Bus bar(Cont.)
8
‣
If all the devices connect to one command point (bus bar) instead of connect to ground
separately, there’s no voltage difference between them.
‣
The current will not pass through the ethernet cable between devices and causing loop.
D1
D2
D3
Common Grounding
666 mV gap between 2 devices
Bus Bar
Common Grounding
Bus Bar
Содержание VIVOTEK
Страница 1: ...Surge Protection Quick Installation Guide General Cameras Aug 10 2021...
Страница 2: ...Installation Guide...
Страница 10: ...Good Installation Example...
Страница 12: ...2021 VIVOTEK Inc All rights reserved 12 Well organized within cabin...
Страница 13: ...2021 VIVOTEK Inc All rights reserved 13 All the devices are well grounded...
Страница 14: ...Bad Installation Example...
Страница 15: ...2021 VIVOTEK Inc All rights reserved 15 Case 1 PCBA burn with MTL surge protector ZB24585...
Страница 17: ...Information for Trouble Shooting...