 
This jumper is used to select whether the internal Thermistor sensor or a 
remotely located Thermistor is connected to IP1.  The diagram to the left 
shows the factory default selection of the Internal 10 K

 Thermistor. 

 
External    For connecting a remotely located 10 K

 Thermistor 

temperature sensor to IP1, which is wired to the connection 
terminals provided. 

 
Internal    For connecting the internal 10 K

 Thermistor temperature 

sensor to IP1. 

TERM

NO TERM

 

NETWORK TERMINATION RESISTOR 
This jumper is used to select the termination resistor at each end of each 
MS/TP network segment.  The diagram to the left shows the factory 
default selection of No Term.  

 

Mounting 

The BACstat II backplate is designed for mounting directly on standard North American, European or 
Australian electrical boxes. 
 
 

Document Edition 1.8

 

 

Page 5 of 10 

Содержание DNT-T221

Страница 1: ...damper position and more When connected on a BACnet MS TP network the DNT T221 functions as an independent BACnet thermostat When connected to a controller on a LINKnet network it provides a programma...

Страница 2: ...specify button icons if you want the default but must specify INT if you want the international button icons i e DNT T221 INT Package Contents Delta Network Thermostat BACstat II Product DNT T221 Rev...

Страница 3: ...00 ohm 77 F 25 C Humidity Sensor DNT H121B Model Only Accuracy of 2 RH from 0 100 RH 25 C VSUPPLY 2 6Vdc Display Resolution of 0 1 Stability of 1 RH typical 50 RH over 5 years Note Extended exposure t...

Страница 4: ...MS TP Connection Set via Keypad Configuration Setup or Software Setup Keypad MAC Address Range 1 to 99 per network segment Software Address Range As per the BACnet standard Supports DNA Delta s intuit...

Страница 5: ...hermistor sensor or a remotely located Thermistor is connected to IP1 The diagram to the left shows the factory default selection of the Internal 10 K Thermistor External For connecting a remotely loc...

Страница 6: ...use a wire nut to terminate all the outputs to GND 3 Ensure you use the recommended balanced cable for the network and follow the documented procedures within Delta Controls Wiring and Installation G...

Страница 7: ...ced 100 to 120 nominal impedance Twisted Shielded Pair TSP Cable Nominal capacitance of 16 PF FT or lower Nominal velocity of propagation of 66 or higher Topology For MS TP and LINKnet networks ensure...

Страница 8: ...SC 1212 H E DSC 1280 H E DSC T305 System Devices RS 485 NET1 NET2 NET1 NET2 RS 232 BACstat I BACstat II with No I O BACstat II with muxed I O I O Field Modules LINKnet Devices TRM Level 4 Network LINK...

Страница 9: ...separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV te...

Страница 10: ...4 2 1995 A1 1999 ESD Immunity ESD Immunity Level A Level A EN 61000 4 3 1996 EN 61000 4 3 1996 RF Electromagnetic Field Immunity RF Electromagnetic Field Immunity Level A Level A ENV 50204 1995 ENV 50...