1800 Hurd Drive ● Irving, Texas 75038 ● (972) 580-0200 ● (888) 580-0202 ● Fax (972) 580-0277
URL: www.thermal-edge.com ● Email:
SP-ENG-210-D48-06 Rev 2.4 8 |
P a g e
Unit Specifications
The following table provides electrical and refrigeration specifications for the NE040-D48 Series Air
Conditioners.
NE040-D48 Series
Nominal Capacity Rating: 4,000 BTUH
Standard Maximum Ambient: 131°F
Unit Weight: 103 lbs.
Model
Operating
Voltage
Range
(Volts)
Loading
Current
(Running
Current)
(Amps)
SCCR
(Short
Circuit
Current
Rating)
(Amps)
Recommended
Fuse Selection
(Amps)
KVA Rating
Refrigerant
Type
Refrigerant
Amount
(ounces)
Low/High
Unit
Pressures
(psi)
NE040D48
43 – 53 VDC
25.3
*
40 A, Fast
Acting
1.1
R134a
13.25
39 / 307
*
SCCR rating is based on the SCCR rating for the circuit protection devic e installed in the panel /
enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.