Configuration of connection pipe

1. Standard length of connection pipe

    ● 5m, 7.5m, 8m.

4. The additional refrigerant oil and refrigerant charging required after prolonging  

    connection pipe

    ● After the length of connection pipe is prolonged for 10m at the basis of 

       standard length, you should add 5ml of refrigerant oil for each additional 5m 

       of connection pipe.

    ● The calculation method of additional refrigerant charging amount (on the basis 

       of liquid pipe):

             Additional refrigerant charging amount = prolonged length of liquid pipe × 

            additional refrigerant charging amount per meter

    ● When the length of connection pipe is above 5m, add refrigerant according to 

       the prolonged length of liquid pipe. The additional refrigerant charging amount 

       per meter is different according to the diameter of liquid pipe. See the 

       following sheet.

Cooling 

capacity

Cooling 

capacity

5000Btu/h

(1465W)

24000Btu/h

(7032W)

7000Btu/h

(2051W)

28000Btu/h

(8204W)

9000Btu/h

(2637W)

36000Btu/h

(10548W)

12000Btu/h

(3516W)

42000Btu/h

(12306W)

18000Btu/h

(5274W)

48000Btu/h

(14064W)

Max height 

difference

Max height 

difference

Max length 

of connec-

tion pipe

Max length 

of connec-

tion pipe

15

25

5

10

15

30

5

10

15

30

5

20

20

30

10

20

25

30

10

20

2.

 

Min. length of connection pipe is 3m.

3.

 

Max. length of connection pipe and max. high difference.

Содержание 26WB009I24-028DWFXZ

Страница 1: ...www delta dct com MINI SPLIT INVERTER INSPIRE Ultra 16 INSTRUCTION MANUAL WARNING Read and follow all safety precautions in Instruction Manual improper use can cause serious injury 26WC Series...

Страница 2: ...26WC012I24 035DWG 26WC018I24 053DWG 26WC024I24 070DWG 26WC009I24 028DWG...

Страница 3: ...6 Screen Operation Guide Buttons on remote controller 7 Introduction for icons on display screen 7 Introduction for buttons on remote controller 8 Function introduction for combination buttons 10 Oper...

Страница 4: ...pliance Cleaning and user maintenance shall not be made by children without supervision years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowl...

Страница 5: ...amage Precautions WARNING conditioner and disconnect power immediately and then If the air conditioner operates under abnormal conditions it may cause malfunction electric shock or fire hazard Do not...

Страница 6: ...les before using the air conditioner An all pole disconnection switch having a contact separation Must follow the electric safety regulations when installing the unit grounding wire of power socket Pr...

Страница 7: ...nnected by a professional national wiring regulations requirement of NEC and CEC by authorized personnel only Precautions WARNING wire which can t be used for other purposes The grounding resistance s...

Страница 8: ...the line For the air conditioner without plug an circuit break far away from animals or plants If it is unavoidable please add the fence for safety purpose Select a location which is out of reach for...

Страница 9: ...Unit Outdoor Unit air inlet panel aux button horizontal louver air outlet heating indicator temp indicator cooling indicator power indicator receiver window drying indicator display remote control ai...

Страница 10: ...6 7 1 3 5 2 4 6 7 ON OFF button MODE button button FAN button SWING button SLEEP button TIMER button Timer on Timer off Sending signal swing operation sleep operation lock set speed Set time Set temp...

Страница 11: ...be displayed either Press FAN button to adjust fan speed When selecting cool mode air conditioner will operate under cool mode Then press or button to adjust set temperature Press FAN button to adjus...

Страница 12: ...ress or button to adjust the time for Timer Off Pressing or button once will increase or decrease the time by 0 5h Hold or button for 2s time will change quickly Release the button after your required...

Страница 13: ...p LOCK indicator on remote controller is ON If you operate the remote controller remote controller won t send signal Note Range of time setting is 0 5 24h The interval between two motions can t exceed...

Страница 14: ...or there s no display please replace batteries 1 After putting through the power press ON OFF button on remote controller to turn on the air conditioner 2 Press MODE button to select your required mod...

Страница 15: ...utton panel Clean and maintenance Turn off the air conditioner and disconnect the power before cleaning the air conditioner to avoid electric shock Do not wash the air conditioner with water to avoid...

Страница 16: ...pen panel Pull out the panel to a certain Use dust catcher or water to the water below 45 to clean it and then put it in a shady and cool place to dry panel cover tightly operation environment clean f...

