4421 Tradition Trail ● Plano, Texas 75093 ● 972-964-2700 ● 800-836-7472
SP-ENG-210-100-08 Rev 3.0
8
|
P a g e
Unit Specifications
The following table provides electrical and refrigeration specifications for the DI-02A Series Air
Conditioners.
DI-02A Series
Nominal Capacity Rating: 2,000 BTUH
Standard Maximum Ambient: 131°F
Unit Weight: 120 VAC
– 44lbs, 230 VAC – 49lbs
Model
Operating
Voltage
Range
(Volts)
Inrush
Current
(Start
Up
Current)
(Amps)
Loading
Current
(Running
Current)
(Amps)
SCCR
(Short
Circuit
Current
Rating)
(Amps)
Recommended
Fuse Selection
(Amps)
KVA Rating
Refrigerant
Type
Refrigerant
Amount
(ounces)
Low/High
Unit
Pressures
(psi)
DI-02A-126
110-120
10.63
4.1
*2
7 Amp Class
CC, CCMR
Time Delay *
0.5
R134a
12.00
59 / 195
DI-02A-236
220-240
8.84
2.00
*2
4 Amp Class
CC, CCMR
Time Delay *
0.5
R134a
12.00
64 / 203
* HACR Type Circuit Breakers or Time-delay Fuses with the following electrical characteristics are
recommended. Fast-acting fuses are not recommended.
% of Ampere Rating
Opening Time
110 %
15min Minimum
125 %
1hr Maximum
200 %
12sec Minimum
4min Maximum
*2
SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel /
enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.