Technical Specifications

7

Model

1000VA

Capacity

1kVA/600W

Nominal 
Input Voltage

230 Vac

Input Voltage Range

170 ~ 280 Vac

Output Voltage 

230 Vac ± 10% (Bat. mode)

Transfer Time

Typical 2 ~ 6 ms

Waveform

Simulated Sine Wave

Battery Type & No.

12V/7Ah x 2

Charging Time

Typical 6 ~ 8 hours 

Dimensions             
(D x W x H)

320 x 130 x 182 mm

Net Weight (kgs)

8.2

Humidity

0 - 90% RH @ 0 - 40°C (non-condensing)

Noise Level

Less than 40dB

* Specifications are subject to change without notice. 

                        

Warranty

8

Seller warrants this product, if used in accordance with all applicable 

instructions, to be free from original defects in material and workman-

ship within the warranty period. If the product has any failure problem 

within the warranty period, Seller will repair or replace the product at its 

sole discretion according to the failure situation.

This warranty does not apply to normal wear or to damage resulting 

from improper installation, operation, usage, maintenance or irre-

sistible force (i.e. war, fire, natural disaster, etc.), and this warranty 

also expressly excludes all incidental and consequential damages. 

Maintenance service for a fee is provided for any damage out of the 

warranty period. If any maintenance is required, please directly contact 

the supplier or Seller.

WARNING:

  

The individual user should take care to determine prior to 

use whether the environment and the load characteristic are 

suitable, adequate or safe for the installation and the usage of 

this product. The Quick Guide must be carefully followed. Seller 

makes no representation or warranty as to the suitability or 

fitness of this product for any specific application.

Safety Caution

5

SAVE THESE INSTRUCTIONS-This quick guide contains important 

instructions that should be followed during installation and 

maintenance of the UPS and battery (batteries).

y

y

The UPS utilizes voltage that may be hazardous. Do not attempt 

to disassemble the unit. The unit contains no user replaceable 

parts. Only factory service personnel may perform repairs.

y

y

This pluggable type A equipment with battery (batteries) already 

installed by the supplier is operator installable and may be oper-

ated by laymen.

y

y

The mains socket outlet that supplies the UPS shall be installed near 

the UPS and shall be easily accessible.

y

y

During the installation of this equipment it should be assured that 

the sum of the leakage current of the UPS and the connected loads 

does not exceed 3.5mA.

y

y

Connection to any other type of receptacle other than a two-pole, 

three-wire grounded receptacle may result in shock hazard as well 

as violate local electrical codes.

y

y

In the event of an emergency, press the ON/ OFF Button and dis-

connect the power cord from the AC power supply to properly dis-

able the UPS.

y

y

Do not allow any liquid or any foreign object to enter the UPS. Do 

not place beverages or any other liquid-containing vessels on or 

near the unit.

y

y

The unit is intended for installation in a controlled environment (tem-

perature controlled, indoor area free of conductive contaminants). 

Avoid installing the UPS in any location where there is standing or 

running water, or excessive humidity.

y

y

Do not plug the UPS input into its own output.

y

y

Do not attach a power strip or surge suppressor to the UPS.

y

y

Do not attach non-computer-related items, such as medical equip-

ment, life-support equipment, microwave ovens, or vacuum cleaners 

to the UPS.

y

y

Do not dispose of battery (batteries) in a fire as they may explode.

y

y

A battery can present a risk of electrical shock and high short circuit 

current. The following precautions should be observed when working 

on batteries:

1. Remove watches, rings, or other metal objects from the hands.

2. Use tools with insulated handles.

3. Wear rubber gloves and boots.

4. Do not lay tools or metal parts on top of battery (batteries).

5. Disconnect charging source prior to connecting or disconnecting   

     the terminals of battery (batteries).

y

y

Internal battery voltage is 12Vdc. Battery type is sealed, lead-acid, 

6-cell battery.

y

y

Servicing of batteries should be performed or supervised by person-

nel knowledgeable of batteries and the required precautions. Keep 

unauthorized personnel away from batteries.

y

y

When replacing battery (batteries), replace with the same number 

and type of sealed lead-acid battery (batteries).

y

y

Do not open or mutilate the battery or batteries. Release electrolyte 

is harmful to the skin and eyes. It may be toxic.

y

y

Attention! Hazardous through electric shock. Even disconnection of 

this unit from the mains, hazardous voltage still may be accessible 

through supply from the battery (batteries). The battery supply should 

be therefore disconnected in the plus and minus pole at the connec-

tors of the battery (batteries) when maintenance or service work inside 

the UPS is necessary.

y

y

To reduce the risk of overheating the UPS, do not cover the UPS’s 

cooling vents and avoid exposing the unit to direct sunlight or install-

ing the unit near heat emitting appliances such as heaters or furnaces.

y

y

Unplug the UPS prior to cleaning and do not use liquid or spray deter-

gent.

Troubleshooting

6

Problem                                

Possible Cause

Solutions

Nothing is 

displayed 

on the LCD 

panel

The UPS is not on.

Press the ON/ OFF Button again 

to turn on the UPS.

Battery voltage is too 

low.

Charge the battery (batteries) at 

least 6 hours.

Battery fault.

Replace the battery (batteries).

The UPS 

always runs 

in battery 

mode.

The power cord    

becomes loose.       

Re-plug the power cord.

The circuit breaker is 

tripped.

Reset the breaker.

The UPS 

continuously 

beeps.

Please check the 

Fault Code Table

 for 

the details.

Please check the 

Fault Code 

Table

 for the details.

Backup time 

is too short.

Battery voltage is too 

low.

Charge the battery (batteries) at 

least 6 hours.

Overload.

Remove some unnecessary 

loads. Before reconnecting 

equipment, please verify that the 

load matches the UPS capability 

specified in the specs.

Battery defect.

Replace the battery (batteries).

If any abnormal situations occur that are not listed above, please call for 

service immediately.

Copyright © 2019 by Delta Electronics Inc. All Rights Reserved. 

This Quick Guide is subject to change without prior notice.

Version Date : 2019_02_27