26
(Figure 6-8: MBB Bus Bar Installation for Dual Source Input & Single Phase
Configuration)
6.3.3. Dual Source Input
&
Three Phase Output
1. Install the bus bars following
Figure 6-9
.
2. Connect to AC source (L1/ L2/ L3/ N): connect L1 to
mL1
; L2 to
mL2
; L3 to
mL3
;
N
*
1
to one of the
N
terminals.
3. Connect to bypass source (L1/ L2/ L3/ N): connect L1 to
bL1
; L2 to
bL2
; L3 to
bL3
.
4. Connect to the loads (L1/ L2/ L3/ N): connect the loads’ L1/ L2/ L3 to
L1
/
L2
/
L3
respectively and the loads’ N to one of the
N
terminals.
NOTE:
*
1
For dual-source input configurations, the main AC source and the
bypass source must use the same neutral (N).