P a g e

                                                                                   

An air conditioner is designed to dehumidify and extract heat from an area, or provide heat to an area.  
The cooling is done using a simple refrigeration cycle.  A product of this simple refrigeration cycle is 
excess humidity that condenses to a liquid.   
 
DELTA-T air conditioners are designed using an advanced refrigeration cycle and are equipped with a 
Condensate Removal System that changes the excess humidity liquid into a vapor which is then 
vented to the atmosphere.   In the event of excess water vapor where the enclosure door has been left 
open there is an overflow hole on the bottom of every unit.  Please contact ISC Inc. if you encounter 
excess water coming from your air conditioner. 

 

Preliminary Testing 
 

Before mounting the air conditioner to the enclosure, test for proper operation.  Follow the steps below 
prior to installation. 
 

 

WARNINGS 

The air conditioner must sit upright for 24 hours to assure the compressor oil has drained down to the 
compressor.  Check the unit label to assure the electric power available to the air conditioner is the 
proper voltage and phase.  Check the electric power source for proper ground wire and neutral wire 
installation per 2008 NEC.  Assure that the electric power is protected by a circuit protection device; 
refer to the Unit Specification section in this manual for proper circuit protection sizing.  

 

 

Connect a power source to the air conditioner and turn on the power switch.   The evaporator 
fan will start and the digital controller will power up. If cooling is called for, the compressor will 
start in 3 minutes. 

 

If desired, change the cooling set point.  Refer to Digital Temperature Controller Programming 
section on this manual for details on changing the set point.  Factory default settings should be 
satisfactory; however you may want to adjust heat, cooling and alarm set points for your 
specific application.  

 

The condenser fan is controlled by the refrigerant high heat pressure and will turn on later 
when the operating pressure builds up.  This feature allows low ambient operation and 
reduces current inrush at initial power on. 

 

Run the air conditioner for 15 minutes; during this time the condenser fan will turn on after the 
condenser coil warms up.

 Note: Ambient Temperature must be at least 75°F.

 

 

Turn the unit off if the equipment makes any unexpected or hard mechanical noises or 
vibrations and refer to the troubleshooting guide in this manual. 

 

The supply cold air should be at least 10°F colder than the return air entering the unit.  If it is 
not, refer to the troubleshooting guide in this manual; 

 

When you are satisfied that the unit is operating properly, turn unit off, disconnect the power 
and mount the unit on the enclosure in accordance with the Mounting the Air Conditioner 
section in this manual. 

Содержание RZ-04A-D48 Series

Страница 1: ...User Technical Manual RZ 04A D48 Series Rev 2 3 ...

Страница 2: ...ption description 1 9 09 25 2018 B Slotnick Updated warranty 2 0 02 21 2019 B Slotnick Updated mounting instructions alarm settings RMA procedure 2 1 06 20 2019 B Slotnick Updated preliminary testing instructions compressor protection default setting field serviceable parts 2 2 08 20 19 B Slotnick Updated preventative maintenance warranty information 2 3 06 03 20 B Slotnick Updated System Faults A...

Страница 3: ...oving the Air Conditioner 5 Unit Label 5 Operation 6 Preliminary Testing 6 Mounting the Air Conditioner 7 Unit Specifications 8 Options 10 System Faults 13 Digital Temperature Controller Programming 13 Preventative Maintenance 16 Field Serviceable Parts 17 Safety Information 17 Troubleshooting Guide 18 Physical Dimensions 21 Electrical Schematic 23 Warranty Information 24 Return Material Authoriza...

Страница 4: ...e Equipment ISC air conditioning equipment is designed manufactured and packed to prevent damage from normal handling shock and vibration during shipment It is necessary to inspect your equipment upon receipt to ensure that there is no visual or hidden damage Upon receipt of the equipment ensure that it is always top side up as indicated by THIS SIDE UP labels This ensures that the compressor oil ...

