  Connect the two battery cables to the two battery packs’ connectors 

respectively. For each battery cable, use the two screws and two 

standoffs (provided in the package with the battery cable) to firmly fix the 

battery cable on the battery pack. See 

Figure 13

.

Standoffs 

& Screws

Battery Cables

6

15/ 20kVA UPS

Delta External Battery Packs

(RT-10KB Model)

External Battery

Connectors

External Battery Connectors

(Figure 13)

NOTE: 

There are two identical external battery connectors on the 

Delta external battery pack, and you may use either of the battery 

connectors to connect to the UPS. 

 

y

Parallel the Delta External Battery Packs with the 5/ 6/ 8/ 10kVA UPS

To extend the backup time, you may parallel the Delta external battery packs 

before connecting them to the UPS. The Delta external battery pack has two 

models, RT-6KB and RT-10KB. The two models’ parallel methods are similar. 

Thus, in 

Figure 14

, only the illustration of RT-6KB model is taken for example.

WARNING: 

For parallel application, only use the same type of Delta external 

battery packs (same material No.).

1

  Use the provided battery cable ( 

1

 ) to connect each parallel Delta 

external battery pack’s battery connector ( 

4

 ). Each Delta external 

battery pack has two identical battery connectors; you can choose either 

of them for connection. Make sure that the positive cable (+) connects to 

the positive pole (+) and the negative cable (-) connects to the negative 

pole (-). Use the screws ( 

2

 ) and standoffs ( 

3

 ) (provided in the 

battery cable’s package) to fix the battery cable firmly on the parallel 

Delta external battery packs. Please see 

Figure 14

.

NOTE: 

If you want to connect more than two Delta external battery 

packs, follow the steps mentioned above.

外接

电池

连接

192

V D

C 5

0A

外接

电池

连接

192

V D

C 5

0A

断路

250

V D

C 6

3A

外接

电池

连接

192

V D

C 5

0A

断路

250

V D

C 6

3A

外接

电池

连接

92V

 DC

 50

A

外接

电池

连接

192

V D

C 5

0A

断路

250

V D

C 6

3A

外接

电池

连接

192

V D

C 5

0A

断路

250

V D

C 6

3A

1

2

3

4

Delta External Battery 

2

3

Packs (RT-6KB Model)

(Figure 14)

2

  After paralleling the Delta external battery packs, follow the steps 

mentioned in ‘

Connect the Delta External Battery Pack with the 

5/ 6/ 

8/ 10kVA 

UPS

’ to complete the connection between the UPS and the 

parallel Delta external battery packs.

 

y

Connect the 15/ 20kVA UPS (Single Unit) with the Parallel Delta External 

Battery Packs

WARNING: 

For parallel application, only use the same type of Delta external 

battery packs (same material No.).

If it is not for common battery application, each 15/ 20kVA UPS must connect 

to at least two external battery packs, and the number of battery packs must be 

the multiple of two and only two of the battery packs need to be connected to 

the 15/ 20kVA UPS. The Delta external battery pack has two models, RT-6KB 

and RT-10KB. The two models’ parallel methods and UPS connection methods 

are similar. Thus, in the following instructions and 

Figure 15

, only one 15/ 

20kVA UPS connecting to four parallel Delta external battery packs (model RT-

10KB) is taken for example.

1

  Each Delta external battery pack has two identical battery connectors; 

you can choose either of them for the battery cable connection 

mentioned below. Use the battery cable (provided in the Delta external 

battery pack) to connect the 1

st

 and 3

rd

 parallel Delta external battery 

packs’ battery connectors. Use the battery cable (provided in the Delta 

external battery pack) to connect the 2

nd

 and 4

th

 parallel Delta external 

battery packs’ battery connectors. Make sure that the positive cable (+) 

connects to the positive pole (+) and the negative cable (-) connects to 

the negative pole (-). Please see 

Figure 15

.

2

  After paralleling the Delta external battery packs, follow the steps 

mentioned in ‘

Connect the Delta External Battery Pack with the 1

5/   

20kVA 

UPS

’ to complete the connection between the UPS and any two 

of the parallel Delta external battery packs. Please see 

Figure 15

.

 

Battery Cables

Battery Cables

(Provided in the

Package of the UPS)

(Provided in the Package of the

Delta External

Battery Packs

15/ 20kVA UPS

Delta External Battery Packs)

(RT-10KB Model)

(Figure 15)

 

y

Connect the 15/ 20kVA UPSs (Parallel Units) with the Delta External 

Battery Packs

If it is not for common battery application, each 15/ 20kVA UPS must connect 

to at least two external battery packs, and the number of battery packs must 

be the multiple of two and only two of the battery packs need to be connected 

to the 15/ 20kVA UPS. The Delta external battery pack has two models, RT-

6KB and RT-10KB. The two models’ parallel methods and UPS connection 

methods are similar. Thus, in the following instructions and 

Figure 16

, each 

of the two parallel 15/ 20kVA UPSs connecting to two parallel Delta external 

battery packs (model RT-10KB) is taken for example.

1

  Use the two battery cables (provided in the 1

st

 parallel 15/ 20kVA UPS’s 

package) to connect the 1

st

 parallel 15/ 20kVA UPS with its two Delta 

external battery packs. Use the two battery cables (provided in the 2

nd 

parallel 15/ 20kVA UPS’s package) to connect the 2

nd

 parallel 15/ 20kVA 

UPS with its two Delta external battery packs. Please see 

Figure 16

 and 

cross-refer to ‘

Connect the Delta External Battery Pack with the 1

5/   

20kVA 

UPS

’.

BREAKER 

250V DC 63A

EXTERNAL BATT. CONNECTOR 

240V DC 46A

EXTERNAL BATT. CONNECTOR 

240V DC 46A

PA

R

AL

LE

L 2

PA

RA
LLE

L 1

RS-485

P1 P2 P3

P4

DRY CONTACT

REPO

MINI SLOT

-

+

-

+

L1

L2

L3

N

PE

T

U

P

N

S

S

A

P

Y

B

T

U

P

N

C

A

C

D

V

0

4

2

±

T

T

A

B

C

D

V

0

4

2

±

T

T

A

B

L1

L2

L3

N

PE

N

L3

L2

L1

AC OUTPUT

PA

R

AL

LE

L 2

PA

R

AL

LE

L 1

RS-485

P1 P2 P3

P4

DRY CONTACT

REPO

MINI SLOT

-

+

-

+

L1

L2

L3

N

PE

T

U

P

N

S

S

A

P

Y

B

T

U

P

N

C

A

C

D

V

0

4

2

±

T

T

A

B

C

D

V

0

4

2

±

T

T

A

B

L1

L2

L3

N

PE

N

L3

L2

L1

AC OUTPUT

BREAKER 

250V DC 63A

EXTERNAL BATT. CONNECTOR 

240V DC 46A

EXTERNAL BATT. CONNECTOR 

240V DC 46A

BREAKER 

250V DC 63A

EXTERNAL BATT. CONNECTOR 

240V DC 46A

EXTERNAL BATT. CONNECTOR 

240V DC 46A

BREAKER 

250V DC 63A

EXTERNAL BATT. CONNECTOR 

240V DC 46A

EXTERNAL BATT. CONNECTOR 

240V DC 46A

15/ 20kVA UPS

15/ 20kVA UPS

Delta External

Battery Pack

(RT-10KB Model)

Delta External

Battery Pack

(RT-10KB Model)

Delta External

Battery Pack

(RT-10KB Model)

Delta External

Battery Pack

(RT-10KB Model)

(Figure 16)

NOTE: 

If you want to connect more than two Delta external battery 

packs (the number of battery packs must be the multiple of two) to 

any parallel 15/ 20kVA UPS, please refer to the steps above.

Continue to the Next Page

 

