background image

WARNING: 

This kit and the cable used with it must

be installed by a qualified electrician. All assembly, 
installation, and test instructions must be followed.

 

Improper installation can result in property damage, 
serious injury, and/or death due to electric shock and fires. 
Please call Delta-Therm Corporation at 1-800-526-7887 
with any installation or operating questions.

DELTA-THERM

 Corporation, 

6711 Sands Road Suite A, Crystal Lake, IL 60014

(847)

526-2407   Fax (847) 526-4456    

(800) 526-7887

A.

Heat Shrink Sleeve .375” x 6”  (1 x 15cm)

B.

Cable Connector Assembly

C.

Standoff Bracket

D. High Temp 

Fiberglass Tape

 (60" x 1/2")

E.

Heat Shrink Sleeve .5” x 1.5” (1 x 11cm)

F.

Ground Screw

G.

Closed-End Crimp Connectors (2)

H.

Ring Connector

I.

.75” Sealing Locknut

J.

Heat Shrink Sleeve .25” x 1.5” (.5 x 11cm)

K.

Heat Shrink Sleeve .125” x 2.5” (.3 x 6cm)

L.

Caution Labels (6)

 Small

TOOLS NEEDED

Crimping Tool

Wire Stripper/Cutter

Utility Knife

Flat-Blade Screwdriver

Needle-Nose Pliers

Adjustable Wrench

Heat Gun 

(750

F)

Measuring Tape

A

B

C

D

F

E

G

H

I

J

K

L

Installation Instructions

 

PCK-

TT

Power Connection Kit: 

TT

 Series for Pipe Tracing

CONNECTINg TO POwER

 

For braided Cable

1.

Remove 6" (15cm) of any optional overjacket.

2.

Push the braid back to loosen it.

3.

Approximately 6" (15cm) from the end of the

cable,

 

spread the braid strands to create an

opening.

4.

Bend the cable at the opening, then pull the cable

through the opening to free the braid.

5.

Twist the braid into a cold lead, then trim the cold

lead to

 

remove the tapered end.

Detail 1.

6

.

 

Insert the cable through the connector cap, the gland

washer, and the grommet, leaving 4” (10cm)

exposed

 

from the end of the rubber grommet.

Detail 2. 

continued...

.