Delta Electronics Power Output Module DVPPS01 Скачать руководство пользователя страница 2

 

3  

Function/Electrical 

Specification 

 

                                                Model   

 Item 

DVPPS01 

DVPPS02 

Power Input 

100~240 VAC (-15%~+10%), 50 / 60 Hz 

100~240 VAC (-15%~+10%), 50 / 60 Hz 

Output Power 

24VDC (±3%), output current: 1A max. 

24VDC (±3%), output current: 2A max. 

Ripple & Noise 

Under 100mV

p-p

 Typical at full load 

Under 240mV

p-p

 Typical at full load 

Efficiency 

78%~87% Typical at full load 

Over Load / Short Circuit Protection 

Auto Recovery 

Grounding 

The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N 

(All PLC units should be grounded directly to the ground pole). 

Operation/Storage Environment 

Operation: 0

~55

  (Temperature), 50~95% (Humidity), Pollution degree 2; 

 Storage: -25

~70

 (Temperature), 5~95% (Humidity) 

Agency Approvals 

Underwriters Laboratories, Inc.: UL508 Listed (Industrial Control Equipment) 

European Community EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC 

Weight (g) 

158 250 

 

4   

Installation and Wiring   

4.1 Mounting Arrangements and Wiring 

 DIN 

Rail 

Installation 

The DVPPS can be secured to a cabinet by using the DIN rail that is 35mm 
high with a depth of 7.5mm. When mounting the DVPPS on the DIN rail, be 
sure to use the end bracket to stop any side-to-side motion of the DVPPS, 
thus to reduce the chance of the wires being pulled loose. On the bottom of 
the DVPPS is a small retaining clip. To secure the DVPPS to the DIN rail, 
place it onto the rail and gently push up on the clip. To remove it, pull down 
on the retaining clip and gently pull the DVPPS away from the DIN rail. 
Please see the figure on the right:   

For heat dissipation. Make sure to 
provide a minimum clearance of 
50mm between the unit and all 
sides of the cabinet. (as shown 
below) 

DVP MPU

> 50mm

> 50mm

> 50mm

> 50mm

 

  Direct mounting: Tighten M4 screws into direct mount hole. 

 Wiring 

To suit M3.5 screw terminals

Below 6.2

Below 6.2

 

Notes: 

1.  Please use O-type or Y-type terminals for I/O wiring terminals. The specification for the terminals is 

as shown on the left. Tighten PLC terminal screws to a torque of 5~8 kg-cm (4.3~6.9 in-lbs). 

2.  Please avoid tiny metal material enter DVPPS01/PS02 when screwing and wiring. After finishing 

wire, remove the affix that pasted on the heat sink for heat dissipation.   

3.  Use Copper Conductors Only, 60

4.2 Wiring Notes 

 Environment 

1. 

DO NOT

 store the DVPPS01/PS02 in a dusty, smoky, or corrosive atmosphere.   

2. 

DO NOT

 store the DVPPS01/PS02 in an environment with high temperature or high humidity. 

3. 

DO NOT

 install PLC on a shelf or on an unstable surface.   

 Power 

Input 

Wiring 

Power input of DVPPS01/PS02 is AC input; following items should be noticed: 

1.  Connect the AC input (100VAC ~ 240VAC) to terminals L and N. Any AC110V or AC220V connected to the +24V terminal will 

permanently damage the DVPPS01/PS02.   

2.  Please use wires of 1.6mm and above for the grounding. 
3.  If the power-cut time is less than 10ms, the DVPPS01/PS02 still operates unaffectedly. If the power-cut time is too long, the 

DVPPS01/PS02 will stop operating and all the outputs will be Off.     

 

5  

Trial 

Run 

  Power indicator, Running and Test 

The “POWER” LED at the front of DVPPS01/PS02 will be lit (in green) if the power is on. If the indicator is not ON, it indicates that the 
power supply is not enough or short circuit. Please check your power wiring.   

 

6  

Troubleshooting 

 

Judge the errors by the indicators on the front panel. When errors occurred on DVPPS01/PS02, please check:   

 

POWER

LED 

The “POWER” LED at the front of the MPU will be lit (in green) if the power is on. If the indicator is not on when the MPU is powered up, 
please check if power supply is normal. If the indicator is not on when the MPU is powered up and with the input power being normal, it is 
an indication that the PLC is malfunction. Please have this machine replaced or have it repaired at a dealer near you.   