Страница 5: ... template below and keep this information in a safe place for warranty and ordering parts To prevent damage to equipment electrical panel and wiring and to prevent personal injury assure that the power source is compatible with the equipment before operating When recharging refrigeration type and amount must be the same as shown on the unit label or air conditioner will not operate properly or may...

Страница 6: ...tric power is protected by a circuit protection device refer to the Unit Specification section in this manual for proper circuit protection sizing Connect a power source to the air conditioner and turn on the power switch The evaporator fan will start and the digital controller will power up If cooling is called for the compressor will start in 3 minutes If desired change the cooling set point Ref...

Страница 7: ...and from inside the enclosure use the fasteners supplied to attach the air conditioner to the enclosure Screw all fasteners hand tight Then torque to 96 in lbs These fasteners should be checked periodically to ensure that they have not become loose due to vibration The air conditioner is provided with a power terminal block Ensure that the power supplied is compatible with the air conditioner s po...

Страница 8: ...000 BTUH Standard Maximum Ambient 131 F Unit Weight 103 lbs Model Operating Voltage Range Volts Loading Current Running Current Amps SCCR Short Circuit Current Rating Amps Recommended Fuse Selection Amps KVA Rating Refrigerant Type Refrigerant Amount ounces Low High Unit Pressures psi RZ 04A D48 43 53 VDC 22 3 40 Amp Fast Acting 1 1 R134a 13 25 39 307 SCCR rating is based on the SCCR rating for th...

Страница 9: ...4421 Tradition Trail Plano Texas 75093 972 964 2700 800 836 7472 URL www iscenclosurecooling com Email iscinfo iscsales com SP ENG 210 D48 06 Rev 2 3 9 P a g e THIS PAGE IS INTENTIONALLY LEFT BLANK ...

Страница 10: ...m Delay At the default settings the Dry Contact initial conditions are normally open and or normally closed When the unit is powered on and the temperature exceeds 105 F for a period longer than 3 minutes the Dry Contact will activate At this time the normally open contact will close and the normally closed contact will open This state will remain until the temperature has decreased to 103 F Note ...

Страница 11: ... high ambient application upgrades from our Standard Maximum Ambient temperature of 125 F With this option we can optimize the Air Conditioner during manufacturing to achieve improved performance at high ambient conditions Condenser Filters For environments with airborne dirt dust oil etc these air conditioners can be ordered with a 2 pleated extended surface area filter Corrosion Protection The c...

Страница 12: ...e installed anywhere in your enclosure This allows you to have the flexibility to monitor and maintain the temperature at any specific location of your enclosure Remote Controller When having our Programmable Digital Controller on the face of our Air Conditioner does not fit your application ISC offers the Remote Controller Option This option moves the controller into your enclosure using a 10 cab...

Страница 13: ...oller and the compressor will turn off after a 2 minute time delay A thermal overload protects the compressor against faults In the event that the snowflake status LED is on but is not flashing and the compressor is not running an internal fault may have occurred Refer to the Troubleshooting Guide in this manual Digital Temperature Controller Programming For the end user this section will provide ...

Страница 14: ...or DOWN arrow key Press the SET key to display its value 4 Use the UP or DOWN arrow key to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP arrow keys or wait 15 seconds without pressing a key Note The set value is stored even when the procedure is exited by waiting for the time out to expire HOW TO LOCK THE KEYPAD 1 Press and hold the UP...

Страница 15: ... Alarm Only 2 HA2 Condenser High Temperature Alarm P2 153 F for 3 minutes Compressor turned Off by pressure switch if temperature continues to rise 2 LA2 Condenser Low Temperature Alarm P2 50 F for 3 minutes No Action Alarm Only 2 CA Evaporator Coil Alarm Low Pressure for 2 minutes Compressor Off 2 noP Invalid Probe Selected Low Evaporator Coil No Action Alarm Only 2Note When both Heater and Dry C...

Страница 16: ...ended to enhance air filter efficiency Replacement filters are readily available from ISC Customer Service DO NOT operate the air conditioner without the air filter Such operation will allow the condenser coil to become dirty and lose efficiency causing overheating and diminished cooling capacity Periodically remove dust from the components inside the condenser section of the air conditioner with ...