Страница 17: ...nage pipe is damaged 1 Disconnect power supply 3 Check whether mounting bracket for outdoor unit is damaged or corroded If yes please contact dealer Notice for recovery 1 Many packing materials are re...

Страница 18: ...oom Pull out the plug Reinsert the plug after about 3min and then turn on the unit again Signal receiving range is 8m Remove obstacles Select proper angle and point the remote controller at the re cei...

Страница 19: ...door temperature and hum idity is high Because indoor air is cooled rapidly After a while indoor temperature and humidity will be decrease and mist will disappear Phenomenon Check items Solution Set t...

Страница 20: ...t again Outdoor unit has vapor Heating mode is turned on During defrosting under he ating mode it may generate vapor which is a normal phenomenon Water flowing noise Air conditioner is turned on or tu...

Страница 21: ...maged There s abnormal sound during operation Circuit break trips off frequently Air conditioner gives off burning smell Indoor unit is leaking If the air conditioner operates under abnormal condition...

Страница 22: ...At least 30cm At least 300cm At least 200cm Space to the floor Space to the obstruction Space to the obstruction Space to the obstruction Space to the ceiling Space to the obstruction Space to the obs...

Страница 23: ...ified power cord Basic requirement Outdoor unit Indoor unit Installing the unit in the following pla ces maycause malfunction If it is un avoidable please consult the local dealer 1 The place with str...

Страница 24: ...nal wiring regulations 10 Installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel only grounding with specialized grounding device by a professional Pl...

Страница 25: ...ping hole 2 Open a piping hole with the diameter of 55 or 70 on the selected outlet pipe position In order to drain smoothly slant the piping hole on the wall slightly downward to the outdoor side wit...

Страница 26: ...ng out the pipe from left or right please cut off the corresponding hole on the bottom case cut off the hole left right 1 The pipe can be led out in the direction of right rear right left or rear left...

Страница 27: ...55 60 65 70 75 15 20 insulating pipe 1 Connect the drain hose to the outlet pipe of indoor unit 2 Bind the joint with tape outlet pipe drain hose drain hose tape outlet pipe drain hose insulating pip...

Страница 28: ...st be installed in the line The circuit break should be all pole parting and the contact parting distance should be more than 3mm 3 Remove the wire clip connect the power connection wire to the wiring...

Страница 29: ...parately at the end Note The power cord and control wire can t be crossed or winding The drain hose should be bound at the bottom drain hose band connection pipe indoor power cord Step nine hang the i...

Страница 30: ...t least 3cm above the floor in order to install drain joint For the unit with cooling capacity of 2300W 5000W 6 expansion screws are needed for the unit with cooling capacity of 6000W 8000W 8 expansio...

Страница 31: ...t with torque wrench by referring to the sheet below handle screw gas pipe liquid pipe liquid valve gas valve union nut pipe joint Hex nut diameter Tightening torque N m 6 9 52 12 16 19 30 40 45 55 60...

Страница 32: ...slightly dow nwards The drain hose can t be curved raised and fluctuant etc The water outlet can t be placed in water in order to drain smoothly Installation of outdoor unit U shaped curve wall drain...

Страница 33: ...ure decreases there may be leakage 5 Remove the piezometer open the valve core of liquid valve and gas valve completely with inner hexagon spanner 6 Tighten the screw caps of valves and refrigerant ch...

Страница 34: ...unit grounded securely It may cause electric leakage Does the power cord follow the speci fication It may cause malfunction or damaging the parts Is there any obstruction in the air inlet and outlet I...

Страница 35: ...rant charging amount per meter When the length of connection pipe is above 5m add refrigerant according to the prolonged length of liquid pipe The additional refrigerant charging amount per meter is d...

Страница 36: ...4a Diameter of connection pipe Liquid pipe mm Gas pipe mm 6 6 or 9 52 12 16 19 22 2 9 52 or 12 16 or 19 19 or 22 2 25 4 or 31 8 _ _ Cooling only g m Cooling and heating g m 15 15 30 60 250 250 350 350...

Страница 37: ...n suitable insulating pipe D Put on the union nut Remove the union nut on the indoor connection pipe and outdoor valve install the union nut on the pipe union pipe pipe E Expand the port Expand the po...

Страница 38: ......

Страница 39: ...Thank you for Choosing airconditioners Perfectly engineered for your comfort www delta dct com 66129916516...

Отзывы: