System Faults 
 

 

If any of the critical control parameters exceed limits, the compressor is turned off and an alarm 
condition is indicated on the front panel. 
 
There are three main conditions that can shut the AC compressor down: 

 

  The condenser high temperature alarm 

  The evaporator coil alarm 

  The compressor thermal overload 

 

In the event that the condenser coil overheats, a condenser high temperature alarm, 

HA2

, will flash on 

the display of the digital temperature controller and the compressor will turn off after a 3 minute time 
delay. 
 
In the case that the evaporator coil ices up or there is a leak, an evaporator coil alarm, 

CA

, will flash 

on the display of the digital temperature controller and the compressor will turn off after a 2 minute 
time delay. 
 
A thermal overload protects the compressor against faults.  In the event that the snowflake status LED 
is on, but is not flashing, and the compressor is not running, an internal fault may have occurred.  
Refer to the Troubleshooting Guide in this manual. 
 

Digital Temperature Controller Programming 
 

 

For the end user this section will provide all the necessary information to view and change all functions 
and parameters available to you.  
 

 

 

 

HOW TO SEE THE SETPOINT

…….. 

 

1. 

Press and immediately release the 

SET

 key.  The display will show the setpoint value.

 

2. 

Press and immediately release the 

SET

 key or wait for 15 seconds to display the  enclosure temperature 

again.

 

 

 

HOW TO CHANGE THE SETPOINT

…….. 

 

1. 

Press the 

SET

 key for more than 2 seconds to change the setpoint value.

 

2. 

The value of the setpoint will be displayed and the 

“F”

 LED starts blinking.

 

3. 

To change the 

SET

 value, press the 

UP

 or

 DOWN

 arrow key within 15 seconds.

 

4. 

To store the new setpoint value, press the 

SET

 key again or wait 15 seconds.

 

 

Note:

 The set value is stored even when the procedure is exited by waiting for the time -out to expire.  

Содержание EL-20B Series

Страница 1: ...User Technical Manual EL 20B Series for Class I Division 2 Hazardous Locations Rev 1 8 ...

Страница 2: ...tructions compressor protection default setting 1 6 08 20 19 B Slotnick Updated preventative maintenance warranty information 1 7 01 02 20 B Slotnick Updated field serviceable parts 1 8 06 03 20 B Slotnick Updated System Faults Alarm Signals Warranty Statement of Confidentiality The Manual and other materials contain proprietary information comprising ISC Sales Inc s trade secrets Please maintain ...

Страница 3: ...ng the Air Conditioner 5 Unit Label 5 Operation 5 Preliminary Testing 8 Mounting the Air Conditioner 9 Unit Specifications 10 Options 12 System Faults 14 Digital Temperature Controller Programming 14 Preventative Maintenance 17 Field Serviceable Parts 18 Safety Information 18 Troubleshooting Guide 19 Physical Dimensions 22 Electrical Schematic 24 Warranty Information 25 Return Material Authorizati...

Страница 4: ...ment DELTA T air conditioning equipment is designed manufactured and packed to prevent damage from normal handling shock and vibration during shipment It is necessary to inspect your equipment upon receipt to ensure that there is no visual or hidden damage Upon receipt of the equipment ensure that it is always top side up as indicated by THIS SIDE UP labels This ensures that the compressor oil is ...

Страница 5: ... the template below and keep this information in a safe place for warranty and ordering parts To prevent damage to equipment electrical panel and wiring and to prevent personal injury assure that the power source is compatible with the equipment before operating When recharging refrigeration type and amount must be the same as shown on the unit label or air conditioner will not operate properly or...

Страница 6: ... THIS APPARATUS IS SUITABLE FOR USE IN CLASS I DIVISION 2 GROUPS A B C AND D HAZARDOUS LOCATIONS OR UNCLASSIFIED LOCATIONS ONLY WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA IS KNOW TO BE FREE OF IGNITABLE CONCENTRATIONS AVERTISSEMENT RISQUE D EXPLOSION AVANT DE DECONNECTER L EQUIPEMENT COUPER LE COURANT OU S ASSURER QUE L EMPLACEMENT EST DESIGNE...