Страница 17: ...erter for Digital Controller 52314 1 Low Pressure Switch 38151 1 3 High Pressure Switch 38006 1 3 Condenser Fan Cut In Pressure Switch 38001 1 3 Temperature Probe 52126 1 Thermal Expansion Value TXV 32012 1 Compressor 31509 1 48 VDC Compressor Controller 31509 2 Gasket Installation Kit 71401 N234 Evaporator Fan 41010 4 1 Condenser Fan 41010 6 1 Filter Media 44202 12 pack Safety Information Unit is...

Страница 18: ... position ON OFF Toggle Switch then Retry Verify input power meets voltage requirements as shown in the UL label YES If problem is still present contact technical support Unit Overheats Insufficient Cooling Is Filter Clean NO Clean Replace Filter YES Are Condenser Evaporator Fans ON NO Check for Faulty Fan replace YES Is Condenser Coil dirty YES Clean Coil NO NO Is Evaporator Coil Frozen Iced YES ...

Страница 19: ... Use meter3 Check for faulty evaporator fan3 Measure Temperature at Evaporator Verify Heat Load Requirements Is unit capacity adequate for internal head load Possible low refrigerant Is compressor thermal overload open Use ohm meter 3 Check for error code CA LA HA LA2 HA2 P1 or P2 YES NO Check contactor circuit Does it have power 3 NO YES Refer to Alarm Signals in Digital Temperature Controller Pr...

Страница 20: ...controller CA YES NO Check Low Pressure Switch Connections and Verify Pressure switch is closed Use meter 3 P1 or P2 NO YES Check probe connections potential faulty probe LA LA2 HA HA2 YES Refer to Alarm Signals in Digital Temperature Controller Programming Section Fuse Circuit Protection Nuisance Trip Is fuse opening as soon as unit turns on NO YES Check incoming power supply and connections for ...

Страница 21: ... Physical Dimensions Water overflow excessive Check drain is it plugged YES NO Clean condensate pan and drain add 1 tbsp bleach to upper pan monthly to kill mold Is Air Conditioner sealed against enclosure properly tightly sealed and door closed YES Contact Customer Service NO Ensure air tight seal between air conditioner and enclosure Make sure door is closed ...

Страница 22: ...4421 Tradition Trail Plano Texas 75093 972 964 2700 800 836 7472 URL www iscenclosurecooling com Email iscinfo iscsales com SP ENG 210 D48 06 Rev 2 3 22 P a g e THIS PAGE IS INTENTIONALLY LEFT BLANK ...

Страница 23: ... 06 Rev 2 3 23 P a g e Electrical Schematics System Schematic Digital Controller Schematic Note Schematics apply to all voltages optional accessories wiring not provided in this document If you require electrical schematic with options contact our technical support and provide your model number Drawing 51201 D48 Rev D RZ 04A D48 Cool Only ...

Страница 24: ...t at the ISC factory in Dallas Texas Use of equipment for other than its designed purpose or operating conditions Operation in harsh oily corrosive or other abnormal environmental conditions without the proper filtration sealing protective coatings and or weather protection or cosmetic corrosion that does not affect operation Damage to hermetic system resulting from continuous operation with dirty...

Страница 25: ...nd contact info email phone number and address Shipping method Pack unit in a suitable packing for shipment preferably the original packaging if available If suitable packing is not available arrange for packaging to be shipped to you Air Conditioners must be returned in an upright position properly secured to a pallet Tip unit to empty water from the evaporator and boil off pans Clearly mark the ...

Страница 26: ...ly channels facing UP 4 Starting from the left connect the wires by inserting them into the lower receptacles located on the front of connector in the following order NOTE If using stranded wires it may be difficult to insert into the receptacles without releasing the spring tension as described below in the removal instructions The wires can be tinned or pin terminals as shown above or pin ferrul...

Отзывы: