Trial Operation and Panel Display ASDA-A3
4-12
Revision December, 2017
4
4.4.2 Force DO on
You can switch to the Diagnosis mode by the following steps. Set P2.008 to 406 and enable the
function to force DO on. Then, set the DO by binary method with P4.006. When the parameter
value is 2, it forces DO2 on. When the value is 5, it forces DO1 and DO3 on. No data is retained
in this mode. The mode returns to the normal DO mode after cycling the power. You can also set
P2.008 to 400 to switch to the normal DO mode.
Force to enable DO
mode
Force DO1 on
S
Force DO2 on
Force DO3 on
Force DO4 on
Force DO5 on
Force DO1 and DO3 on
Force DO1, DO2, and DO3 on
S
S
Note: P4.006 is displayed in hexadecimal format. Therefore, it does not show the fifth 0.
Содержание ASD-A3-0121
Страница 13: ...Revision December 2017 This page is intentionally left blank...
Страница 43: ...Installation ASDA A3 2 20 Revision December 2017 2 This page is intentionally left blank...
Страница 105: ...Wiring ASDA A3 3 62 Revision December 2017 3 This page is intentionally left blank...
Страница 187: ...Operation Mode ASDA A3 6 36 Revision December 2017 6 This page is intentionally left blank...
Страница 467: ...Parameters ASDA A3 8 210 Revision December 2017 8 This page is intentionally left blank...
Страница 483: ...MODBUS Communication ASDA A3 9 16 Revision December 2017 9 This page is intentionally left blank...
Страница 577: ...Specifications ASDA A3 A 28 Revision December 2017 A This page is intentionally left blank...
Страница 597: ...Accessories ASDA A3 B 20 Revision December 2017 B This page is intentionally left blank...
Страница 603: ...4 Revision December 2017 This page is intentionally left blank...