Страница 7: ... ST 22 manufactured by SEKI Controls Co Enclosure Manufacture of Material LG Chemical Ltd Designation of Material Type GP 2306F Epoxy Manufacture of Material Rhenatech GbmH Designation of Material Type EP VERGUSSMASSE 5315 Generic Name of Plastic Material epoxy resin Sealed Device Fan Motor Thermal Protector Type S01 manufactured by Thermik Geraetebau GMBH Insulation Cap Manufacture of Material E ...

Страница 8: ... in 3 minutes If desired change the cooling set point Refer to Digital Temperature Controller Programming section on this manual for details on changing the set point Factory default settings should be satisfactory however you may want to adjust heat cooling and alarm set points for your specific application The condenser fan is controlled by the refrigerant high heat pressure and will turn on lat...

Страница 9: ... from inside the enclosure use the fasteners supplied to attach the air conditioner to the enclosure Screw all fasteners hand tight Then torque to 96 in lbs These fasteners should be checked periodically to ensure that they have not become loose due to vibration The air conditioner is provided with a power cord or a power terminal block Ensure that the power supplied is compatible with the air con...

Страница 10: ... Short Circuit Current Rating Amps Recommended Circuit Protection Amps KVA Rating Refrigerant Type Refrigerant Amount ounces Low High Unit Pressures psi EL 20B 236 207 253 76 3 13 7 2 30 Amp Class CC CCMR Time Delay 3 3 R438a 64 95 327 EL 20B 486 414 506 38 2 6 9 2 15 Amp Class CC CCMR Time Delay 3 3 R438a 64 95 327 HACR Type Circuit Breakers or Time delay Fuses with the following electrical chara...

Страница 11: ...4421 Tradition Trail Plano Texas 75093 972 964 2700 800 836 7472 URL www iscenclosurecooling com Email iscinfo iscsales com SP ENG 211 100 11 Rev 1 8 11 P a g e THIS PAGE IS INTENTIONALLY LEFT BLANK ...

Страница 12: ...will activate to notify you that there is a problem in achieving your cooling set point Default Settings 105 F Dry Contact High Temperature Alarm Set Point 2 F Recovery Differential 3min Temperature Alarm Delay At the default settings the contact initial condition is normally open When the unit is powered on and the temperature exceeds 105 F for a period longer than 3 minutes the contact will acti...

Страница 13: ... Controller Programming section for details on all default settings Adjustable Temperature Probe The adjustable temperature probe provides you with a 12 temperature probe that can be installed anywhere in your enclosure This allows you to have the flexibility to monitor and maintain the temperature at any specific location of your enclosure Remote Controller When having our Programmable Digital Co...

Страница 14: ...inute time delay A thermal overload protects the compressor against faults In the event that the snowflake status LED is on but is not flashing and the compressor is not running an internal fault may have occurred Refer to the Troubleshooting Guide in this manual Digital Temperature Controller Programming For the end user this section will provide all the necessary information to view and change a...

Страница 15: ...ue 4 Use the UP or DOWN arrow key to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP arrow keys or wait 15 seconds without pressing a key Note The set value is stored even when the procedure is exited by waiting for the time out to expire HOW TO LOCK THE KEYPAD 1 Press and hold the UP and DOWN arrow keys simultaneously for more than 3 se...

Страница 16: ...larm Only 2 HA2 Condenser High Temperature Alarm P2 164 F for 3 minutes Compressor turned Off by pressure switch if temperature continues to rise 2 LA2 Condenser Low Temperature Alarm P2 50 F for 3 minutes No Action Alarm Only 2 CA Evaporator Coil Alarm Low Pressure for 2 minutes Compressor Off 2 noP Invalid Probe Selected Low Evaporator Coil No Action Alarm Only 2Note When both Heater and Dry Con...

Страница 17: ...ded to enhance air filter efficiency Replacement filters are readily available from ISC Customer Service DO NOT operate the air conditioner without the air filter Such operation will allow the condenser coil to become dirty and lose efficiency causing overheating and diminished cooling capacity Periodically remove dust from the components inside the condenser section of the air conditioner with a ...

