Chapter 7 Optional Accessories
MS300 (IP66 / NEMA 4X)
7-18
Installation
During installation, pass the cable through at least one zero phase reactor.
Use a suitable cable type (insulation class and wire section) so that the cable passes easily through the
zero phase reactor. Do not pass the grounding cable through the zero phase reactor; only pass the motor
wire through the zero phase reactor.
With longer motor cables the zero-phase reactor can effectively reduce interference at the motor
output. Install the zero-phase reactor as close to the output of the drive as possible. Figure A shows the
installation diagram for a single turn zero-phase reactor. If the wire diameter allows several turns, Figure
B shows the installation of a multi-turn zero-phase reactor. The more turns, the better the noise
suppression effect.
Figure A
:
Single turn wiring diagram for shielding wire with a
zero phase
reactor
Power
Supply
Zero Phase Reactor
MOTOR
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
Figure B: Multi-turn zero phase reactor
Installation notes
Install the zero phase reactor at the drive’s output terminal (U/T1, V/T2, W/T3).
After the zero phase reactor is installed, it reduces the electromagnetic radiation and load stress emitted
by the wiring of the frequency converter. The number of zero phase reactors required for the drive
depends on the wiring length and the drive voltage.
The normal operating temperature of the zero phase reactor should be lower than 85 °C (176 °F).
However, when the zero phase reactor is saturated, its temperature may exceed 85 °C (176 °F). In this
case, increase the number of zero phase reactors to avoid saturation. The following are reasons that
might cause saturation of the zero phase reactors: the drive wiring is too long; the drive has several
sets of loads; the wiring is in parallel; or the drive uses high capacitance wiring. If the temperature of the
zero phase reactor exceeds 85 °C (176 °F) during the operation of the drive, increase the number of
zero phase reactors.
Содержание Compact Drive MS300 IP66/NEMA 4X Series
Страница 3: ......
Страница 10: ...Chapter 1 Introduction MS300 IP66 NEMA 4X 1 3 1 2 Model Name 1 3 Serial Number...
Страница 18: ...Chapter 1 Introduction MS300 IP66 NEMA 4X 1 11 This page intentionally left blank...
Страница 24: ...Chapter 2 Dimensions MS300 IP66 NEMA 4X 2 6 This page intentionally left blank...
Страница 28: ...Chapter 3 Installation MS300 IP66 NEMA 4X 3 4 This page intentionally left blank...
Страница 29: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 1 Chapter 4 Wiring 4 1 System Wiring Diagram 4 2 Wiring...
Страница 32: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 4 4 2 Wiring Figure 4 2...
Страница 34: ...Chapter 4 Wiring MS300 IP66 NEMA 4X 4 6 This page intentionally left blank...
Страница 83: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 33 The drive with MKMX SWA...
Страница 84: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 34 MKMX SWB Applicable model Frame B Unit mm inch...
Страница 85: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 35 The drive with MKMX SWB...
Страница 86: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 36 MKMX SWC Applicable model Frame C Unit mm inch...
Страница 87: ...Chapter 7 Optional Accessories MS300 IP66 NEMA 4X 7 37 The drive with MKMX SWC...
Страница 96: ...Chapter 8 Optional Cards MS300 IP66 NEMA 4X 8 6 Frame C Torque 10 20 kg cm 17 4 Ib in 1 96 Nm Figure 8 7...
Страница 126: ...Chapter 10 Digital Keypad MS300 IP66 NEMA 4X 10 8 This page intentionally left blank...