Страница 18: ... Pressure Switch 38140 1 3 Temperature Probe 0 25m 52126 1 Temperature Probe 1 5m 52126 2 2 Temperature Probe Mounting Clip 52126 375C Condenser Fan Relay 55754 1 Thermal Expansion Value TXV 32010 1 Compressor 31076 1 Compressor Thermal Overload Internal Gasket Installation Kit 71405 HC20 Evaporator Fan Motor 41062 2 1 Condenser Fan Motor 41060 2 1 Filter Media 44260 12 pack Note 3 filters are use...

Страница 19: ...ower If problem is still present contact technical support Unit Overheats Insufficient Cooling Is Filter Clean NO Clean Replace Filter YES Are Condenser Evaporator Fans ON NO Check for Faulty Fan replace YES Is Condenser Coil dirty YES Clean Coil NO NO Is Evaporator Coil Frozen Iced YES Potential Bad Evaporator Fan check for faulty fan NO Contact Qualified Refrigeration Service Technician to check...

Страница 20: ...Fan on YES NO Is there voltage to compressor Use meter3 Check for faulty evaporator fan3 Measure Temperature at Evaporator Verify Heat Load Requirements Is unit capacity adequate for internal head load Possible low refrigerant Check for error code CA LA HA LA2 HA2 P1 or P2 NO Check contactor circuit Does it have power 3 NO YES Refer to Alarm Signals in Digital Temperature Controller Programming Se...

Страница 21: ...controller CA YES NO Check Low Pressure Switch Connections and Verify Pressure switch is closed Use meter 3 P1 or P2 NO YES Check probe connections potential faulty probe LA LA2 HA HA2 YES Refer to Alarm Signals in Digital Temperature Controller Programming Section Fuse Circuit Protection Nuisance Trip Is fuse opening as soon as unit turns on NO YES Check incoming power supply and connections for ...

Страница 22: ... Physical Dimensions Water overflow excessive Check drain is it plugged YES NO Clean condensate pan and drain add 1 tbsp bleach to upper pan monthly to kill mold Is Air Conditioner sealed against enclosure properly tightly sealed and door closed YES Contact Customer Service NO Ensure air tight seal between air conditioner and enclosure Make sure door is closed ...

Страница 23: ...4421 Tradition Trail Plano Texas 75093 972 964 2700 800 836 7472 URL www iscenclosurecooling com Email iscinfo iscsales com SP ENG 211 100 11 Rev 1 8 23 P a g e THIS PAGE IS INTENTIONALLY LEFT BLANK ...

Страница 24: ...P ENG 211 100 11 Rev 1 8 24 P a g e Electrical Schematics System Schematic Digital Controller Schematic Note Schematics apply to all voltages optional accessories wiring not provided in this document If you require electrical schematic with options contact our technical support and provide your model number Controller 1 3 4 5 ...

Страница 25: ...t at the ISC factory in Dallas Texas Use of equipment for other than its designed purpose or operating conditions Operation in harsh oily corrosive or other abnormal environmental conditions without the proper filtration sealing protective coatings and or weather protection or cosmetic corrosion that does not affect operation Damage to hermetic system resulting from continuous operation with dirty...

Страница 26: ...nd contact info email phone number and address Shipping method Pack unit in a suitable packing for shipment preferably the original packaging if available If suitable packing is not available arrange for packaging to be shipped to you Air Conditioners must be returned in an upright position properly secured to a pallet Tip unit to empty water from the evaporator and boil off pans Clearly mark the ...

Страница 27: ... wires to air conditioners equipped with a Wago power terminal block 1 Remove cover from chassis using T25 Torx bit 2 The sequence of the connecting the wires is from LEFT TO RIGHT 3 Connect each wire as shown by lifting the lever and inserting the wire into the receptacle directly below Snap the lever down to secure the wire in place 4 If wires need to be removed raise the lever directly above ea...

Отзывы: